12.4 System Commissioning, Testing, Adjusting & Balancing (TAB)
Key Takeaways
- System commissioning and TAB follow ASHRAE Standard 111 and ACCA Quality Installation (ANSI/ACCA 5 QI) standards to verify design airflow, static pressures, electrical operating limits, and proper refrigerant charge.
- Total External Static Pressure (TESP) is measured across the air handler/furnace (Supply Plenum SP minus Return Plenum SP) and compared to manufacturer blower performance tables to determine actual operating system CFM.
- The Fan Laws define the mathematical relationships of air distribution: Airflow (CFM) varies directly with RPM, Static Pressure varies with the square of RPM, and Fan Power (Brake Horsepower) varies with the cube of RPM.
- Duct velocity and airflow volume are measured using pitot tube duct traverses based on the velocity pressure formula: V = 4,005 · √(Pv), with CFM = Duct Area (sq ft) · Average Velocity (FPM).
- The North Carolina Energy Conservation Code and NC Mechanical Code mandate verified duct leakage limits (tested via duct pressurization at 25 Pascals to meet CFM25 / 100 sq ft CFA thresholds) and functional testing of economizers and ventilation systems.
System Commissioning, Testing, Adjusting & Balancing (TAB)
Core TAB Principle: Design engineering on paper is only as good as physical field execution. Testing, Adjusting, and Balancing (TAB) and structured System Commissioning (Cx) per ASHRAE Standard 111, ACCA Standard 5 (ANSI/ACCA QI), and the North Carolina Energy Conservation Code ensure that air and hydronic distribution systems deliver exact design airflow, design thermal capacity, proper indoor air quality (IAQ), and maximum energy efficiency.
Total External Static Pressure (TESP) & Airflow Determination
Total External Static Pressure (TESP) is the total resistance that the air distribution duct system (supply ducts, return ducts, filters, coils, registers) imposes on the indoor blower fan.
[ Return Duct ]
|
v
(P_return) [ Static Probe 1 ] (Entering Air Handler / Before Blower)
|
[ Air Filter ]
|
[ Blower Motor ]
|
[ Heating Elements / Heat Exchanger ]
|
(P_supply) [ Static Probe 2 ] (Leaving Air Handler / Before A-Coil)
|
[ Evaporator Coil ]
|
v
[ Supply Plenum ]
1. The TESP Calculation Formula
- Measurement Protocol: Using a calibrated dual-port digital manometer and static pressure tips pointing directly into the airstream:
- $P_{\text{return}}$ is measured in the return plenum between the air filter and the blower inlet (typically a negative pressure, e.g., $-0.25\text{ in. w.c.}$). Drop the negative sign and take the absolute value.
- $P_{\text{supply}}$ is measured in the supply plenum downstream of the furnace/air handler (typically a positive pressure, e.g., $+0.25\text{ in. w.c.}$). In electric air handlers with internal coils, measure after the coil; in gas furnaces with cased uncased add-on coils, measure between furnace and coil to isolate furnace TESP from coil pressure drop.
2. Interpreting Manufacturer Blower Performance Tables
Once TESP is measured, the technician references the manufacturer's engineering blower performance chart for the specific motor speed tap or ECM profile to determine delivered CFM:
Sample Blower Performance Table (CFM vs. TESP in inches w.c.)
| Motor Speed Tap | $0.10\text{ in. w.c.}$ | $0.20\text{ in. w.c.}$ | $0.30\text{ in. w.c.}$ | $0.40\text{ in. w.c.}$ | $0.50\text{ in. w.c.}$ | $0.60\text{ in. w.c.}$ | $0.70\text{ in. w.c.}$ | $0.80\text{ in. w.c.}$ |
|---|---|---|---|---|---|---|---|---|
| Low (Red) | $850$ | $820$ | $780$ | $740$ | $690$ | $630$ | $560$ | $480$ |
| Med-Low (Yellow) | $1,120$ | $1,080$ | $1,040$ | $990$ | $930$ | $860$ | $780$ | $690$ |
| Med-High (Blue) | $1,380$ | $1,340$ | $1,290$ | $1,230$ | $1,170$ | $1,090$ | $1,000$ | $890$ |
| High (Black) | $1,620$ | $1,570$ | $1,510$ | $1,440$ | $1,360$ | $1,270$ | $1,160$ | $1,030$ |
Standard Rule: Residential cooling systems require $350\text{ to }450\text{ CFM per ton}$ ($400\text{ CFM/ton}$ nominal in North Carolina's humid climate to balance sensible cooling and latent dehumidification).
Quantitative Airflow Measurement Methods
When blower tables are unavailable or duct geometry requires physical verification, three primary engineering methods are used:
1. Electric Resistance Heat Temperature Rise Method
Because electric resistance strip heaters convert electrical energy into heat at $100%$ efficiency ($1\text{ kW} = 3,412.14\text{ BTU/hr}$), measured temperature rise and electric power provide an exact calculation of system CFM:
Where $1.08$ is the sensible heat constant for standard air density ($0.075\text{ lb/ft}^3 \times 0.24\text{ BTU/(lb}\cdot^\circ\text{F)} \times 60\text{ min/hr}$). (For high-altitude adjustments, use $c_p \cdot \rho \cdot 60$).
2. Pitot Tube Duct Traverse & Velocity Pressure ($P_v$)
A Pitot tube connected to a digital manometer senses Total Pressure ($P_t$) through its open impact tip and Static Pressure ($P_s$) through its side radial ports. The manometer calculates Velocity Pressure ($P_v$):
ASHRAE 111 Duct Traverse Grid Methods:
├── Round Ducts: Log-Tchebycheff Rule or Equal Area Method (Min 12 to 20 traverse points across 2 perpendicular diameters)
└── Rectangular Ducts: Minimum 16 to 64 traverse grid points centered in equal rectangular areas.
The Governing Fan Laws & Sheave Sizing
The Fan Laws govern all aerodynamic performance changes in commercial and residential centrifugal and axial fans when motor speed, pulley diameter, or duct static pressures are altered.
+-----------------------------------------------------------------------------------------+
| THE GOVERNING FAN LAWS |
+-----------------------------------------------------------------------------------------+
| Fan Law 1 (Airflow vs Speed): CFM_2 / CFM_1 = RPM_2 / RPM_1 |
| Fan Law 2 (Static Press vs Speed): SP_2 / SP_1 = (RPM_2 / RPM_1)² = (CFM_2 / CFM_1)² |
| Fan Law 3 (Power vs Speed): BHP_2 / BHP_1 = (RPM_2 / RPM_1)³ = (CFM_2 / CFM_1)³ |
+-----------------------------------------------------------------------------------------+
The Critical Cubic Power Relationship (Fan Law 3)
[!WARNING] Fan Law 3 Mandate: Blower fan Brake Horsepower (BHP) increases with the CUBE of the speed ratio ($(\text{RPM}_2 / \text{RPM}_1)^3$). A modest $20%$ increase in airflow ($1.20\times\text{CFM}$) requires an $72.8%$ increase in motor horsepower ($1.20^3 = 1.728$). Attempting to solve airflow deficits by simply speeding up a belt-driven blower will rapidly overload the motor, causing nuisance overcurrent trips or winding burnout unless motor horsepower is upgraded.
Pulley (Sheave) Sizing Formula
For belt-driven commercial fans:
Where $D_{\text{fan}}$ is pitch diameter of fan pulley and $D_{\text{motor}}$ is pitch diameter of motor pulley.
North Carolina Energy Code & Mechanical Code Commissioning Mandates
Under the North Carolina Energy Conservation Code (NCECC) and NC Mechanical Code (NCMC Chapter 4 & 6), contractors must execute verified commissioning:
NC Building Code Commissioning Checkpoints:
├── 1. Duct Leakage Pressurization Testing (Total Leakage ≤ 5 CFM25 per 100 sq ft CFA
│ or Leakage to Outdoors ≤ 4 CFM25 per 100 sq ft CFA when tested at 25 Pascals).
├── 2. Ventilation Verification (ASHRAE 62.2 / NCMC Chapter 4 mechanical outdoor air rates).
├── 3. Economizer Functional Testing (Air-side economizers must modulate dampers to 100%
│ outdoor air when ambient conditions permit free cooling, with verified sensor calibration).
└── 4. Refrigerant Charge Verification (Subcooling verified within ± 3°F of nameplate on TXV
systems; Superheat within ± 5°F of manufacturer target chart on fixed orifice systems).
Step-by-Step Worked Technical Examples
Example 1: Electric Heat Temperature Rise Airflow Calculation
Problem: A technician commissions a 3.5-ton split-system heat pump with an electric resistance strip heater. With only the electric heat operating, the technician measures:
- Operating Line Voltage: $240.0\text{ V}$
- Total Heater Element Current: $40.5\text{ A}$
- Return Air Temperature entering air handler: $68.0^\circ\text{F}$
- Supply Air Temperature leaving air handler: $92.5^\circ\text{F}$
Calculate: (1) Total electric heat output in $\text{Watts}$ and $\text{BTU/hr}$, (2) Air temperature rise ($\Delta T$), and (3) Actual delivered system airflow in $\text{CFM}$.
Solution:
-
Calculate Heat Output in Watts and BTU/hr:
-
Calculate Air Temperature Rise ($\Delta T$):
-
Calculate System Delivered Airflow (CFM):
- Normalized per ton: $1,253.4\text{ CFM} / 3.5\text{ tons} = 358.1\text{ CFM/ton}$ (acceptable for dehumidification in NC).
Example 2: Fan Laws and Sheave Sizing for Commercial Air Handler
Problem: A commercial belt-drive air handler in Greensboro, NC currently delivers $3,200\text{ CFM}$ at a measured fan speed of $650\text{ RPM}$, with a measured static pressure of $0.80\text{ in. w.c.}$ and motor brake horsepower of $1.80\text{ BHP}$. The design specification requires increasing airflow to $3,800\text{ CFM}$.
Calculate: (1) New fan RPM required, (2) New system static pressure, (3) New brake horsepower required, and (4) The required motor pulley diameter if the motor spins at $1,725\text{ RPM}$ and the fan pulley diameter is $9.0\text{ inches}$.
Solution:
-
Calculate New Fan RPM (Fan Law 1):
-
Calculate New Static Pressure (Fan Law 2):
-
Calculate New Brake Horsepower (Fan Law 3): (Note: The existing $2.0\text{ HP}$ motor must be upgraded to a $3.0\text{ HP}$ or $5.0\text{ HP}$ motor to prevent overload burnout!)
-
Calculate Required Motor Pulley Diameter ($D_{\text{motor}}$):
- Install an adjustable $3.8" - 4.4"$ pitch diameter motor sheave adjusted to $4.03"$.
Example 3: Pitot Tube Duct Traverse Air Velocity & Volume
Problem: A technician traverses a $24" \times 16"$ rectangular supply trunk duct with a Pitot tube. The average of 16 velocity pressure readings is $P_{v,\text{avg}} = 0.09\text{ in. w.c.}$
Calculate: (1) Average duct air velocity in Feet Per Minute (FPM), (2) Duct cross-sectional area in square feet, and (3) Total volumetric airflow in CFM.
Solution:
-
Calculate Average Air Velocity:
-
Calculate Duct Cross-Sectional Area:
-
Calculate Total Volumetric Airflow (CFM):
A digital manometer measures return static pressure at -0.28 inches w.c. and supply static pressure at +0.24 inches w.c. on a residential air handler. What is the Total External Static Pressure (TESP)?
An electric furnace operating at 240 Volts and 38 Amps produces a measured temperature rise of 22°F between return and supply air. What is the delivered airflow?
If a commercial belt-driven blower fan currently delivering 2,000 CFM at 1.0 Brake Horsepower (BHP) is adjusted to deliver 2,500 CFM (a 25% increase in airflow), what is the new required Brake Horsepower?
A Pitot tube traverse in a supply trunk duct measures an average velocity pressure (Pv) of 0.16 inches w.c. What is the average air velocity in feet per minute (FPM)?
You've completed this section
Continue exploring other exams