6.2 Mechanical Splices and Couplers (Type 1 and Type 2 Requirements)
Key Takeaways
ACI 318-19 Section 25.5.7.1 requires at least 1.25 times specified yield strength in tension or compression as required.
Type 2 also develops the specified tensile strength of the spliced bars under Section 18.2.7.1.
The Section 18.2.7.2 location exception is for Type 2 on Grade 60 reinforcement, with a separate precast restriction under Section 18.9.2.1(c).
Verify the specific model, bar size, grade and approval. Thread engagement, shear head, swaging and grout checks vary by product.
Measure coupler location, clearance and cover to the applicable surface. Keep field records traceable to the installed units.
6.2 Mechanical Splices and Couplers
Mechanical splices transfer forces through an approved connecting assembly. A sleeve can reduce the space needed for an overlap, but its body can reduce available cover or clearance. Read the plans for the specified splice type and location and use the installation instructions for the actual model.
Recognize the connection and the installation checks
| System | Typical connection method | Evidence to verify |
|---|---|---|
| Parallel-threaded | Prepared bar ends engage an internally threaded assembly | Correct model and thread preparation, required insertion or engagement, seating and any specified witness mark. |
| Taper-threaded | Matching tapered threads seat together | Specified assembly, tool and torque where required. Use the approved method to check exposed threads or seating. |
| Shear screw | Sleeve and mechanical screws grip inserted bars | Specified insertion, alignment and bolt sequence. Verify head breakaway where the approved product uses that indicator. |
| Cold-swaged | A press deforms a sleeve around the bars | Approved sleeve, press and dies, required sequence and specified dimensions or gauge checks. |
| Grout-filled | Bar ends develop force through grout in the sleeve | Specified sleeve, grout, bar insertion, mixing, filling and outlet checks, plus any required strength tests and cure restrictions. |
A product approval may be supported by an ICC Evaluation Service (ICC-ES) Evaluation Report. Check its scope, code editions, approved bar sizes and grades, conditions of use and inspection requirements. Obtain the manufacturer's installation instructions referenced by the approval. If a transition splice is needed, confirm that the exact pair of sizes and grades is covered. Do not infer the transition capacity from the sleeve size or an unrelated report.
Apply the ACI 318-19 strength and location checks
Under Section 25.5.7.1, a mechanical splice must develop at least of the bar in tension or compression as required. Under Section 18.2.7.1, a Type 1 splice meets Section 25.5.7 and a Type 2 splice also develops the specified tensile strength of the spliced bars. Use the specified bar strengths for the classification. The classification is separate from product approval and from installation evidence.
For Grade 60, ksi. In the -16 ASTM editions, A706 Grade 60 has specified minimum tensile strength of 80 ksi and A615 Grade 60 has 90 ksi. For the A706 example, the tensile check for Type 2 is 80 ksi, while the A615 example uses 90 ksi. For Grade 80 the base check is ksi. Verify the product listing for the actual bar specification and grade.
Section 18.2.7 applies to special moment frames and special structural walls. With the Grade 60 Type 2 exception, Section 18.2.7.2 restricts mechanical splice locations within twice the member depth from the column or beam face in a special moment frame or from a critical section where reinforcement yielding is likely under inelastic lateral displacements. Type 2 splices on Grades 80 and 100 are subject to the location restriction. Section 18.9.2.1(c) separately requires beam reinforcement mechanical splices in the covered precast ductile connections to be at least from the joint face and to satisfy Section 18.2.7.
Worked location example. In a 24-inch-deep cast-in-place special moment frame beam, the end-zone check is inches from the column face. A Type 1 splice shown 36 inches from the face is inside this limit. A Type 2 splice on Grade 80 reinforcement at that location has the same restriction. For Type 2 on Grade 60, check the exception, approved location and product conditions.
Verify installation in the field
Start with the approved splice location and identification. Check bar preparation, sleeve model, alignment, insertion and clearances. Use the specified field observation and any test frequency in the approved inspection documents or evaluation. ACI 318-19 Section 26.6.1.1(e) identifies splice type and location as design information. Model IBC Table 1705.3 covers reinforcement placement, and an applicable product approval can specify additional checks.
For example, ICC-ES ESR-2495 describes certain Bar-Lock L- and S/CA-series sleeves with lock-shear bolt heads designed to shear off at their specified installation torque. Head breakaway is a check for that design. It does not verify bar grade, insertion, alignment or other steps. Treat an incomplete assembly according to the applicable procedure and record the result. For a torque-controlled threaded product, verify the required torque and tool method without transferring limits from another model.
Measure spacing and cover where the splice assembly enlarges the reinforcement envelope. Use the approved criteria, including any cover measured to the outside of the assembly in the evaluation report. For coated bars, check the required coupler coating and repair where specified. Record the splice location and identification, discrepancies and the verified disposition.
What strength criteria apply to a Type 2 mechanical splice under ACI 318-19 Section 18.2.7.1?
100% of specified yield and 125% of specified tensile strength
150% of specified yield only
125% of specified yield only
Meet Section 25.5.7 and develop the specified tensile strength of the spliced bars
In a 30-inch-deep cast-in-place special moment frame beam, what does ACI 318-19 Section 18.2.7.2 require for a Type 2 coupler on Grade 80 reinforcement at 48 inches from the column face?
It is allowed anywhere because it is Type 2
It is inside the restricted 60-inch zone and does not meet the location rule
It is outside the restricted 30-inch zone
It is allowed there if surrounded by spiral ties
The approved shear-screw sleeve uses heads that shear off at the specified tightening torque. What observation directly checks that indicator?
Epoxy bonding paste is visible inside the threads
The bolts were tightened to an assumed 150 ft-lb
The specified bolt heads have sheared off at their engineered breakaway points
The sleeve has hydraulic swage marks