3.3 The Per-Unit (pu) System: Bases, Conversions & System Modeling

Key Takeaways

  • The per-unit system normalizes electrical quantities as dimensionless ratios: Value_pu = Actual_Value (in physical units) / Base_Value (in same physical units); selecting any two independent base quantities (typically S_base,3φ and V_base,LL) uniquely fixes all other system bases.

  • Derived three-phase base impedance is Z_base = (V_base,LL)^2 / S_base,3φ = (V_base,LN)^2 / S_base,1φ; when V_base is in kV and S_base is in MVA, Z_base = (V_base,kV)^2 / S_base,MVA in ohms.

  • Impedance base conversions across differing power or voltage bases follow the master scaling law: Z_pu,new = Z_pu,old * (S_base,new / S_base,old) * (V_base,old / V_base,new)^2.

  • In multi-voltage networks, base voltages in different zones are strictly dictated by transformer nominal turns ratios; an ideal transformer represented in per-unit has a 1:1 turns ratio, eliminating off-nominal voltage ideal couplings from network equations.

  • Converting a power system one-line diagram to a per-unit reactance diagram establishes a single unified per-phase impedance network, allowing direct application of Thevenin, nodal admittance, and short-circuit fault equations without explicit turns-ratio impedance scaling.

Last updated: August 2026

3.3 The Per-Unit (pu) System: Bases, Conversions & System Modeling

Executive Overview: Power systems encompass vast networks spanning multiple voltage levels—from generator terminals (13.8 kV13.8\text{ kV}) to bulk transmission (115 kV−765 kV115\text{ kV} - 765\text{ kV}) down to industrial distribution (480 V−13.8 kV480\text{ V} - 13.8\text{ kV}). Analyzing such systems in physical ohms requires continually reflecting impedances across transformer turns ratios (a2a^2). The Per-Unit (pu) System normalizes all voltages, currents, powers, and impedances to dimensionless ratios, eliminating ideal transformers and condensing equipment parameters into predictable, standardized ranges. Mastery of per-unit base transformations is among the highest-yield competencies on the NCEES PE Power examination.


1. Core Principles & Advantages of the Per-Unit System

The per-unit value of any electrical quantity is defined as:

Quantitypu=Actual Quantity (in physical engineering units)Base Value of Quantity (in identical physical units)\text{Quantity}_{\text{pu}} = \frac{\text{Actual Quantity (in physical engineering units)}}{\text{Base Value of Quantity (in identical physical units)}} Quantity%=Quantitypu×100%\text{Quantity}_{\%} = \text{Quantity}_{\text{pu}} \times 100\%
+---------------------------------------------------------------------------------------------------+
| KEY ENGINEERING ADVANTAGES OF THE PER-UNIT SYSTEM                                                 |
+---------------------------------------------------------------------------------------------------+
| 1. Eliminates Ideal Transformers: Transformer turns ratios become 1:1 in per-unit, reducing       |
|    multi-voltage networks to simple connected impedance diagrams without turns-ratio scaling.     |
| 2. Standardized Parameter Ranges: Equivalent impedances of similar apparatus fall within narrow   |
|    numerical bands (e.g., power transformers typically have X_leakage = 0.06 - 0.12 pu), making   |
|    erroneous data immediately detectable.                                                         |
| 3. Equal High-Side and Low-Side pu Impedance: A transformer's per-unit impedance is identical     |
|    whether calculated from the primary or secondary winding terminals.                            |
| 4. Intuitive Voltage Profiles: Operating voltages near nominal are close to 1.00 pu (e.g.,         |
|    0.95 pu indicates a 5% undervoltage; 1.05 pu indicates a 5% overvoltage).                      |
+---------------------------------------------------------------------------------------------------+

2. Selection & Derivation of System Base Quantities

A three-phase electrical network is defined by four fundamental interrelated variables: Apparent Power (SS), Voltage (VV), Current (II), and Impedance (ZZ). In standard practice, two independent base quantities are arbitrarily selected, which mathematically dictate the remaining two derived bases.

Standard Base Selection Protocol

  1. System Three-Phase Apparent Power Base (Sbase,3ϕS_{\text{base},3\phi}): Chosen globally for the entire study (standard utility convention is 100 MVA100\text{ MVA} or 10 MVA10\text{ MVA}; industrial studies often select 10 MVA10\text{ MVA} or 1 MVA1\text{ MVA}).
    • Single-phase power base: Sbase,1ϕ=Sbase,3ϕ3S_{\text{base},1\phi} = \frac{S_{\text{base},3\phi}}{3}.
  2. System Line-to-Line Voltage Base (Vbase,LLV_{\text{base},LL}): Selected for one reference voltage zone, and then propagated across each transformer according to its rated voltage ratio.
    • Line-to-neutral voltage base: Vbase,LN=Vbase,LL3V_{\text{base},LN} = \frac{V_{\text{base},LL}}{\sqrt{3}}.

Derivation of Derived Base Current (IbaseI_{\text{base}})

Ibase=Sbase,3ϕ3Vbase,LL=Sbase,1ϕVbase,LN[Amperes]I_{\text{base}} = \frac{S_{\text{base},3\phi}}{\sqrt{3} V_{\text{base},LL}} = \frac{S_{\text{base},1\phi}}{V_{\text{base},LN}} \quad [\text{Amperes}]

Derivation of Derived Base Impedance (ZbaseZ_{\text{base}})

Zbase=Vbase,LNIbase=Vbase,LL/3Sbase,3ϕ/(3Vbase,LL)=(Vbase,LL)2Sbase,3ϕ[Ω]Z_{\text{base}} = \frac{V_{\text{base},LN}}{I_{\text{base}}} = \frac{V_{\text{base},LL} / \sqrt{3}}{S_{\text{base},3\phi} / (\sqrt{3} V_{\text{base},LL})} = \frac{(V_{\text{base},LL})^2}{S_{\text{base},3\phi}} \quad [\Omega]

When line-to-line base voltage is expressed in kilovolts (Vbase,kVV_{\text{base},\text{kV}}) and three-phase base power in megavolt-amperes (Sbase,MVAS_{\text{base},\text{MVA}}):

Zbase=(Vbase,kV×103)2Sbase,MVA×106=(Vbase,kV)2Sbase,MVA[Ω]Z_{\text{base}} = \frac{(V_{\text{base},\text{kV}} \times 10^3)^2}{S_{\text{base},\text{MVA}} \times 10^6} = \frac{(V_{\text{base},\text{kV}})^2}{S_{\text{base},\text{MVA}}} \quad [\Omega]

Derivation of Derived Base Admittance (YbaseY_{\text{base}})

Ybase=1Zbase=Sbase,MVA(Vbase,kV)2[Siemens]Y_{\text{base}} = \frac{1}{Z_{\text{base}}} = \frac{S_{\text{base},\text{MVA}}}{(V_{\text{base},\text{kV}})^2} \quad [\text{Siemens}]
+---------------------------------------------------------------------------------------------------+
| PER-UNIT SYSTEM FUNDAMENTAL BASE EQUATIONS (PE FORMULA MATRIX)                                    |
+---------------------------------------------------------------------------------------------------+
| Base Current:    |  I_base = S_base,3φ / (sqrt(3) * V_base,LL)  [A]                              |
| Base Impedance:  |  Z_base = (V_base,LL_kV)^2 / S_base,3φ_MVA  [Ω]                               |
| Physical Ohms:   |  Z_pu = Z_actual_ohms / Z_base  = Z_actual_ohms * (S_base,MVA / V_base,kV^2) |
| Actual Current:  |  I_actual = I_pu * I_base  [A]                                                 |
| Actual Voltage:  |  V_actual = V_pu * V_base  [V]                                                 |
+---------------------------------------------------------------------------------------------------+

3. Changing Per-Unit Impedance Bases (The Master Scaling Law)

Manufacturer nameplates state equipment impedance in per-unit on the equipment's own nominal ratings (Sbase,oldS_{\text{base},\text{old}} and Vbase,oldV_{\text{base},\text{old}}). Before assembling a system-wide reactance network on a common system base (Sbase,newS_{\text{base},\text{new}} and Vbase,newV_{\text{base},\text{new}}), every per-unit impedance must be rescaled using the Master Base Conversion Formula:

Zpu,new=Zpu,old×(Sbase,newSbase,old)×(Vbase,oldVbase,new)2Z_{\text{pu},\text{new}} = Z_{\text{pu},\text{old}} \times \left(\frac{S_{\text{base},\text{new}}}{S_{\text{base},\text{old}}}\right) \times \left(\frac{V_{\text{base},\text{old}}}{V_{\text{base},\text{new}}}\right)^2

Analytical Derivation

  1. Convert the old per-unit impedance to physical ohms (ZΩZ_\Omega): ZΩ=Zpu,old×Zbase,old=Zpu,old×(Vbase,old)2Sbase,oldZ_\Omega = Z_{\text{pu},\text{old}} \times Z_{\text{base},\text{old}} = Z_{\text{pu},\text{old}} \times \frac{(V_{\text{base},\text{old}})^2}{S_{\text{base},\text{old}}}
  2. Convert physical ohms to the new per-unit base: Zpu,new=ZΩZbase,new=Zpu,old×(Vbase,old)2Sbase,old(Vbase,new)2Sbase,new=Zpu,old×(Sbase,newSbase,old)×(Vbase,oldVbase,new)2Z_{\text{pu},\text{new}} = \frac{Z_\Omega}{Z_{\text{base},\text{new}}} = \frac{Z_{\text{pu},\text{old}} \times \frac{(V_{\text{base},\text{old}})^2}{S_{\text{base},\text{old}}}}{\frac{(V_{\text{base},\text{new}})^2}{S_{\text{base},\text{new}}}} = Z_{\text{pu},\text{old}} \times \left(\frac{S_{\text{base},\text{new}}}{S_{\text{base},\text{old}}}\right) \times \left(\frac{V_{\text{base},\text{old}}}{V_{\text{base},\text{new}}}\right)^2

Exam Warning on Voltage Squaring: In the base conversion formula, power scales linearly (SnewSold\frac{S_{\text{new}}}{S_{\text{old}}}), whereas voltage scales with the square of the inverse ratio ((VoldVnew)2\left(\frac{V_{\text{old}}}{V_{\text{new}}}\right)^2). Omitting the square exponent is one of the most common calculation mistakes on the PE Power exam!


4. Multi-Voltage Zone Power System Partitioning

In a multi-voltage power network, transformers establish distinct voltage zones. Once a base voltage is chosen for any one zone, the base voltages for all other zones are strictly locked by the nominal rated turns ratios of the intervening transformers.

MULTI-ZONE VOLTAGE PARTITIONING:
 [Zone 1: Generation]       [Zone 2: Transmission]       [Zone 3: Distribution]
   V_base1 = 13.8 kV           V_base2 = 138 kV             V_base3 = 4.16 kV
+---------------------+     +---------------------+     +---------------------+
|  (~) Generator      | T1  |   Transmission      | T2  |    Motor Load       |
|  13.8 kV Nominal    |==#==|   Line              |==#==|    4.16 kV Nominal  |
+---------------------+     +---------------------+     +---------------------+
        T1 Ratio:                   T2 Ratio:
     13.8 kV / 138 kV            138 kV / 4.16 kV

Step-by-Step Zone Propagation Rules

  1. Set Vbase1V_{\text{base}1} in Zone 1 (e.g., Vbase1=13.8 kVV_{\text{base}1} = 13.8\text{ kV}).
  2. Across Transformer T1T_1 (ratio N1:N2=13.8 kV:138 kVN_1 : N_2 = 13.8\text{ kV} : 138\text{ kV}): Vbase2=Vbase1×(VT1,secVT1,pri)=13.8 kV×(138 kV13.8 kV)=138 kVV_{\text{base}2} = V_{\text{base}1} \times \left(\frac{V_{T1,\text{sec}}}{V_{T1,\text{pri}}}\right) = 13.8\text{ kV} \times \left(\frac{138\text{ kV}}{13.8\text{ kV}}\right) = 138\text{ kV}
  3. Across Transformer T2T_2 (ratio N2:N3=138 kV:4.16 kVN_2 : N_3 = 138\text{ kV} : 4.16\text{ kV}): Vbase3=Vbase2×(VT2,secVT2,pri)=138 kV×(4.16 kV138 kV)=4.16 kVV_{\text{base}3} = V_{\text{base}2} \times \left(\frac{V_{T2,\text{sec}}}{V_{T2,\text{pri}}}\right) = 138\text{ kV} \times \left(\frac{4.16\text{ kV}}{138\text{ kV}}\right) = 4.16\text{ kV}
  4. Off-Nominal Transformer Voltage Ratings: If a motor or generator operates at a nominal nameplate voltage that differs from the zone base voltage (e.g., a 4.0 kV4.0\text{ kV} motor installed in a 4.16 kV4.16\text{ kV} zone), the voltage correction term (VoldVnew)2=(4.04.16)2=0.9245\left(\frac{V_{\text{old}}}{V_{\text{new}}}\right)^2 = \left(\frac{4.0}{4.16}\right)^2 = 0.9245 must be included in that equipment's base transformation.

5. One-Line Diagram to Per-Unit Reactance Diagram Conversion

To perform fault analysis or load flow on a power system, the physical one-line diagram is systematically transformed into a single-phase per-unit reactance network:

PHYSICAL ONE-LINE DIAGRAM:
  [Gen G1]----(Bus 1)====[Trans T1]====(Bus 2)----[Trans Line]----(Bus 3)====[Trans T2]====(Bus 4)----[Motor M1]

PER-UNIT REACTANCE DIAGRAM (ALL VALUES ON COMMON 100 MVA BASE):
    jX_G1          jX_T1           Z_line,pu          jX_T2          jX_M1
  +-[ZZZZ]- Bus 1 -[ZZZZ]- Bus 2 --[ZZZZZZZZ]-- Bus 3 -[ZZZZ]- Bus 4 -[ZZZZ]-+
  |                                                                          |
 (+)[E_G1]                                                                 (+)[E_M1]
  |                                                                          |
 === Reference Bus (Ground Neutral) ==========================================

Systematic 5-Step Network Modeling Algorithm

  1. Select Global System Bases: Establish a common three-phase power base Sbase,3ϕS_{\text{base},3\phi} (e.g., 100 MVA100\text{ MVA}) and a voltage base for one designated zone.
  2. Determine Base Voltages for All Zones: Calculate VbaseV_{\text{base}} for each zone using transformer nominal turns ratios.
  3. Compute Base Impedances (ZbaseZ_{\text{base}}) and Base Currents (IbaseI_{\text{base}}): Determine Zbase=(Vbase,kV)2/Sbase,MVAZ_{\text{base}} = (V_{\text{base},\text{kV}})^2 / S_{\text{base},\text{MVA}} for every zone.
  4. Convert All Component Impedances to System Base:
    • Generators & Motors: Rescale per-unit subtransient reactances Xd′′X_d'' via the Master Base Conversion Formula.
    • Transformers: Rescale per-unit leakage reactances XTX_T.
    • Transmission Lines & Cables: Convert physical series ohms (ZΩZ_\Omega) to per-unit: Zpu=ZΩ/Zbase,zoneZ_{\text{pu}} = Z_\Omega / Z_{\text{base},\text{zone}}.
  5. Assemble the Reactance Diagram & Solve: Combine all per-unit impedances into a single interconnected network. Solve for per-unit fault currents or bus voltages, then multiply by zone base quantities to recover actual physical values.

6. Comprehensive Step-by-Step Worked System Example

Problem Statement

A balanced three-phase power system has the following equipment specifications:

  • Generator G1G_1: 50 MVA50\text{ MVA}, 13.8 kV13.8\text{ kV}, subtransient reactance Xd′′=0.15 puX_d'' = 0.15\text{ pu}.
  • Step-Up Transformer T1T_1: 60 MVA60\text{ MVA}, 13.8 kV (Δ)−115 kV (Y)13.8\text{ kV (}\Delta\text{)} - 115\text{ kV (Y)}, leakage reactance XT1=0.10 puX_{T1} = 0.10\text{ pu}.
  • Transmission Line: 20 miles20\text{ miles} in length, series impedance z=0.15+j0.80 Ω/milez = 0.15 + j0.80\,\Omega/\text{mile}, operating at 115 kV115\text{ kV}.
  • Step-Down Transformer T2T_2: 40 MVA40\text{ MVA}, 115 kV (Y)−13.8 kV (Δ)115\text{ kV (Y)} - 13.8\text{ kV (}\Delta\text{)}, leakage reactance XT2=0.08 puX_{T2} = 0.08\text{ pu}.
  • Motor M1M_1: 30 MVA30\text{ MVA}, 13.2 kV13.2\text{ kV}, subtransient reactance Xm′′=0.20 puX_m'' = 0.20\text{ pu}.

System Base Specifications: Select a common system power base of Sbase,3ϕ=100 MVAS_{\text{base},3\phi} = 100\text{ MVA} and a generator zone voltage base of Vbase1=13.8 kVV_{\text{base}1} = 13.8\text{ kV}.

Calculate:

  1. The voltage base (VbaseV_{\text{base}}) and base impedance (ZbaseZ_{\text{base}}) in all three zones.
  2. The per-unit impedance of each system component on the common 100 MVA100\text{ MVA} base.
  3. The total series Thevenin impedance between the internal generator EMF and motor EMF.
  4. The symmetrical three-phase short-circuit current in Amperes at the motor bus (Bus 4) for a solid three-phase fault, assuming a prefault voltage of Vf=1.0∠0∘ puV_f = 1.0\angle 0^\circ\text{ pu} and neglecting prefault load current and line resistance.
=========================================================================================
CALCULATION WORKFLOW & DETAILED STEP-BY-STEP SOLUTION:
=========================================================================================

Step 1: Determine Voltage and Impedance Bases for All Zones
  System Power Base: S_base,3ph = 100 MVA

  Zone 1 (Generator Zone):
    V_base1 = 13.8 kV
    Z_base1 = (V_base1)^2 / S_base = (13.8)^2 / 100 = 190.44 / 100 = 1.9044 ohms
    I_base1 = S_base / (sqrt(3) * V_base1) = 100,000 / (1.73205 * 13.8) = 4,183.7 A

  Zone 2 (Transmission Line Zone):
    V_base2 = V_base1 * (115 / 13.8) = 13.8 * (115 / 13.8) = 115.0 kV
    Z_base2 = (V_base2)^2 / S_base = (115.0)^2 / 100 = 13225.0 / 100 = 132.25 ohms
    I_base2 = S_base / (sqrt(3) * V_base2) = 100,000 / (1.73205 * 115.0) = 502.04 A

  Zone 3 (Motor Zone):
    V_base3 = V_base2 * (13.8 / 115.0) = 115.0 * (13.8 / 115.0) = 13.8 kV
    Z_base3 = (V_base3)^2 / S_base = (13.8)^2 / 100 = 1.9044 ohms
    I_base3 = S_base / (sqrt(3) * V_base3) = 4,183.7 A

Step 2: Convert Component Impedances to Common 100 MVA Base
  1. Generator G1 (50 MVA, 13.8 kV, X" = 0.15 pu):
     X_G1,new = X_G1,old * (S_base,new / S_base,old) * (V_base,old / V_base,new)^2
              = 0.15 * (100 / 50) * (13.8 / 13.8)^2
              = 0.15 * 2.0 * 1.0
              = 0.3000 pu

  2. Step-Up Transformer T1 (60 MVA, 13.8/115 kV, X = 0.10 pu):
     X_T1,new = 0.10 * (100 / 60) * (115 / 115)^2
              = 0.10 * 1.6667 * 1.0
              = 0.1667 pu

  3. Transmission Line (20 miles * (0.15 + j0.80 ohms/mi) = 3.0 + j16.0 ohms):
     Z_line,pu = Z_actual / Z_base2
               = (3.0 + j16.0) / 132.25
               = (3.0 / 132.25) + j(16.0 / 132.25)
               = 0.02268 + j0.12098 pu

  4. Step-Down Transformer T2 (40 MVA, 115/13.8 kV, X = 0.08 pu):
     X_T2,new = 0.08 * (100 / 40) * (115 / 115)^2
              = 0.08 * 2.50 * 1.0
              = 0.2000 pu

  5. Motor M1 (30 MVA, 13.2 kV, X" = 0.20 pu):
     Notice: Motor nominal voltage (13.2 kV) differs from Zone 3 base voltage (13.8 kV)!
     X_M1,new = X_M1,old * (S_base,new / S_base,old) * (V_base,old / V_base,new)^2
              = 0.20 * (100 / 30) * (13.2 / 13.8)^2
              = 0.20 * 3.3333 * (0.95652)^2
              = 0.66667 * 0.91493
              = 0.60995 pu ≈ 0.6100 pu

Step 3: Total Series Impedance Calculation (Generator to Motor)
  Z_series = jX_G1 + jX_T1 + Z_line + jX_T2 + jX_M1
           = j0.3000 + j0.1667 + (0.0227 + j0.1210) + j0.2000 + j0.6100
           = 0.0227 + j(0.3000 + 0.1667 + 0.1210 + 0.2000 + 0.6100)
           = 0.0227 + j1.3977 pu

Step 4: Symmetrical Short-Circuit Fault Current Calculation at Motor Bus (Bus 4)
  For a solid 3-phase fault at Bus 4 (upstream Thevenin reactance excluding motor):
    X_th,upstream = X_G1 + X_T1 + X_line + X_T2
                  = 0.3000 + 0.1667 + 0.1210 + 0.2000
                  = 0.7877 pu

  Per-unit fault current contributed from utility/generator source:
    I_f,pu = V_f / X_th,upstream
           = 1.0 / 0.7877
           = 1.2695 pu

  Convert per-unit fault current to actual Amperes in Zone 3:
    I_f,actual = I_f,pu * I_base3
               = 1.2695 * 4,183.7 A
               = 5,311.2 A = 5.311 kA
=========================================================================================

7. Common Exam Traps & Tactical Pitfalls

  • Omitting the Square on the Voltage Conversion Ratio: Using VoldVnew\frac{V_{\text{old}}}{V_{\text{new}}} instead of (VoldVnew)2\left(\frac{V_{\text{old}}}{V_{\text{new}}}\right)^2. Because impedance is proportional to voltage squared (Z∝V2Z \propto V^2), the voltage adjustment ratio must always be squared.
  • Inverting the Voltage Ratio: Multiplying by (VnewVold)2\left(\frac{V_{\text{new}}}{V_{\text{old}}}\right)^2 instead of (VoldVnew)2\left(\frac{V_{\text{old}}}{V_{\text{new}}}\right)^2. An apparatus with a lower rated voltage operating in a higher base voltage zone will have a smaller per-unit impedance on the new base.
  • Single-Phase vs. Three-Phase Base Power Mismatch: Using single-phase MVA in Zbase=VLL2SZ_{\text{base}} = \frac{V_{LL}^2}{S} with line-to-line voltage. Remember: Zbase=(Vbase,LL)2Sbase,3ϕ=(Vbase,LN)2Sbase,1ϕZ_{\text{base}} = \frac{(V_{\text{base},LL})^2}{S_{\text{base},3\phi}} = \frac{(V_{\text{base},LN})^2}{S_{\text{base},1\phi}}. Mixing VLLV_{LL} with S1ϕS_{1\phi} causes a factor of 3 error!
  • Neglecting Off-Nominal Equipment Nameplates: Assuming equipment rated voltage always matches the zone base voltage. Always check the motor and transformer nameplates against the zone base.
Loading diagram...
One-Line Diagram to Per-Unit Reactance Network Conversion
Test Your Knowledge

A 3-phase, 13.8 kV, 25 MVA synchronous generator has a subtransient reactance of X_d'' = 0.18 pu based on its own nameplate rating. What is the generator's subtransient reactance expressed on a system base of 100 MVA and 13.2 kV?

A

0.658 pu

B

0.720 pu

C

0.787 pu

D

0.041 pu

Test Your Knowledge

In a 3-phase power system, Zone 2 represents a 230 kV transmission line section modeled on a 100 MVA base. What is the base impedance Z_base of Zone 2, and what is the per-unit impedance of a transmission line with an actual physical impedance of 10.58 + j52.90 ohms?

A

Z_base = 529.0 ohms and Z_pu = 0.050 + j0.250 pu

B

Z_base = 230.0 ohms and Z_pu = 0.046 + j0.230 pu

C

Z_base = 100.0 ohms and Z_pu = 0.106 + j0.529 pu

D

Z_base = 529.0 ohms and Z_pu = 0.020 + j0.100 pu

Test Your Knowledge

A 3-phase, 500 kVA, 480 V load draws 0.85 pu current at 0.80 power factor lagging from a 480 V system modeled on a 1.0 MVA, 480 V base. What is the actual physical line current drawn by the load in Amperes?

A

1022.4 A

B

511.2 A

C

1202.8 A

D

601.4 A

Sections you finish are checked off in the contents.