3.3 The Per-Unit (pu) System: Bases, Conversions & System Modeling
Key Takeaways
The per-unit system normalizes electrical quantities as dimensionless ratios: Value_pu = Actual_Value (in physical units) / Base_Value (in same physical units); selecting any two independent base quantities (typically S_base,3φ and V_base,LL) uniquely fixes all other system bases.
Derived three-phase base impedance is Z_base = (V_base,LL)^2 / S_base,3φ = (V_base,LN)^2 / S_base,1φ; when V_base is in kV and S_base is in MVA, Z_base = (V_base,kV)^2 / S_base,MVA in ohms.
Impedance base conversions across differing power or voltage bases follow the master scaling law: Z_pu,new = Z_pu,old * (S_base,new / S_base,old) * (V_base,old / V_base,new)^2.
In multi-voltage networks, base voltages in different zones are strictly dictated by transformer nominal turns ratios; an ideal transformer represented in per-unit has a 1:1 turns ratio, eliminating off-nominal voltage ideal couplings from network equations.
Converting a power system one-line diagram to a per-unit reactance diagram establishes a single unified per-phase impedance network, allowing direct application of Thevenin, nodal admittance, and short-circuit fault equations without explicit turns-ratio impedance scaling.
3.3 The Per-Unit (pu) System: Bases, Conversions & System Modeling
Executive Overview: Power systems encompass vast networks spanning multiple voltage levels—from generator terminals () to bulk transmission () down to industrial distribution (). Analyzing such systems in physical ohms requires continually reflecting impedances across transformer turns ratios (). The Per-Unit (pu) System normalizes all voltages, currents, powers, and impedances to dimensionless ratios, eliminating ideal transformers and condensing equipment parameters into predictable, standardized ranges. Mastery of per-unit base transformations is among the highest-yield competencies on the NCEES PE Power examination.
1. Core Principles & Advantages of the Per-Unit System
The per-unit value of any electrical quantity is defined as:
+---------------------------------------------------------------------------------------------------+
| KEY ENGINEERING ADVANTAGES OF THE PER-UNIT SYSTEM |
+---------------------------------------------------------------------------------------------------+
| 1. Eliminates Ideal Transformers: Transformer turns ratios become 1:1 in per-unit, reducing |
| multi-voltage networks to simple connected impedance diagrams without turns-ratio scaling. |
| 2. Standardized Parameter Ranges: Equivalent impedances of similar apparatus fall within narrow |
| numerical bands (e.g., power transformers typically have X_leakage = 0.06 - 0.12 pu), making |
| erroneous data immediately detectable. |
| 3. Equal High-Side and Low-Side pu Impedance: A transformer's per-unit impedance is identical |
| whether calculated from the primary or secondary winding terminals. |
| 4. Intuitive Voltage Profiles: Operating voltages near nominal are close to 1.00 pu (e.g., |
| 0.95 pu indicates a 5% undervoltage; 1.05 pu indicates a 5% overvoltage). |
+---------------------------------------------------------------------------------------------------+
2. Selection & Derivation of System Base Quantities
A three-phase electrical network is defined by four fundamental interrelated variables: Apparent Power (), Voltage (), Current (), and Impedance (). In standard practice, two independent base quantities are arbitrarily selected, which mathematically dictate the remaining two derived bases.
Standard Base Selection Protocol
- System Three-Phase Apparent Power Base ():
Chosen globally for the entire study (standard utility convention is or ; industrial studies often select or ).
- Single-phase power base: .
- System Line-to-Line Voltage Base ():
Selected for one reference voltage zone, and then propagated across each transformer according to its rated voltage ratio.
- Line-to-neutral voltage base: .
Derivation of Derived Base Current ()
Derivation of Derived Base Impedance ()
When line-to-line base voltage is expressed in kilovolts () and three-phase base power in megavolt-amperes ():
Derivation of Derived Base Admittance ()
+---------------------------------------------------------------------------------------------------+
| PER-UNIT SYSTEM FUNDAMENTAL BASE EQUATIONS (PE FORMULA MATRIX) |
+---------------------------------------------------------------------------------------------------+
| Base Current: | I_base = S_base,3φ / (sqrt(3) * V_base,LL) [A] |
| Base Impedance: | Z_base = (V_base,LL_kV)^2 / S_base,3φ_MVA [Ω] |
| Physical Ohms: | Z_pu = Z_actual_ohms / Z_base = Z_actual_ohms * (S_base,MVA / V_base,kV^2) |
| Actual Current: | I_actual = I_pu * I_base [A] |
| Actual Voltage: | V_actual = V_pu * V_base [V] |
+---------------------------------------------------------------------------------------------------+
3. Changing Per-Unit Impedance Bases (The Master Scaling Law)
Manufacturer nameplates state equipment impedance in per-unit on the equipment's own nominal ratings ( and ). Before assembling a system-wide reactance network on a common system base ( and ), every per-unit impedance must be rescaled using the Master Base Conversion Formula:
Analytical Derivation
- Convert the old per-unit impedance to physical ohms ():
- Convert physical ohms to the new per-unit base:
Exam Warning on Voltage Squaring: In the base conversion formula, power scales linearly (), whereas voltage scales with the square of the inverse ratio (). Omitting the square exponent is one of the most common calculation mistakes on the PE Power exam!
4. Multi-Voltage Zone Power System Partitioning
In a multi-voltage power network, transformers establish distinct voltage zones. Once a base voltage is chosen for any one zone, the base voltages for all other zones are strictly locked by the nominal rated turns ratios of the intervening transformers.
MULTI-ZONE VOLTAGE PARTITIONING:
[Zone 1: Generation] [Zone 2: Transmission] [Zone 3: Distribution]
V_base1 = 13.8 kV V_base2 = 138 kV V_base3 = 4.16 kV
+---------------------+ +---------------------+ +---------------------+
| (~) Generator | T1 | Transmission | T2 | Motor Load |
| 13.8 kV Nominal |==#==| Line |==#==| 4.16 kV Nominal |
+---------------------+ +---------------------+ +---------------------+
T1 Ratio: T2 Ratio:
13.8 kV / 138 kV 138 kV / 4.16 kV
Step-by-Step Zone Propagation Rules
- Set in Zone 1 (e.g., ).
- Across Transformer (ratio ):
- Across Transformer (ratio ):
- Off-Nominal Transformer Voltage Ratings: If a motor or generator operates at a nominal nameplate voltage that differs from the zone base voltage (e.g., a motor installed in a zone), the voltage correction term must be included in that equipment's base transformation.
5. One-Line Diagram to Per-Unit Reactance Diagram Conversion
To perform fault analysis or load flow on a power system, the physical one-line diagram is systematically transformed into a single-phase per-unit reactance network:
PHYSICAL ONE-LINE DIAGRAM:
[Gen G1]----(Bus 1)====[Trans T1]====(Bus 2)----[Trans Line]----(Bus 3)====[Trans T2]====(Bus 4)----[Motor M1]
PER-UNIT REACTANCE DIAGRAM (ALL VALUES ON COMMON 100 MVA BASE):
jX_G1 jX_T1 Z_line,pu jX_T2 jX_M1
+-[ZZZZ]- Bus 1 -[ZZZZ]- Bus 2 --[ZZZZZZZZ]-- Bus 3 -[ZZZZ]- Bus 4 -[ZZZZ]-+
| |
(+)[E_G1] (+)[E_M1]
| |
=== Reference Bus (Ground Neutral) ==========================================
Systematic 5-Step Network Modeling Algorithm
- Select Global System Bases: Establish a common three-phase power base (e.g., ) and a voltage base for one designated zone.
- Determine Base Voltages for All Zones: Calculate for each zone using transformer nominal turns ratios.
- Compute Base Impedances () and Base Currents (): Determine for every zone.
- Convert All Component Impedances to System Base:
- Generators & Motors: Rescale per-unit subtransient reactances via the Master Base Conversion Formula.
- Transformers: Rescale per-unit leakage reactances .
- Transmission Lines & Cables: Convert physical series ohms () to per-unit: .
- Assemble the Reactance Diagram & Solve: Combine all per-unit impedances into a single interconnected network. Solve for per-unit fault currents or bus voltages, then multiply by zone base quantities to recover actual physical values.
6. Comprehensive Step-by-Step Worked System Example
Problem Statement
A balanced three-phase power system has the following equipment specifications:
- Generator : , , subtransient reactance .
- Step-Up Transformer : , , leakage reactance .
- Transmission Line: in length, series impedance , operating at .
- Step-Down Transformer : , , leakage reactance .
- Motor : , , subtransient reactance .
System Base Specifications: Select a common system power base of and a generator zone voltage base of .
Calculate:
- The voltage base () and base impedance () in all three zones.
- The per-unit impedance of each system component on the common base.
- The total series Thevenin impedance between the internal generator EMF and motor EMF.
- The symmetrical three-phase short-circuit current in Amperes at the motor bus (Bus 4) for a solid three-phase fault, assuming a prefault voltage of and neglecting prefault load current and line resistance.
=========================================================================================
CALCULATION WORKFLOW & DETAILED STEP-BY-STEP SOLUTION:
=========================================================================================
Step 1: Determine Voltage and Impedance Bases for All Zones
System Power Base: S_base,3ph = 100 MVA
Zone 1 (Generator Zone):
V_base1 = 13.8 kV
Z_base1 = (V_base1)^2 / S_base = (13.8)^2 / 100 = 190.44 / 100 = 1.9044 ohms
I_base1 = S_base / (sqrt(3) * V_base1) = 100,000 / (1.73205 * 13.8) = 4,183.7 A
Zone 2 (Transmission Line Zone):
V_base2 = V_base1 * (115 / 13.8) = 13.8 * (115 / 13.8) = 115.0 kV
Z_base2 = (V_base2)^2 / S_base = (115.0)^2 / 100 = 13225.0 / 100 = 132.25 ohms
I_base2 = S_base / (sqrt(3) * V_base2) = 100,000 / (1.73205 * 115.0) = 502.04 A
Zone 3 (Motor Zone):
V_base3 = V_base2 * (13.8 / 115.0) = 115.0 * (13.8 / 115.0) = 13.8 kV
Z_base3 = (V_base3)^2 / S_base = (13.8)^2 / 100 = 1.9044 ohms
I_base3 = S_base / (sqrt(3) * V_base3) = 4,183.7 A
Step 2: Convert Component Impedances to Common 100 MVA Base
1. Generator G1 (50 MVA, 13.8 kV, X" = 0.15 pu):
X_G1,new = X_G1,old * (S_base,new / S_base,old) * (V_base,old / V_base,new)^2
= 0.15 * (100 / 50) * (13.8 / 13.8)^2
= 0.15 * 2.0 * 1.0
= 0.3000 pu
2. Step-Up Transformer T1 (60 MVA, 13.8/115 kV, X = 0.10 pu):
X_T1,new = 0.10 * (100 / 60) * (115 / 115)^2
= 0.10 * 1.6667 * 1.0
= 0.1667 pu
3. Transmission Line (20 miles * (0.15 + j0.80 ohms/mi) = 3.0 + j16.0 ohms):
Z_line,pu = Z_actual / Z_base2
= (3.0 + j16.0) / 132.25
= (3.0 / 132.25) + j(16.0 / 132.25)
= 0.02268 + j0.12098 pu
4. Step-Down Transformer T2 (40 MVA, 115/13.8 kV, X = 0.08 pu):
X_T2,new = 0.08 * (100 / 40) * (115 / 115)^2
= 0.08 * 2.50 * 1.0
= 0.2000 pu
5. Motor M1 (30 MVA, 13.2 kV, X" = 0.20 pu):
Notice: Motor nominal voltage (13.2 kV) differs from Zone 3 base voltage (13.8 kV)!
X_M1,new = X_M1,old * (S_base,new / S_base,old) * (V_base,old / V_base,new)^2
= 0.20 * (100 / 30) * (13.2 / 13.8)^2
= 0.20 * 3.3333 * (0.95652)^2
= 0.66667 * 0.91493
= 0.60995 pu ≈ 0.6100 pu
Step 3: Total Series Impedance Calculation (Generator to Motor)
Z_series = jX_G1 + jX_T1 + Z_line + jX_T2 + jX_M1
= j0.3000 + j0.1667 + (0.0227 + j0.1210) + j0.2000 + j0.6100
= 0.0227 + j(0.3000 + 0.1667 + 0.1210 + 0.2000 + 0.6100)
= 0.0227 + j1.3977 pu
Step 4: Symmetrical Short-Circuit Fault Current Calculation at Motor Bus (Bus 4)
For a solid 3-phase fault at Bus 4 (upstream Thevenin reactance excluding motor):
X_th,upstream = X_G1 + X_T1 + X_line + X_T2
= 0.3000 + 0.1667 + 0.1210 + 0.2000
= 0.7877 pu
Per-unit fault current contributed from utility/generator source:
I_f,pu = V_f / X_th,upstream
= 1.0 / 0.7877
= 1.2695 pu
Convert per-unit fault current to actual Amperes in Zone 3:
I_f,actual = I_f,pu * I_base3
= 1.2695 * 4,183.7 A
= 5,311.2 A = 5.311 kA
=========================================================================================
7. Common Exam Traps & Tactical Pitfalls
- Omitting the Square on the Voltage Conversion Ratio: Using instead of . Because impedance is proportional to voltage squared (), the voltage adjustment ratio must always be squared.
- Inverting the Voltage Ratio: Multiplying by instead of . An apparatus with a lower rated voltage operating in a higher base voltage zone will have a smaller per-unit impedance on the new base.
- Single-Phase vs. Three-Phase Base Power Mismatch: Using single-phase MVA in with line-to-line voltage. Remember: . Mixing with causes a factor of 3 error!
- Neglecting Off-Nominal Equipment Nameplates: Assuming equipment rated voltage always matches the zone base voltage. Always check the motor and transformer nameplates against the zone base.
A 3-phase, 13.8 kV, 25 MVA synchronous generator has a subtransient reactance of X_d'' = 0.18 pu based on its own nameplate rating. What is the generator's subtransient reactance expressed on a system base of 100 MVA and 13.2 kV?
0.658 pu
0.720 pu
0.787 pu
0.041 pu
In a 3-phase power system, Zone 2 represents a 230 kV transmission line section modeled on a 100 MVA base. What is the base impedance Z_base of Zone 2, and what is the per-unit impedance of a transmission line with an actual physical impedance of 10.58 + j52.90 ohms?
Z_base = 529.0 ohms and Z_pu = 0.050 + j0.250 pu
Z_base = 230.0 ohms and Z_pu = 0.046 + j0.230 pu
Z_base = 100.0 ohms and Z_pu = 0.106 + j0.529 pu
Z_base = 529.0 ohms and Z_pu = 0.020 + j0.100 pu
A 3-phase, 500 kVA, 480 V load draws 0.85 pu current at 0.80 power factor lagging from a 480 V system modeled on a 1.0 MVA, 480 V base. What is the actual physical line current drawn by the load in Amperes?
1022.4 A
511.2 A
1202.8 A
601.4 A
Sections you finish are checked off in the contents.