16.3 Three-Phase Systems & Phase Sequence
Key Takeaways
- Three-phase generation produces three EMFs displaced by 120 electrical degrees, identified in Australia as L1, L2 and L3 with brown, black and grey conductors
- In a star-connected 400/230 V system, line voltage = √3 × phase voltage, so 230 × 1.732 ≈ 400 V
- In star, line current equals phase current; in delta, line current = √3 × phase current and there is no neutral
- Three-phase power P = √3 × Vₗ × Iₗ × cos φ for a balanced load, and energy is that power multiplied by time
- Phase rotation must be confirmed with a rotation indicator before energising motors and distribution boards — reversed rotation runs motors backwards and can be a serious defect
Three-Phase Systems & Phase Sequence
Quick Answer: Three windings spaced 120° apart produce three EMFs displaced by 120 electrical degrees. In a star-connected Australian supply, Vₗ = √3 × Vₚ gives 230 V phase and 400 V line. Balanced three-phase power is P = √3 × Vₗ × Iₗ × cos φ. Always confirm phase rotation with an indicator before energising rotating plant.
Why Three Phase
Three phases deliver constant total power to a balanced load, allow smaller conductors for the same power transferred, and produce the rotating magnetic field that makes induction motors start without additional apparatus. Every commercial and industrial installation you will meet on the capstone practical is three phase at the switchboard even if the final subcircuits are single phase.
Generation and the 120° Displacement
An alternator carries three windings physically spaced 120° apart in the stator. As the rotor field sweeps past them, each winding reaches its peak EMF one third of a cycle after the previous one. At 50 Hz, one third of a 20 ms cycle is 6.67 ms.
| Phase | Australian identification | Colour (fixed wiring) | Angle |
|---|---|---|---|
| L1 | A phase | Brown | 0° |
| L2 | B phase | Black | 120° |
| L3 | C phase | Grey | 240° |
| N | Neutral | Light blue | Star point |
Because the three sinusoids sum to zero at every instant, a perfectly balanced star-connected load draws no neutral current. Real installations are never perfectly balanced, which is why the neutral is still installed and still sized properly, and why harmonic currents from electronic loads can make neutral current exceed line current in some circuits.
Star (Wye) Connection
The three winding ends are joined at a common star point, which becomes the neutral and, in a MEN installation, is earthed at the distributor’s transformer.
- Line voltage Vₗ = √3 × phase voltage Vₚ → 230 × 1.732 = 398 V, nominally 400 V.
- Line current Iₗ = phase current Iₚ.
That single relationship explains the Australian 400/230 V description: 400 V between any two actives, 230 V between any active and the neutral.
Delta Connection
The three windings are connected end to end in a closed loop, with the lines taken from the junctions. There is no neutral.
- Line voltage Vₗ = phase voltage Vₚ.
- Line current Iₗ = √3 × phase current Iₚ.
Delta is common for motor windings and for the primary of distribution transformers. A three-phase motor nameplate showing 400 V delta / 690 V star tells you which connection suits which supply.
Power and Energy in Three-Phase Circuits
For a balanced load:
- Apparent power S = √3 × Vₗ × Iₗ (VA)
- True power P = √3 × Vₗ × Iₗ × cos φ (W)
- Energy W = P × t (Wh, or kWh when P is in kW and t in hours)
Worked example. A balanced three-phase load draws 25 A per line at 400 V with a power factor of 0.85.
- S = 1.732 × 400 × 25 = 17,320 VA ≈ 17.3 kVA
- P = 17,320 × 0.85 = 14,722 W ≈ 14.7 kW
- Running 8 hours a day: W = 14.7 × 8 = 117.8 kWh per day
Reverse-worked example — the version that appears on maximum demand papers. A 30 kW balanced load at 400 V and 0.9 power factor draws:
Iₗ = P / (√3 × Vₗ × cos φ) = 30,000 / (1.732 × 400 × 0.9) = 30,000 / 623.5 = 48.1 A
That current — not the kilowatt figure — is what you take into cable selection and protective device coordination.
Phase Sequence and Rotation
Phase sequence is the order in which the three phases reach their positive peaks: L1–L2–L3 (often called ABC or clockwise) or the reversed L1–L3–L2.
Why it matters:
- A three-phase induction motor rotates in the direction set by the sequence. Reverse any two lines and the motor runs backwards — which can destroy a pump, a conveyor, a compressor or a lift.
- Parallel sources and generator changeover schemes require matching sequence.
- Multi-board installations must keep sequence consistent so downstream plant behaves predictably.
Methods of determining rotation:
- Rotating-disc or LED phase rotation indicator connected to the three lines — the standard site instrument, giving a clear clockwise/anticlockwise or L1-L2-L3 indication.
- Two-wattmeter or phase-angle instruments in engineering contexts.
- Oscilloscope comparison of waveforms where instrumentation permits.
Trial-and-error — energising the motor and watching which way it spins — is not an acceptable capstone answer where the driven machine can be damaged or people can be hurt.
Correcting rotation: swap any two line conductors at the isolator or motor terminals. Never swap the neutral or the protective earthing conductor to change rotation. Re-label conductors correctly after the change, retest polarity, and record the result.
Practical Discipline
- Confirm rotation before connecting rotating plant, and after any board or supply alteration.
- Check that phase identification is consistent from origin to final board — crossed phases between boards is a defect even when everything still runs.
- Measure and record all three line-to-line and line-to-neutral voltages during commissioning; unequal readings point to a loose connection, a lost phase or an unbalanced load.
- Remember that a lost neutral on a star-connected installation lets connected single-phase loads see up to line voltage — one of the most destructive faults in a domestic or commercial board.
In a star-connected 400/230 V supply, what is the relationship between line voltage and phase voltage?
A balanced three-phase load draws 40 A per line at 400 V with a power factor of 0.9. What true power is being consumed?
A three-phase motor runs in the wrong direction after a switchboard alteration. What is the correct remedy?
Why is energising a motor to observe its direction an unacceptable way to determine phase rotation on a capstone practical?