3.2 Balanced Three-Phase Power Calculations & Phasor Relationships

Key Takeaways

  • Total three-phase real, reactive, and apparent power formulas apply universally to both balanced Wye and balanced Delta topologies when expressed in terms of line-to-line voltage and line current: P_3φ = sqrt(3) * V_LL * I_line * cos(θ), Q_3φ = sqrt(3) * V_LL * I_line * sin(θ), and S_3φ = sqrt(3) * V_LL * I_line.

  • The instantaneous power delivered by a balanced three-phase source is constant over time (p(t) = P_3φ), generating uniform electromagnetic torque in rotating machinery without double-frequency power pulsations characteristic of single-phase circuits.

  • Complex power for a balanced three-phase system is S_3φ = 3 * V_LN * I_line* = sqrt(3) * V_LL * I_line ∠θ, where positive θ corresponds to an inductive load (lagging power factor, absorbing reactive power +jQ) and negative θ corresponds to a capacitive load (leading power factor, supplying reactive power -jQ).

  • Power factor correction requires adding shunt capacitance to supply reactive power: Q_cap = P_3φ * (tan(θ_initial) - tan(θ_target)); Delta-connected capacitor banks require only 1/3 the capacitance per phase (C_Delta = C_Wye / 3) compared to Wye-connected banks for the same kVAR rating.

  • In the two-wattmeter method on 3-wire systems, total three-phase active power is P_3φ = W_1 + W_2 and reactive power is Q_3φ = sqrt(3) * (W_1 - W_2); when the load power factor drops below 0.5 lagging (θ > 60°), wattmeter W_2 produces a negative reading.

Last updated: August 2026

3.2 Balanced Three-Phase Power Calculations & Phasor Relationships

Executive Overview: Quantifying real power (PP), reactive power (QQ), apparent power (SS), and complex power (S\mathbf{S}) in three-phase networks is essential for equipment sizing, feeder ampacity verification, and utility tariff compliance. A defining attribute of balanced polyphase systems is constant instantaneous power delivery, eliminating mechanical torque ripple in industrial motors. On the PE Power exam, candidates must seamlessly calculate total three-phase power using line and phase parameters, design Delta and Wye power factor correction capacitor banks, and interpret two-wattmeter instrumentation readings.


1. Instantaneous & Total Balanced Three-Phase Power Derivation

In a single-phase AC circuit, instantaneous power pulsates at twice the fundamental line frequency (2ω2\omega), creating cyclic mechanical vibration in motors. In a balanced three-phase system with line-to-neutral voltages va,vb,vcv_a, v_b, v_c and phase currents ia,ib,ici_a, i_b, i_c lagging by power factor angle θ\theta:

va(t)=2VLNcos⁡(ωt),ia(t)=2ILcos⁡(ωt−θ)v_a(t) = \sqrt{2} V_{LN} \cos(\omega t), \quad i_a(t) = \sqrt{2} I_L \cos(\omega t - \theta) vb(t)=2VLNcos⁡(ωt−120∘),ib(t)=2ILcos⁡(ωt−120∘−θ)v_b(t) = \sqrt{2} V_{LN} \cos(\omega t - 120^\circ), \quad i_b(t) = \sqrt{2} I_L \cos(\omega t - 120^\circ - \theta) vc(t)=2VLNcos⁡(ωt+120∘),ic(t)=2ILcos⁡(ωt+120∘−θ)v_c(t) = \sqrt{2} V_{LN} \cos(\omega t + 120^\circ), \quad i_c(t) = \sqrt{2} I_L \cos(\omega t + 120^\circ - \theta)

Summing the three instantaneous phase powers:

p3ϕ(t)=va(t)ia(t)+vb(t)ib(t)+vc(t)ic(t)p_{3\phi}(t) = v_a(t)i_a(t) + v_b(t)i_b(t) + v_c(t)i_c(t)

Using the trigonometric product identity cos⁡(α)cos⁡(β)=12[cos⁡(α−β)+cos⁡(α+β)]\cos(\alpha)\cos(\beta) = \frac{1}{2}[\cos(\alpha - \beta) + \cos(\alpha + \beta)], the time-varying 2ωt2\omega t terms cancel identically to zero, yielding:

p3ϕ(t)=3VLNILcos⁡θ=CONSTANTp_{3\phi}(t) = 3 V_{LN} I_L \cos\theta = \text{CONSTANT}
INSTANTANEOUS POWER COMPARISON:
Power p(t)
  ^                                     --- Single-Phase Power (Pulsates 0 to 2P at 2ω)
  |     /\        /\        /\          === Three-Phase Power (Constant P_3φ = 3*V_LN*I_L*cosθ)
  |    /  \      /  \      /  \
  |===+====+====+====+====+====+====+==== Constant 3-Phase Power Level
  |  /      \  /      \  /      \  /
  | /        \/        \/        \/
  +-------------------------------------> Time t

2. Universal Three-Phase Power Formulas

Whether a balanced load is connected in Wye or Delta, total three-phase power quantities can be formulated equivalently using either per-phase quantities (VLN,IphaseV_{LN}, I_{phase}) or terminal line quantities (VLL,IlineV_{LL}, I_{line}):

+---------------------------------------------------------------------------------------------------+
| BALANCED THREE-PHASE POWER FORMULAS (UNIVERSAL REFERENCE)                                         |
+-----------------------+-----------------------------------+---------------------------------------+
| Power Quantity        | Formulated with Phase Variables   | Formulated with Line Variables        |
+-----------------------+-----------------------------------+---------------------------------------+
| **Real Power ($P$)**  | $P_{3\phi} = 3 V_{LN} I_{ph} \cos\theta$ | $P_{3\phi} = \sqrt{3} V_{LL} I_{line} \cos\theta$ [W, kW, MW] |
| **Reactive Power ($Q$)**| $Q_{3\phi} = 3 V_{LN} I_{ph} \sin\theta$ | $Q_{3\phi} = \sqrt{3} V_{LL} I_{line} \sin\theta$ [VAR, kVAR] |
| **Apparent Power ($S$)**| $S_{3\phi} = 3 V_{LN} I_{ph}$     | $S_{3\phi} = \sqrt{3} V_{LL} I_{line} = \sqrt{P^2 + Q^2}$ [VA]|
| **Complex Power ($\mathbf{S}$)**| $\mathbf{S}_{3\phi} = 3 \mathbf{V}_{LN} \mathbf{I}_{ph}^*$ | $\mathbf{S}_{3\phi} = \sqrt{3} V_{LL} I_{line} \angle \theta = P + jQ$ [VA]|
| **Power Factor ($PF$)**| $PF = \cos\theta = \frac{P_{1\phi}}{S_{1\phi}}$ | $PF = \cos\theta = \frac{P_{3\phi}}{\sqrt{3} V_{LL} I_{line}}$ |
+-----------------------+-----------------------------------+---------------------------------------+

The Power Triangle & Sign Conventions

  • Inductive Loads (Motors, Transformers, Inductors):
    • Current lags voltage (θ>0\theta > 0).
    • Absorbs active power (P>0P > 0) and absorbs reactive power (Q>0Q > 0).
    • Complex power S=P+jQ\mathbf{S} = P + jQ.
  • Capacitive Loads (Capacitor Banks, Overexcited Synchronous Motors):
    • Current leads voltage (θ<0\theta < 0).
    • Absorbs active power (P>0P > 0) and supplies reactive power (absorbs −jQ-jQ).
    • Complex power S=P−jQ\mathbf{S} = P - jQ.
THE COMPLEX POWER TRIANGLE:
             +-----------------------------------------> Real Power P (kW)
             | \                                      |
             |  \                                     | Inductive Reactive
             |   \                                    | Power +jQ (kVAR)
             |    \ Apparent Power S (kVA)            | (Lagging PF)
             |     \                                  |
             |  θ   \                                 v
             +-------+--------------------------------+
             |      /
             |     / Capacitive Reactive
             |    /  Power -jQ (kVAR)
             |   /   (Leading PF)
             v  /

3. Phasor Diagrams for Balanced Wye & Delta Loads

Understanding the relative phase angles between voltages and currents is crucial for power flow and protection analysis.

Lagging vs. Leading Phasor Relationships (Wye Load, ABC Sequence)

  1. Lagging Power Factor (Inductive Load, θ=+36.87∘\theta = +36.87^\circ, PF=0.80PF = 0.80 lag):
    • Van=VLN∠0∘\mathbf{V}_{an} = V_{LN}\angle 0^\circ
    • Ia=IL∠−36.87∘\mathbf{I}_a = I_L \angle -36.87^\circ
    • Vab=3VLN∠+30∘\mathbf{V}_{ab} = \sqrt{3} V_{LN}\angle +30^\circ
    • Angle between line voltage Vab\mathbf{V}_{ab} and line current Ia\mathbf{I}_a: ϕ=30∘−(−36.87∘)=66.87∘\phi = 30^\circ - (-36.87^\circ) = 66.87^\circ.
  2. Leading Power Factor (Capacitive Load, θ=−36.87∘\theta = -36.87^\circ, PF=0.80PF = 0.80 lead):
    • Van=VLN∠0∘\mathbf{V}_{an} = V_{LN}\angle 0^\circ
    • Ia=IL∠+36.87∘\mathbf{I}_a = I_L \angle +36.87^\circ
    • Vab=3VLN∠+30∘\mathbf{V}_{ab} = \sqrt{3} V_{LN}\angle +30^\circ
    • Angle between line voltage Vab\mathbf{V}_{ab} and line current Ia\mathbf{I}_a: ϕ=30∘−(+36.87∘)=−6.87∘\phi = 30^\circ - (+36.87^\circ) = -6.87^\circ.

4. Power Factor Correction Engineering for Three-Phase Systems

Industrial plants primarily operate inductive loads (e.g., induction motors operating at 0.70−0.850.70 - 0.85 lagging power factor), resulting in large reactive currents that increase line losses (I2RI^2 R), reduce system voltage, and incur utility power factor financial penalties. Installing shunt capacitor banks compensates for inductive VARs locally.

POWER FACTOR CORRECTION VECTOR REDUCTION:
                      P_3φ (Constant Active Load)
     +--------------------------------------------------------->
     | \                                                      |
     |  \                                                     |
     |   \ S_initial                                          | Q_target
     |    \                                                   | (Corrected)
     |     \                        +-------------------------+
     |      \                      / |                        |
     |       \       S_target     /  |                        | Q_cap,3φ
     |        \                  /   |                        | (Injected VARs)
     |       θ1\             θ2 /    |                        |
     +----------+--------------+-----+                        v
                                     +------------------------+
                                               Q_initial (Uncorrected)

Required Capacitive Reactive Power Formulation

To improve a facility load from initial power factor PF1=cos⁡θ1PF_1 = \cos\theta_1 (lagging) to target power factor PF2=cos⁡θ2PF_2 = \cos\theta_2 (lagging) while real power P3ϕP_{3\phi} remains constant:

Qinitial=P3ϕtan⁡θ1,Qtarget=P3ϕtan⁡θ2Q_{\text{initial}} = P_{3\phi} \tan\theta_1, \quad Q_{\text{target}} = P_{3\phi} \tan\theta_2 Qcap,3ϕ=Qinitial−Qtarget=P3ϕ(tan⁡θ1−tan⁡θ2)Q_{\text{cap},3\phi} = Q_{\text{initial}} - Q_{\text{target}} = P_{3\phi} (\tan\theta_1 - \tan\theta_2)

Delta-Connected vs. Wye-Connected Capacitor Banks

Capacitors can be wired in Delta or Wye configuration. Evaluating the required capacitance per phase (CC in Farads or μF\mu\text{F}) reveals a critical engineering trade-off:

DELTA-CONNECTED CAPACITOR BANK:             WYE-CONNECTED CAPACITOR BANK:
       Line A o-----+--------+                     Line A o-----+ 
                    |        |                                  |
                   --- C_Δ  --- C_Δ                            --- C_Y
                   ---      ---                                --- 
                    |        |                                  |
       Line B o-----+        |                     Line B o-----+--- N (Neutral)
                             |                                  |
                            --- C_Δ                            --- C_Y
                            ---                                --- 
                             |                                  |
       Line C o--------------+                     Line C o-----+ 
                                                                |
                                                               --- C_Y
                                                               --- 
                                                                |
                                                               ===
Design ParameterDelta-Connected Bank (Δ\Delta)Wye-Connected Bank (Y\text{Y})
Voltage across each capacitorVC=VLLV_C = V_{LL}VC=VLN=VLL3V_C = V_{LN} = \frac{V_{LL}}{\sqrt{3}}
Reactive power per phase (Q1ϕQ_{1\phi})Q1ϕ=ωCΔVLL2=Qcap,3ϕ3Q_{1\phi} = \omega C_\Delta V_{LL}^2 = \frac{Q_{\text{cap},3\phi}}{3}Q1ϕ=ωCYVLN2=ωCY(VLL3)2=ωCYVLL23Q_{1\phi} = \omega C_Y V_{LN}^2 = \omega C_Y \left(\frac{V_{LL}}{\sqrt{3}}\right)^2 = \frac{\omega C_Y V_{LL}^2}{3}
Required Capacitance per phase (CC)CΔ=Qcap,3ϕ3ωVLL2C_\Delta = \frac{Q_{\text{cap},3\phi}}{3 \omega V_{LL}^2}CY=Qcap,3ϕωVLL2C_Y = \frac{Q_{\text{cap},3\phi}}{\omega V_{LL}^2}
Capacitance Comparison RatioCΔ=CY3C_\Delta = \frac{C_Y}{3}CY=3CΔC_Y = 3 C_\Delta
Capacitor Voltage Rating RequiredRated for full line-to-line voltage VLLV_{LL}Rated for line-to-neutral voltage VLNV_{LN}

Exam Key Fact: A Delta-connected capacitor bank requires only 1/31/3 the capacitance (in μF\mu\text{F}) compared to a Wye-connected bank for the exact same total three-phase kVAR compensation. Because commercial capacitor cost scales with μF\mu\text{F} dielectric volume, Delta banks are universally preferred in low- and medium-voltage distribution systems.


5. The Two-Wattmeter Method for Three-Phase Power Measurement

In any three-wire system (balanced or unbalanced, Wye or Delta, with no neutral conductor), total three-phase power can be measured using two single-phase wattmeters (Blondel's Theorem: N−1N-1 wattmeters suffice for an NN-wire system).

TWO-WATTMETER (ARON) CONNECTION SCHEMATIC:
          Line A       [ ± Current Coil W1 ]
   o------------------+---( I_a )---+-------------------------> Load
                      |             |
                      |            [+] Voltage Coil W1 (V_ab)
                      |             |
          Line B      |             +--------+
   o------------------+----------------------|----------------> Load
                      |                      |
                      |            [+] Voltage Coil W2 (V_cb)
                      |             |
          Line C      |             +--------+
   o------------------+---( I_c )---+-------------------------> Load
                       [ ± Current Coil W2 ]

Mathematical Formulation for Balanced Positive (ABC) Sequence

With wattmeter 1 measuring current Ia\mathbf{I}_a and voltage Vab\mathbf{V}_{ab}, and wattmeter 2 measuring current Ic\mathbf{I}_c and voltage Vcb\mathbf{V}_{cb}:

W1=∣Vab∣∣Ia∣cos⁡(∠Vab−∠Ia)=VLLILcos⁡(30∘−θ)W_1 = |\mathbf{V}_{ab}| |\mathbf{I}_a| \cos(\angle\mathbf{V}_{ab} - \angle\mathbf{I}_a) = V_{LL} I_L \cos(30^\circ - \theta) W2=∣Vcb∣∣Ic∣cos⁡(∠Vcb−∠Ic)=VLLILcos⁡(30∘+θ)W_2 = |\mathbf{V}_{cb}| |\mathbf{I}_c| \cos(\angle\mathbf{V}_{cb} - \angle\mathbf{I}_c) = V_{LL} I_L \cos(30^\circ + \theta)

Summing and subtracting the two meter readings:

P3ϕ=W1+W2=VLLIL[cos⁡(30∘−θ)+cos⁡(30∘+θ)]=3VLLILcos⁡θP_{3\phi} = W_1 + W_2 = V_{LL} I_L [\cos(30^\circ - \theta) + \cos(30^\circ + \theta)] = \sqrt{3} V_{LL} I_L \cos\theta W1−W2=VLLIL[cos⁡(30∘−θ)−cos⁡(30∘+θ)]=VLLIL[2sin⁡30∘sin⁡θ]=VLLILsin⁡θW_1 - W_2 = V_{LL} I_L [\cos(30^\circ - \theta) - \cos(30^\circ + \theta)] = V_{LL} I_L [2 \sin 30^\circ \sin\theta] = V_{LL} I_L \sin\theta Q3ϕ=3(W1−W2)Q_{3\phi} = \sqrt{3}(W_1 - W_2) tan⁡θ=3W1−W2W1+W2  ⟹  θ=arctan⁡(3W1−W2W1+W2)\tan\theta = \sqrt{3} \frac{W_1 - W_2}{W_1 + W_2} \implies \theta = \arctan\left(\sqrt{3} \frac{W_1 - W_2}{W_1 + W_2}\right)

Wattmeter Reading Interpretation Across Power Factors

Load Power Factor (PFPF)Power Factor Angle (θ\theta)Wattmeter 1 (W1W_1)Wattmeter 2 (W2W_2)Diagnostic Significance
PF=1.0PF = 1.0 (Unity)θ=0∘\theta = 0^\circW1=32VLLILW_1 = \frac{\sqrt{3}}{2} V_{LL} I_LW2=32VLLILW_2 = \frac{\sqrt{3}}{2} V_{LL} I_LW1=W2>0W_1 = W_2 > 0 (Identical positive readings)
PF=0.866PF = 0.866 Laggingθ=+30∘\theta = +30^\circW1=VLLILW_1 = V_{LL} I_LW2=0.5VLLILW_2 = 0.5 V_{LL} I_LW1=2W2W_1 = 2 W_2 (W1W_1 reads twice W2W_2)
PF=0.500PF = 0.500 Laggingθ=+60∘\theta = +60^\circW1=32VLLILW_1 = \frac{\sqrt{3}}{2} V_{LL} I_LW2=0W_2 = 0W2W_2 reads exactly zero
PF<0.500PF < 0.500 Laggingθ>+60∘\theta > +60^\circW1>0W_1 > 0W2<0W_2 < 0 (Negative)W2W_2 deflects backwards (reverse voltage coil leads to read magnitude)
PF=0.0PF = 0.0 (Pure Inductive)θ=+90∘\theta = +90^\circW1=0.5VLLILW_1 = 0.5 V_{LL} I_LW2=−0.5VLLILW_2 = -0.5 V_{LL} I_LW1=−W2  ⟹  W1+W2=0W_1 = -W_2 \implies W_1 + W_2 = 0 (P3ϕ=0P_{3\phi} = 0)

6. Comprehensive Step-by-Step Worked Mathematical Example

Problem Scenario

An industrial manufacturing facility is supplied by a 480 V480\text{ V} (line-to-line RMS), three-phase, 60 Hz60\text{ Hz} utility service. The total plant load consists of:

  • Load 1 (Induction Motors): Consumes 300 kW300\text{ kW} at 0.750.75 power factor lagging.
  • Load 2 (Lighting & Resistance Heaters): Consumes 60 kW60\text{ kW} at 1.01.0 power factor.
  • Load 3 (Synchronous Machine): Absorbs 80 kVA80\text{ kVA} at 0.800.80 power factor leading.

Determine:

  1. The uncorrected total plant active power (PtotalP_{total}), reactive power (QtotalQ_{total}), apparent power (StotalS_{total}), power factor (PFuncorrPF_{uncorr}), and total line current (Iline,uncorrI_{line,uncorr}).
  2. The total three-phase kVAR rating (Qcap,3ϕQ_{\text{cap},3\phi}) of a shunt capacitor bank required to correct the facility to an overall power factor of 0.960.96 lagging.
  3. The required capacitance per phase in microfarads (μF\mu\text{F}) if the capacitor bank is connected in Delta.
  4. The corrected total line current drawn from the utility (Iline,corrI_{line,corr}).
=========================================================================================
CALCULATION WORKFLOW & DETAILED STEP-BY-STEP SOLUTION:
=========================================================================================

Step 1: Compute Individual Load Powers
  Load 1 (Induction Motors - Lagging PF):
    P_1 = 300.0 kW
    theta_1 = +arccos(0.75) = +41.4096°
    Q_1 = P_1 * tan(theta_1) = 300.0 * tan(41.4096°) = 300.0 * 0.88192 = +264.575 kVAR
    S_1 = P_1 / PF_1 = 300.0 / 0.75 = 400.0 kVA

  Load 2 (Lighting & Heaters - Unity PF):
    P_2 = 60.0 kW
    Q_2 = 0.0 kVAR
    S_2 = 60.0 kVA

  Load 3 (Synchronous Machine - Leading PF):
    S_3 = 80.0 kVA
    theta_3 = -arccos(0.80) = -36.8699°
    P_3 = S_3 * cos(theta_3) = 80.0 * 0.80 = 64.0 kW
    Q_3 = S_3 * sin(theta_3) = 80.0 * (-0.60) = -48.0 kVAR  (Supplying VARs)

Step 2: Aggregate Total Plant Uncorrected Power
  P_total = P_1 + P_2 + P_3
          = 300.0 + 60.0 + 64.0 = 424.0 kW

  Q_total = Q_1 + Q_2 + Q_3
          = +264.575 + 0.0 + (-48.0) = +216.575 kVAR (Lagging)

  S_total = sqrt( P_total^2 + Q_total^2 )
          = sqrt( 424.0^2 + 216.575^2 )
          = sqrt( 179776.0 + 46904.73 )
          = sqrt( 226680.73 )
          = 476.11 kVA

  Uncorrected Power Factor:
    PF_uncorr = P_total / S_total = 424.0 / 476.11 = 0.8905 lagging (theta_initial = 27.06°)

  Uncorrected Line Current:
    I_line,uncorr = S_total / (sqrt(3) * V_LL)
                  = 476,110 / (1.73205 * 480)
                  = 476,110 / 831.384
                  = 572.67 A

Step 3: Size Power Factor Correction Capacitor Bank
  Target power factor: PF_target = 0.96 lagging
    theta_target = arccos(0.96) = 16.2602°
    tan(theta_target) = tan(16.2602°) = 0.29167

  Target net reactive power:
    Q_target = P_total * tan(theta_target)
             = 424.0 * 0.29167
             = 123.667 kVAR

  Required Capacitor Bank 3-Phase Rating:
    Q_cap,3ph = Q_total - Q_target
              = 216.575 - 123.667
              = 92.908 kVAR ≈ 92.91 kVAR

Step 4: Calculate Required Delta Capacitance per Phase
  Operating frequency: f = 60 Hz => omega = 2 * pi * 60 = 376.991 rad/s
  Capacitor voltage in Delta = V_LL = 480 V

  Capacitance formula for Delta bank:
    C_Delta = Q_cap,3ph / (3 * omega * V_LL^2)
            = (92.908 * 10^3) / (3 * 376.991 * 480^2)
            = 92,908 / (1130.973 * 230,400)
            = 92,908 / 260,576,256
            = 3.5655 * 10^-4 Farads
            = 356.55 μF per phase

Step 5: Compute Corrected System Parameters
  Corrected Apparent Power:
    S_corr = P_total / PF_target = 424.0 / 0.96 = 441.67 kVA

  Corrected Line Current:
    I_line,corr = S_corr / (sqrt(3) * V_LL)
                = 441,667 / (1.73205 * 480)
                = 441,667 / 831.384
                = 531.24 A

  Net Line Current Reduction: Delta_I = 572.67 - 531.24 = 41.43 A (7.23% reduction in cable loading)
=========================================================================================

7. Common Exam Traps & Tactical Pitfalls

  • Direct Algebraic Summation of Apparent Powers: Adding kVA values directly (Stotal=S1+S2+S3S_{total} = S_1 + S_2 + S_3). This is mathematically invalid because apparent power is a phasor magnitude. Always decompose loads into orthogonal active (PP) and reactive (QQ) components, sum PP and QQ independently, and compute Stotal=Ptotal2+Qtotal2S_{total} = \sqrt{P_{total}^2 + Q_{total}^2}.
  • Leading Power Factor Sign Error: Treating leading power factor loads as +jQ+jQ instead of −jQ-jQ. Overexcited synchronous machines and capacitor banks supply reactive power, subtracting from the plant's inductive VAR demand.
  • Capacitor Sizing Voltage Confusion: Using line-to-neutral voltage (277 V277\text{ V}) instead of line-to-line voltage (480 V480\text{ V}) when sizing Delta-connected capacitors. In Delta, each capacitor experiences the full line-to-line voltage.
  • Two-Wattmeter Negative Power Misinterpretation: Neglecting the minus sign on wattmeter W2W_2 when PF<0.50PF < 0.50 lagging. If W1=12 kWW_1 = 12\text{ kW} and W2=−4 kWW_2 = -4\text{ kW}, the total real power is P3ϕ=12+(−4)=8 kWP_{3\phi} = 12 + (-4) = 8\text{ kW}, NOT 12+4=16 kW12 + 4 = 16\text{ kW}.
Loading diagram...
Power Triangle and Three-Phase Power Factor Correction Architecture
Test Your Knowledge

A balanced three-phase 480 V feeder supplies an induction motor load drawing 150 kW at 0.80 power factor lagging. What is the total apparent power S_3φ and the magnitude of the feeder line current I_line?

A

S_3φ = 150.0 kVA and I_line = 180.4 A

B

S_3φ = 187.5 kVA and I_line = 390.6 A

C

S_3φ = 120.0 kVA and I_line = 144.3 A

D

S_3φ = 187.5 kVA and I_line = 225.5 A

Test Your Knowledge

A 3-phase, 480 V (line-to-line), 60 Hz facility requires 120 kVAR of capacitive reactive power to correct its power factor. If the capacitor bank is configured in Delta, what is the required capacitance per phase in microfarads?

A

460.5 μF

B

1381.5 μF

C

153.5 μF

D

795.8 μF

Test Your Knowledge

Two wattmeters are connected to measure the total power consumed by a balanced 3-phase, 3-wire inductive load using the two-wattmeter method. Wattmeter 1 reads W_1 = 15.0 kW and Wattmeter 2 reads W_2 = 5.0 kW. What are the total active power P_3φ and the power factor of the load?

A

P_3φ = 10.0 kW and PF = 0.500 lagging

B

P_3φ = 20.0 kW and PF = 0.756 lagging

C

P_3φ = 20.0 kW and PF = 0.866 lagging

D

P_3φ = 25.0 kW and PF = 0.920 lagging

Sections you finish are checked off in the contents.