8.1 Formwork Inspection, Alignment, Tolerances & Release Agents (ACI 347 & ACI 117)
Key Takeaways
Under model IBC Table 1705.3, the special inspection of formwork concerns the shape, location and dimensions of the member being formed.
ACI 117-10 Section 4.5.1 gives cross-sectional tolerances for elements other than slabs. Separate provisions cover suspended and ground-supported slab thickness.
For ordinary lines and surfaces up to 83 ft 4 in. above the applicable support datum, ACI 117-10 Section 4.1.1 limits deviation from plumb to the smaller of 0.3% of height and 1 inch.
Check line, grade, camber and formed details against their own approved dimensions and measurement datums.
Where ACI 301-20 applies and a release agent is used, apply it before reinforcement is placed, remove excess and keep it off steel and hardened construction-joint surfaces.
Formwork Inspection, Alignment, Tolerances & Release Agents
Forms shape the concrete and must maintain the specified geometry during placement. ACI 318-19 Section 26.11.1.2 requires the formwork design to account for the placement method, rate and construction loads. The section requires forms tight enough to inhibit loss of paste or mortar and braced or tied to maintain position and shape. ACI 301-20 assigns formwork design to the contractor. Model IBC Table 1705.3 item 14 assigns periodic special inspection of the member’s formwork shape, location and dimensions. Check the approved scope and report discrepancies to the contractor under Section 1704.2.4.
1. Verify line, grade and member details
Locate the member using the project grid and benchmark. Measure line and position relative to the applicable grid, elevation relative to the benchmark, and deviation from plumb relative to the vertical reference. A form can be plumb while displaced from its grid, so check location independently. Check the cross section between the actual contact faces, including liners or offsets that affect member dimensions.
Review the specified elevations at supports and at locations such as midspan where the detail shows camber. ACI 301-20 Section 2.3.1.7 addresses setting formwork and screed strips to produce the designated elevation, camber and contour before formwork removal, with allowance for anticipated formwork movement. Check the designated measurement stage and the project tolerances. For an exterior edge with a drip groove, check its shape and position from the approved detail.
Under ACI 301-20 Sections 2.2.1.6 and 2.3.1.2, the default chamfer material is 3/4 by 3/4 inch lumber, and the default chamfer applies to corners of permanently exposed surfaces. The default excludes beveling reentrant corners or edges of formed joints. Check any drawing requirements for a different finish or size. Verify that inserts and chamfers stay in position and that joints and openings are prepared to inhibit mortar leakage.
2. Apply the correct dimensional tolerance
| ACI 117-10 measurement | Specified condition | Tolerance |
|---|---|---|
| Section 4.5.1 cross-sectional thickness of elements other than slabs | 12 in. or less | +3/8 in., −1/4 in. |
| Section 4.5.1 cross-sectional thickness of elements other than slabs | Over 12 through 36 in. | +1/2 in., −3/8 in. |
| Section 4.5.1 cross-sectional thickness of elements other than slabs | Over 36 in. | +1 in., −3/4 in. |
| Section 4.5.3 suspended slab thickness | Applicable suspended slab | −1/4 in. |
| Section 4.4.2 formed surface elevation | Before shores are removed | ±3/4 in. |
| Section 4.2.1 horizontal position of a vertical element | Measured at foundation top or lowest support level | ±1 in. |
ACI 117-10 Section 4.5.1 applies to the completed member. Measurements between form faces before placement help anticipate that result. For a formed 10-inch wall, the numerical thickness bounds are 9-3/4 inches and 10-3/8 inches. Check unformed beams and walls cast against soil separately under Section 4.5.2.
Worked example: Plumbness at 20 and 80 feet
ACI 117-10 Section 4.1.1 applies through 83 ft 4 in. above the foundation top or lowest support level shown. For ordinary lines, surfaces, corners and arrises, use the smaller of 0.3% of the height or 1 inch. At 20 ft, inch, so the limit is 0.72 inch. At 80 ft, inches, so the 1-inch cap governs.
The outside corner of an exposed corner column and grooves in exposed concrete use the separate 0.2% and 1/2-inch limits in Section 4.1.1. At 20 ft, the exposed corner check gives the smaller of inch and 1/2 inch. For taller work, use Section 4.1.2. Local departures from a plane and form irregularities have their own checks.
3. Inspect the form contact surfaces
ACI distinguishes barrier release agents that form a physical film from chemically active agents that react with calcium ions in the paste to form a soap film. Use the specified product for the form-facing material and finish. Chemically active products can help reduce staining and surface air voids in architectural work. Verify the application and any required mockup against the specification.
Where ACI 301-20 Section 2.3.1.15 applies, follow the product instructions, apply the release agent before placing reinforcement, remove excess before concrete placement, and prevent contact with reinforcement or hardened concrete receiving fresh concrete. If oil reaches the cage or a joint face, identify the extent and verify approved cleaning and reinspection before it is concealed. Record the observed contamination and correction.
Under ACI 117-10 Section 4.5.1, what thickness range results for a formed wall specified to be 10 inches thick?
9-3/4 through 10-3/8 inches
9-5/8 through 10-1/2 inches
9-3/4 through 10-1/4 inches
9-1/4 through 11 inches
When ACI 301-20 Section 2.3.1.15 applies and a form release agent is used, which installation complies?
Spray over the installed cage and rely on the concrete to displace residue.
Apply before reinforcement, remove excess and keep it off steel and hardened concrete receiving fresh concrete.
Leave pooled release agent at the base to ease form removal.
Apply release agent to the construction joint after roughening.
An ordinary wall line is checked for plumb 20 ft above the applicable support datum under ACI 117-10 Section 4.1.1. What is the limit?
0.25 inch
0.50 inch
0.72 inch
1.00 inch