2.4 Electrical Theory for the Exam: Ohm's Law, Power & Three-Phase
Key Takeaways
- Ohm's law and the power formulas cover most single-phase theory items: E = I x R and P = E x I, with P = I squared x R for conductor heating.
- Single-phase apparent power is VA = E x I; three-phase apparent power is VA = 1.732 x E-line x I-line, so a three-phase line current is kVA x 1000 divided by (1.732 x line voltage).
- Power factor is real power divided by apparent power, so line current rises as power factor falls for the same kilowatt load.
- In a balanced wye system, line voltage equals 1.732 times phase voltage while line current equals phase current; in a delta system, line current equals 1.732 times phase current while line voltage equals phase voltage.
- The single-phase voltage-drop formula is VD = 2 x K x I x L divided by CM; the three-phase version substitutes 1.732 for the 2, using K of about 12.9 for copper and 21.2 for aluminum.
The Formulas Worth Owning
The NEC contains rules, not physics. Theory questions and the arithmetic inside code questions come from a short list of relationships. Write these on the inside cover of your working notes and drill until they are automatic.
Ohm's Law and Power
| Quantity | Formula |
|---|---|
| Voltage | E = I x R |
| Current | I = E / R |
| Resistance | R = E / I |
| Power (resistive) | P = E x I |
| Power from current and resistance | P = I squared x R |
| Power from voltage and resistance | P = E squared / R |
P = I squared x R is the one that explains the Code. Conductor heating rises with the square of current, which is why ampacity tables exist, why bundling forces adjustment, and why a 20 percent overload is far worse than it sounds.
Single-Phase Current
I = VA / E (apparent power)
I = (kW x 1000) / (E x PF) (real power with power factor)
A 9.6 kW, 240 V single-phase resistance heater at unity power factor draws 9600 / 240 = 40 A.
Three-Phase Current
I(line) = VA / (1.732 x E-line)
I(line) = (kW x 1000) / (1.732 x E-line x PF)
The 1.732 is the square root of 3. A 30 kW, 480 V three-phase heater at unity power factor draws 30,000 / (1.732 x 480) = 30,000 / 831.4 = 36.1 A.
A 75 kVA, 208 V three-phase transformer secondary delivers 75,000 / (1.732 x 208) = 75,000 / 360.3 = 208.2 A. That number is worth remembering as a sanity check: a 75 kVA 208Y/120 V transformer is roughly a 200 A secondary.
Power Factor
PF = P (watts) / S (volt-amperes)
Power factor is the ratio of real power doing work to apparent power the system must carry. Purely resistive loads — heaters, incandescent lamps — run at unity. Motors and transformers run lagging because magnetizing current does no work.
The practical consequence is that current increases as power factor falls. A 20 kW three-phase 480 V load at unity PF draws 24.1 A. The same 20 kW at 0.80 PF draws 20,000 / (1.732 x 480 x 0.80) = 30.1 A — the conductors, raceway, and overcurrent device must all be sized for the larger figure.
The power triangle relates the three: apparent power S in kVA is the hypotenuse, real power P in kW is the horizontal leg, and reactive power Q in kVAR is the vertical leg, with S squared = P squared + Q squared.
Wye and Delta Relationships
These two sets of relationships are frequently reversed in distractor answers:
| System | Voltage | Current |
|---|---|---|
| Wye (star) | E-line = 1.732 x E-phase | I-line = I-phase |
| Delta | E-line = E-phase | I-line = 1.732 x I-phase |
A 208Y/120 V system is a wye: 120 V phase-to-neutral, 120 x 1.732 = 208 V phase-to-phase. A 480Y/277 V system is the same relationship scaled: 277 x 1.732 = 480 V.
The high-leg delta. A 240/120 V three-phase four-wire delta has a centre tap on one winding, giving 120 V to neutral on two phases and 208 V to neutral on the third — the "high leg" or "wild leg." 110.15 requires the high leg to be durably and permanently marked by an orange outer finish or other effective means at each point where a connection is made if the grounded conductor is present, and 408.3(E)(1) requires it to be phase B in switchboards and panelboards. Never land a 120 V load on the high leg.
Voltage Drop
Voltage drop is a performance issue, not a mandatory rule for most conductors. The 3 percent branch-circuit and 5 percent total figures live in Informational Notes to 210.19(A) and 215.2(A), which 90.5(C) makes non-enforceable. Some specific rules do mandate voltage-drop limits — 647.4(D) for sensitive electronic equipment, 695.7 for fire pumps, and Article 690 for PV — but for ordinary branch circuits and feeders the 3/5 figures are recommendations.
The Circular-Mil Formulas
Single-phase: VD = (2 x K x I x L) / CM
Three-phase: VD = (1.732 x K x I x L) / CM
Solve for wire size:
Single-phase: CM = (2 x K x I x L) / VD
Three-phase: CM = (1.732 x K x I x L) / VD
Where K is the resistivity constant — approximately 12.9 for copper and 21.2 for aluminum — I is load current in amperes, L is the one-way length in feet, CM is the conductor's circular-mil area from Chapter 9, Table 8, and VD is the voltage drop in volts. The 2 in the single-phase formula accounts for the out-and-back path, which is why L is one-way.
Useful circular-mil values from Table 8: 14 AWG = 4,110; 12 AWG = 6,530; 10 AWG = 10,380; 8 AWG = 16,510; 6 AWG = 26,240; 4 AWG = 41,740; 3 AWG = 52,620; 2 AWG = 66,360; 1 AWG = 83,690; 1/0 = 105,600.
Worked Example 1 — Find the Drop
A 240 V single-phase circuit carries 30 A to a load 150 feet away on 10 AWG copper.
VD = (2 x 12.9 x 30 x 150) / 10,380
= 116,100 / 10,380
= 11.19 V
That is 11.19 / 240 = 4.7 percent — beyond the 3 percent recommendation, so upsize if performance matters.
Worked Example 2 — Find the Wire Size
A 480 V three-phase load draws 50 A over 400 feet, and you want to hold the drop to 3 percent (0.03 x 480 = 14.4 V) using copper.
CM = (1.732 x 12.9 x 50 x 400) / 14.4
= 446,856 / 14.4
= 31,032 circular mils
From Table 8, 6 AWG is 26,240 CM — too small. 4 AWG at 41,740 CM is the smallest conductor that satisfies the target. Always verify separately that the chosen conductor also meets its ampacity requirement; voltage drop can only drive you larger, never smaller.
What is the line current of a 45 kVA, 208 V three-phase transformer secondary at full load?
A 20 kW three-phase load operates at 480 V with a power factor of 0.80. What is the line current?
In a balanced three-phase delta system, what is the relationship between line current and phase current?
A 120 V single-phase branch circuit carries 16 A over a one-way distance of 100 feet using 12 AWG copper with a circular-mil area of 6,530. What is the approximate voltage drop?