9.3 Single Line-to-Ground (SLG) & Line-to-Line (LL) Fault Analysis
Key Takeaways
- Single Line-to-Ground (SLG / 1LG) faults are the most frequent power system fault (~70-80% of all faults); boundary conditions on Phase A (I_b = 0, I_c = 0, V_a = I_a * Z_f) dictate that all three sequence currents are equal: I_a0 = I_a1 = I_a2 = I_a / 3.
- The sequence network interconnection for an SLG fault is a SERIES connection of the positive, negative, and zero sequence networks; the total fault current is I_fault = I_a = 3 * I_a0 = 3 * V_f / (Z_1 + Z_2 + Z_0 + 3*Z_f).
- In solidly grounded systems where the zero-sequence impedance is smaller than the positive-sequence impedance (Z_0 < Z_1, common near solidly grounded autotransformers and generator neutrals), the SLG fault current magnitude strictly EXCEEDS the three-phase symmetrical fault current (I_SLG > I_3φ)!
- Line-to-Line (L-L / 2L) faults (~15% of faults) involve a short circuit between two phases (e.g., Phase B to C); boundary conditions (I_a = 0, I_b = -I_c, V_b - V_c = I_b * Z_f) isolate the zero-sequence network completely (I_a0 = 0) and force I_a1 = -I_a2.
- The sequence network interconnection for an L-L fault is a PARALLEL connection of the positive and negative sequence networks; the phase fault current magnitude is |I_fault| = |I_b| = √3 * |I_a1| = √3 * |V_f| / |Z_1 + Z_2 + Z_f|, which equals exactly (√3 / 2) * I_3φ ≈ 0.866 * I_3φ when Z_1 = Z_2 and Z_f = 0.
9.3 Single Line-to-Ground (SLG) & Line-to-Line (LL) Fault Analysis
Unsymmetrical short circuits represent over $95%$ of all faults occurring in electrical power systems. Because unsymmetrical faults destroy the natural phase balance of three-phase networks, they cannot be analyzed using simple single-phase per-phase equivalent circuits alone. Instead, we utilize Fortescue's Symmetrical Components Method, which transforms three coupled, unbalanced phase quantities into three decoupled, balanced symmetrical sequence networks: Positive-Sequence ($1$), Negative-Sequence ($2$), and Zero-Sequence ($0$).
On the NCEES PE Electrical and Computer: Power examination, mastering Single Line-to-Ground (SLG) and Line-to-Line (L-L) fault calculations requires deriving sequence current equations from boundary conditions, synthesizing sequence network interconnections, and calculating ground return currents and unfaulted phase voltage elevations.
1. Symmetrical Components Transformation Review
Fortescue's transformation expresses physical phase quantities ($A, B, C$) in terms of symmetrical sequence components ($0, 1, 2$) using the complex phase rotation operator $a = 1\angle 120^\circ = -0.5 + j0.866025$ (where $a^2 = 1\angle 240^\circ = -0.5 - j0.866025$, and $1 + a + a^2 = 0$):
Sequence Thevenin Voltage Equations Seen at Fault Bus
- Positive-Sequence: $V_{a1} = V_f - I_{a1} Z_1$ (Contains internal prefault generated voltage $V_f$)
- Negative-Sequence: $V_{a2} = 0 - I_{a2} Z_2 = -I_{a2} Z_2$ (Passive network, no internal sources)
- Zero-Sequence: $V_{a0} = 0 - I_{a0} Z_0 = -I_{a0} Z_0$ (Passive network, no internal sources)
2. Single Line-to-Ground (SLG / 1LG) Fault Analysis
The Single Line-to-Ground fault is the most common short-circuit event in power systems, accounting for approximately $70%$ to $80%$ of all faults (caused by insulator flashover, lightning strikes, tree branches, or animal contact).
SINGLE LINE-TO-GROUND (SLG) FAULT TOPOLOGY
Phase A o----------------+--------o Fault Current: I_a
|
+---+
| | Z_f (Fault Impedance)
+---+
|
===
Phase B o-------------------------o I_b = 0 (Open)
Phase C o-------------------------o I_c = 0 (Open)
Boundary Conditions (Fault on Phase A to Ground through $Z_f$)
- $I_b = 0$
- $I_c = 0$
- $V_a = I_a Z_f$ (For a bolted fault, $Z_f = 0 \implies V_a = 0$)
Sequence Current Derivation
Substituting the boundary conditions $I_b = 0, I_c = 0$ into the inverse symmetrical component transformation:
Sequence Network Interconnection: SERIES Connection
Because all three sequence currents flowing out of the sequence networks are identical ($I_{a0} = I_{a1} = I_{a2}$), the Positive, Negative, and Zero sequence networks must be connected in SERIES at the fault point.
SLG SEQUENCE NETWORK INTERCONNECTION (SERIES)
+---[ Z_1 ]---(~) V_f (Positive Sequence)
| |
+---------------+ I_a1
|
+---[ Z_2 ]-----+ (Negative Sequence)
| | I_a2
+---------------+
|
+---[ Z_0 ]-----+ (Zero Sequence)
| | I_a0
+---------------+
|
+---[ 3*Z_f ]---+
| |
+---------------+ Reference
Master SLG Fault Current Formula
Summing the voltages around the closed series loop:
Since $I_{a1} = I_{a2} = I_{a0}$:
3. High SLG Fault Current Phenomenon in Solidly Grounded Systems
One of the most critical and counter-intuitive phenomena tested on the PE Power examination is that Single Line-to-Ground fault currents can exceed Three-Phase symmetrical fault currents.
+---------------------------------------------------------------------------------------------------+
| SLG vs. THREE-PHASE FAULT CURRENT MAGNITUDE |
+---------------------------------------------------------------------------------------------------+
| Three-Phase Symmetrical Fault: I_f,3φ = V_f / Z_1 = (3 * V_f) / (3 * Z_1) |
| Single Line-to-Ground Fault: I_f,SLG = (3 * V_f) / (Z_1 + Z_2 + Z_0) |
| |
| In typical power networks, Z_2 ≈ Z_1. Substituting Z_2 = Z_1 into the SLG formula: |
| |
| I_f,SLG = (3 * V_f) / (2 * Z_1 + Z_0) |
| |
| CRITICAL COMPARISON: |
| - If Z_0 = Z_1: I_f,SLG = (3 * V_f) / (3 * Z_1) = I_f,3φ (SLG equals 3-Phase fault current) |
| - If Z_0 > Z_1: I_f,SLG < I_f,3φ (SLG is LESS than 3-Phase) |
| - If Z_0 < Z_1: I_f,SLG > I_f,3φ (SLG is GREATER than 3-Phase!) |
+---------------------------------------------------------------------------------------------------+
[!IMPORTANT] Where Does $Z_0 < Z_1$ Occur? In solidly grounded systems near generating stations, large solidly grounded autotransformers, or grounded-wye/delta step-down transformers, the zero-sequence path has very low impedance ($Z_0 \approx 0.4$ to $0.8 \times Z_1$). In these locations, the SLG fault produces the highest short-circuit current in the entire facility, dictating breaker interrupting ratings and grounding grid sizing!
Unfaulted Phase Voltages During Bolted SLG Fault ($V_b, V_c$)
During an SLG fault on Phase A ($V_a = 0$), the healthy phase voltages ($V_b$ and $V_c$) shift depending on system grounding:
- In Solidly Grounded Systems ($Z_0 \approx Z_1$): Healthy phase voltages remain near nominal ($|V_b| = |V_c| \approx 0.9$ to $1.0\text{ pu}$).
- In Ungrounded Systems ($Z_0 \to \infty$): Zero-sequence voltage rises to full phase voltage ($V_{a0} = -V_f$), causing the healthy phase voltages to elevate to full line-to-line voltage ($|V_b| = |V_c| = \sqrt{3} V_{LN} \approx 1.732\text{ pu}$). Insulation and surge arresters must be rated for line-to-line voltage.
4. Line-to-Line (L-L / 2L) Fault Analysis
A Line-to-Line fault occurs when two phase conductors make physical contact or flashover across insulators without involving earth ground (e.g., Phase B shorted to Phase C).
LINE-TO-LINE (L-L) FAULT TOPOLOGY
Phase A o----------------------------------o I_a = 0 (Unfaulted)
Phase B o----------------+-----------------o Fault Current: I_b
|
+---+
| | Z_f (Fault Impedance)
+---+
|
Phase C o----------------+-----------------o Fault Current: I_c = -I_b
Boundary Conditions (Fault between Phase B and Phase C through $Z_f$)
- $I_a = 0$
- $I_b = -I_c \implies I_b + I_c = 0$
- $V_b - V_c = I_b Z_f$ (For a bolted fault, $Z_f = 0 \implies V_b = V_c$)
Sequence Current Derivation
Applying symmetrical component transformation:
+---------------------------------------------------------------------------------------------------+
| L-L FAULT SEQUENCE CURRENT RELATIONSHIPS |
+---------------------------------------------------------------------------------------------------+
| 1. Zero-Sequence Current is ZERO: I_a0 = 0 (Zero-sequence network is completely ISOLATED/OPEN!) |
| 2. Negative-Sequence opposes Pos.: I_a2 = -I_a1 |
| 3. Phase Fault Current: I_b = -j*sqrt(3) * I_a1 |
+---------------------------------------------------------------------------------------------------+
Sequence Network Interconnection: PARALLEL Connection (Pos & Neg)
Because $I_{a1} = -I_{a2}$ and $I_{a0} = 0$, the Positive-Sequence and Negative-Sequence networks are connected in PARALLEL across the fault impedance $Z_f$, while the Zero-Sequence network is completely open.
L-L SEQUENCE NETWORK INTERCONNECTION (PARALLEL)
+---[ Z_1 ]---(~) V_f (Positive Sequence)
| |
+-----+---------------+-----+ I_a1
| |
| +---[ Z_2 ]-----+ | I_a2 = -I_a1
| | (Negative Seq)| |
+-----+---------------+-----+
| |
+-----------[ Z_f ]---------+ (Fault Impedance)
[ Z_0 Network ] ===> OPEN CIRCUIT (I_a0 = 0)
Master Line-to-Line Fault Current Formula
From the parallel sequence loop:
The Standard $0.866$ Ratio for Bolted L-L Faults
When $Z_f = 0$ and the negative-sequence impedance equals the positive-sequence impedance ($Z_2 = Z_1$):
+---------------------------------------------------------------------------------------------------+
| SUMMARY OF 3-PHASE, SLG, AND L-L FAULT CURRENT FORMULAS |
+---------------------------------------------------------------------------------------------------+
| Fault Type | Sequence Interconnection | Sequence Currents | Fault Current (I_fault)|
| :--- | :--- | :--- | :--- |
| **3-Phase (3Φ)** | Positive Sequence Only | $I_{a1} = I_a$ | $I_f = \frac{V_f}{Z_1}$ |
| | | $I_{a2}=0, I_{a0}=0$ | |
| **Single Line-to- | Series Connection of | $I_{a0} = I_{a1} = I_{a2}$ | $I_f = \frac{3 V_f}{Z_1 + Z_2 + Z_0 + 3Z_f}$ |
| **Ground (SLG)** | Pos, Neg, & Zero | $= I_a / 3$ | |
| **Line-to-Line (L-L)** | Parallel Connection of | $I_{a1} = -I_{a2}$ | $|I_f| = \frac{\sqrt{3} V_f}{Z_1 + Z_2 + Z_f}$ |
| | Pos & Neg (Zero Open) | $I_{a0} = 0$ | $= 0.866 \cdot I_{3\phi}$ (if $Z_1=Z_2$) |
+---------------------------------------------------------------------------------------------------+
5. Step-by-Step Worked Mathematical Example
Problem Statement
A $13.8\text{ kV}$ (line-to-line), $100\text{ MVA}$ base substation bus is fed by a solidly grounded power system with the following equivalent Thevenin sequence impedances:
- Positive-Sequence Impedance: $Z_1 = j0.12\text{ pu}$
- Negative-Sequence Impedance: $Z_2 = j0.12\text{ pu}$
- Zero-Sequence Impedance: $Z_0 = j0.06\text{ pu}$ (Solidly grounded source with low zero-sequence impedance)
- Prefault Voltage: $V_f = 1.0\angle 0^\circ\text{ pu}$
Calculate:
- The base current ($I_{base}$) at $13.8\text{ kV}$.
- The bolted Three-Phase fault current ($I_{3\phi}$) in per-unit and Amperes.
- The bolted Single Line-to-Ground (SLG) fault current ($I_{SLG}$) in per-unit and Amperes, and determine the percentage by which $I_{SLG}$ exceeds $I_{3\phi}$.
- The SLG fault current if a fault impedance of $Z_f = 0.50,\Omega$ is present in the ground return path.
- The bolted Line-to-Line (L-L) fault current ($I_{LL}$) in per-unit and Amperes, and verify the $86.6%$ ratio.
- The voltages of the healthy phases ($V_b$ and $V_c$) during the bolted SLG fault on Phase A.
=========================================================================================
CALCULATION WORKFLOW & DETAILED STEP-BY-STEP SOLUTION:
=========================================================================================
Step 1: Calculate System Base Quantities
Base Power: S_base = 100 MVA
Base Voltage: V_base_LL = 13.8 kV
Base Current:
I_base = (100 * 10^6 VA) / (sqrt(3) * 13,800 V) = 4,183.70 A
Base Impedance:
Z_base = (V_base_LL)^2 / S_base = (13.8 kV)^2 / 100 MVA = 1.9044 ohms
Step 2: Three-Phase Symmetrical Fault Current
I_f,3φ,pu = V_f / Z_1 = (1.0 /_ 0°) / (j0.12) = -j8.3333 pu = 8.3333 /_ -90° pu
I_f,3φ,actual = 8.3333 * 4,183.70 A = 34,864.2 A ≈ 34.86 kA rms
Step 3: Bolted Single Line-to-Ground (SLG) Fault Current (Z_f = 0)
Total Sequence Impedance:
Z_total,SLG = Z_1 + Z_2 + Z_0 = j0.12 + j0.12 + j0.06 = j0.30 pu
Sequence Currents:
I_a0 = I_a1 = I_a2 = V_f / Z_total,SLG = (1.0 /_ 0°) / (j0.30) = -j3.3333 pu
Total Phase A Fault Current:
I_a = 3 * I_a0 = 3 * (-j3.3333 pu) = -j10.0000 pu = 10.0000 /_ -90° pu
Actual SLG Fault Current:
I_f,SLG,actual = 10.0000 * 4,183.70 A = 41,837.0 A ≈ 41.84 kA rms
Comparison Ratio:
Ratio = I_f,SLG / I_f,3φ = 10.0000 pu / 8.3333 pu = 1.200 (120% of 3-Phase fault!)
--> The SLG fault current is 20.0% GREATER than the 3-phase fault current!
Step 4: SLG Fault with Fault Impedance Z_f = 0.50 ohms
Convert Z_f to per-unit:
Z_f,pu = 0.50 ohms / 1.9044 ohms = 0.26255 pu
3 * Z_f,pu = 3 * 0.26255 = 0.78765 pu
Total Series Loop Impedance:
Z_loop = (3 * Z_f,pu) + j(Z_1 + Z_2 + Z_0) = 0.78765 + j0.30000 pu
|Z_loop| = sqrt( (0.78765)^2 + (0.30000)^2 ) = sqrt( 0.62039 + 0.09000 ) = 0.84285 pu
Sequence Current Magnitude:
|I_a0| = 1.0 / 0.84285 = 1.18645 pu
Total Fault Current Magnitude:
|I_a| = 3 * 1.18645 pu = 3.55935 pu
I_f,actual = 3.55935 * 4,183.70 A = 14,891.3 A ≈ 14.89 kA rms
Step 5: Bolted Line-to-Line (L-L) Fault Current (Z_f = 0)
Sequence Currents:
I_a0 = 0
I_a1 = -I_a2 = V_f / (Z_1 + Z_2) = (1.0 /_ 0°) / (j0.12 + j0.12) = 1.0 / (j0.24) = -j4.1667 pu
Phase B Fault Current Magnitude:
|I_b| = sqrt(3) * |I_a1| = sqrt(3) * 4.1667 pu = 7.2169 pu
Actual L-L Fault Current:
I_f,LL,actual = 7.2169 * 4,183.70 A = 30,193.3 A ≈ 30.19 kA rms
Verification of 0.866 Ratio:
|I_b| / I_f,3φ = 7.2169 pu / 8.3333 pu = 0.86603 = sqrt(3)/2 (CONFIRMED)
Step 6: Healthy Phase Voltages (V_b, V_c) During Bolted SLG Fault on Phase A
Sequence Voltages at Fault Point:
V_a0 = -I_a0 * Z_0 = -(-j3.3333) * (j0.06) = -0.2000 pu
V_a1 = V_f - I_a1 * Z_1 = 1.0 - (-j3.3333)*(j0.12) = 1.0 - 0.4000 = 0.6000 pu
V_a2 = -I_a2 * Z_2 = -(-j3.3333) * (j0.12) = -0.4000 pu
Check Phase A Voltage: V_a = V_a0 + V_a1 + V_a2 = -0.2000 + 0.6000 - 0.4000 = 0.00 pu (CONFIRMED)
Phase B Voltage:
V_b = V_a0 + a^2 * V_a1 + a * V_a2
= -0.2000 + (0.6000 /_ 240°) + (-0.4000 /_ 120°)
= -0.2000 + 0.6000(-0.5 - j0.86603) - 0.4000(-0.5 + j0.86603)
= -0.2000 - 0.3000 - j0.51962 + 0.2000 - j0.34641
= -0.3000 - j0.86603 pu
|V_b| = sqrt( (-0.3000)^2 + (-0.86603)^2 ) = sqrt( 0.0900 + 0.7500 ) = sqrt(0.8400) = 0.9165 pu
Phase C Voltage:
V_c = V_a0 + a * V_a1 + a^2 * V_a2
= -0.2000 + (0.6000 /_ 120°) + (-0.4000 /_ 240°)
= -0.3000 + j0.86603 pu
|V_c| = sqrt( (-0.3000)^2 + (0.86603)^2 ) = sqrt(0.8400) = 0.9165 pu
=========================================================================================
6. Common PE Exam Traps & Tactical Pitfalls
- Assuming Three-Phase Fault Current is Always the Maximum: Assuming $I_{3\phi}$ is always greater than $I_{SLG}$. In solidly grounded systems with $Z_0 < Z_1$, the SLG fault current is strictly higher than the 3-phase fault current. Always check $Z_0$ relative to $Z_1$ before declaring the maximum fault level.
- Omitting the Factor of 3 on Fault Impedance ($3 Z_f$): Placing $Z_f$ directly in series with the sequence networks instead of $3 Z_f$. Because $I_a = 3 I_{a0}$, the actual voltage drop across $Z_f$ is $V_f = I_a Z_f = 3 I_{a0} Z_f$. In the sequence loop where current $I_{a0}$ circulates, the effective impedance is $3 Z_f$.
- Forgetting that Ground Return Current is $3 I_{a0}$: Calculating ground/neutral current as $I_{a0}$ instead of $3 I_{a0}$. Neutral overcurrent relays (50N/51N) connected in the residual CT circuit measure $I_n = I_a + I_b + I_c = 3 I_{a0}$.
- Attempting to Circulate Zero-Sequence Current in Line-to-Line Faults: Including $Z_0$ in L-L fault calculations. Because an L-L fault does not involve ground, the sum of phase currents is zero ($I_b + I_c = 0$), forcing $I_{a0} = 0$. The zero-sequence network is completely isolated and plays no role.
A power substation engineer calculates the sequence Thevenin impedances at a 115 kV transmission bus as Z_1 = j0.10 pu, Z_2 = j0.10 pu, and Z_0 = j0.04 pu. Why does the bolted Single Line-to-Ground (SLG) fault current exceed the bolted Three-Phase symmetrical fault current at this bus?
In the symmetrical component analysis of a bolted Line-to-Line (L-L) fault occurring between Phase B and Phase C with zero fault impedance (Z_f = 0), what is the relationship between sequence networks, and what is the fault current magnitude if Z_1 = Z_2 = j0.15 pu on a 1.0 pu voltage base?
When deriving the equivalent sequence circuit for a Single Line-to-Ground (SLG) fault that contacts earth through an intentional grounding resistor of impedance R_g, why must the term (3 * R_g) be inserted into the zero-sequence network loop rather than just R_g?