Free PE Electrical Power Exam Flashcards

Memorize 50 essential terms and definitions for the NCEES Principles and Practice of Engineering (PE) Electrical and Computer: Power. See the term, recall the definition, then flip to check yourself.

50 Flashcards
9 Topics
100% Free
TermClick to flip

A meter reads 3.5 A on the secondary of a 600:5 current transformer. What primary current does that represent?

Tap to reveal definition
Card 1 of 50Measurement & Instrumentation

Filter by Topic

Jump to Card

About These PE Electrical Power Flashcards

These 50 flashcards are designed to help you memorize key terms and definitions for the NCEES Principles and Practice of Engineering (PE) Electrical and Computer: Power. Each card shows a term on the front and its definition on the back—the classic flashcard format for vocabulary memorization. Use these alongside our practice questions to build both recall and comprehension.

Topics Covered

Measurement & Instrumentation4 cards
General Applications6 cards
Electrical Safety7 cards
Circuit Analysis7 cards
Power Electronics & Controls4 cards
Rotating Machines4 cards
Electric Power Devices5 cards
Transmission & Distribution6 cards
Protection7 cards

Complete Flashcard Reference

Review every term in this set. Open any term to reveal its definition.

A meter reads 3.5 A on the secondary of a 600:5 current transformer. What primary current does that represent?

About 420 A. Multiply by the rated primary-to-secondary ratio, 600 ÷ 5 = 120. This assumes the CT is operating accurately.

A diagram shows an open CT secondary while primary current still flows. What electrical hazard does that create?

The open secondary can develop a hazardous voltage while primary current flows. That voltage can cause electric shock or damage insulation.

How is polarization index (PI) calculated in a DC insulation-resistance test?

Divide the insulation resistance at 10 minutes by its value at 1 minute during the same test. The ratio is dimensionless and describes how the resistance changes with time.

What does a plateau on a fall-of-potential ground-test plot represent?

The nearly flat region gives the electrode’s resistance to earth when the current probe is far enough away. The reading changes little as the potential probe moves through this region.

A meter records 18 kWh during one 15-minute demand interval. What was the average demand?

72 kW. Divide the energy by 0.25 hour. If this is the highest interval average in the billing period, it is the measured peak demand.

How is demand factor calculated for a group of loads?

Divide the group’s maximum demand by its total connected load, using the same power units. The ratio shows how much of the connected load is demanded at the group’s peak.

What does one lux measure?

One lumen of incident luminous flux per square meter. Lux describes the light falling on a surface.

How does a parallel surge protective device limit a voltage spike?

It briefly provides a lower-impedance path for surge current. Diverting that current limits the transient voltage seen by equipment connected to the circuit.

What is the job of an air terminal on a roof lightning protection system?

It provides a strike attachment point. The connected lightning protection conductors and grounding system carry the intercepted current toward earth.

Why bond a metal enclosure to the equipment grounding path?

Bonding provides an electrically continuous, low-impedance path back to the source. A fault to the enclosure can then drive enough current for the circuit’s overcurrent protection to operate.

Which overcurrent device marks the start of a branch circuit?

The final overcurrent device protecting that circuit. The branch-circuit conductors run from that device to the outlets. A feeder supplies branch-circuit overcurrent devices.

What current measurement makes a GFCI trip?

It senses an imbalance between current leaving and returning on the circuit conductors. A sufficient imbalance opens the circuit to reduce the risk of shock from current taking another path.

What hazard distinguishes Class I from Class II locations?

Class I deals with flammable gases or vapors. Class II deals with combustible dust. The class identifies the type of material that can create an ignition hazard.

When is a gas or vapor hazard typically Division 2 in the Class I system?

In a common Division 2 case, ignitable concentrations are expected only under abnormal conditions, such as a leak from closed equipment. Division 1 can include ignitable concentrations during normal operation.

Why must absence of voltage be verified after opening the disconnect?

The circuit can still be energized by backfeed, induced voltage, or another source. A qualified person verifies absence of voltage with suitable test equipment as part of establishing the deenergized condition.

What causes an arc-flash burn even without body contact with a live part?

Thermal energy released by the electric arc can burn exposed skin or ignite clothing. Electric shock occurs when current passes through the body.

What does an NEC Article 700 emergency system supply when normal power fails?

It automatically provides power, lighting, or both to designated life-safety loads, such as required egress lighting.

A balanced three-phase load draws 41 kW from a 460 V line-to-line supply at 0.86 power factor. What is its line current?

About 59.8 A RMS. Rearrange P = √3 × line-to-line RMS voltage × RMS line current × power factor, then divide 41,000 W by √3 × 460 V × 0.86.

How does line current magnitude compare with winding current magnitude in a balanced delta?

Line current is √3 times the winding current. Each line current is the phasor difference of the two winding currents at that line terminal.

What impedance base corresponds to 34.5 kV line-to-line and 25 MVA three-phase?

47.61 Ω. Use Zbase = Vbase² ÷ Sbase with the line-to-line voltage base and total three-phase apparent-power base. kV²/MVA gives ohms.

What is the zero-sequence current component in terms of the three phase-current phasors?

I0 = (Ia + Ib + Ic) / 3. The zero-sequence components of the three phases are equal in magnitude and phase.

How does sinusoidal current through an ideal inductor align with the voltage?

Current lags voltage by 90°. In a phasor diagram, the current is a quarter-cycle behind the voltage.

How do RMS voltage and current phasors give single-phase complex power into a load?

Multiply the voltage by the complex conjugate of the current, S = V × I*. With current entering the positive-voltage terminal, the real part is watts and the imaginary part is vars.

What two quantities define the Thévenin equivalent of a linear DC network at a pair of terminals?

The open-circuit terminal voltage and the resistance looking back into the network. Model them as an ideal voltage source in series with that resistance.

An ideal buck converter runs in continuous conduction from a 48 V DC source at 37.5% duty. What is its average output voltage?

18 V DC. In steady state, multiply the input voltage by the duty cycle as a fraction, 48 V × 0.375.

Why does a scalar drive keep the voltage-to-frequency ratio roughly constant below base speed?

The ratio helps maintain motor air-gap flux as the drive changes frequency. Keeping the flux near its rated value preserves torque capability in that range.

What does a grid-forming inverter establish that a grid-following inverter typically tracks?

A voltage waveform with its own phase and frequency reference. A grid-following inverter typically synchronizes its current injection to a voltage waveform already present on the grid.

What Boolean operation do two normally open ladder contacts in series implement?

AND. Both contacts must evaluate true to make that series path true.

A synchronous generator turns at 750 rpm and produces 50 Hz. How many poles does it have?

Eight poles. Rearrange nₛ = 120f/p to p = 120 × 50 ÷ 750. Use electrical frequency in hertz and mechanical speed in rpm.

A motor’s rotor runs at 1,164 rpm while its rotating field runs at 1,200 rpm. What is its slip?

3%. Divide the speed difference, 36 rpm, by synchronous speed, 1,200 rpm. Use the rotating field’s speed as the denominator.

How does starting torque in wye compare with direct-on-line starting in delta for the same motor and supply?

Roughly one-third. Each winding sees 1/√3 of its delta starting voltage, and starting torque is approximately proportional to winding voltage squared.

What does adjusting field excitation change in a grid-connected synchronous motor at essentially fixed shaft load?

It changes the reactive power exchanged with the grid and therefore the motor’s power factor. Sufficient overexcitation can make the motor supply reactive power at a leading power factor.

An ideal transformer has 800 primary turns and 120 secondary turns. What secondary voltage results from 2,400 V across the primary winding?

360 V across the secondary winding. Multiply the primary winding voltage by the secondary-to-primary turns ratio, 120 ÷ 800.

What loss does the input wattmeter mainly measure during a transformer’s rated-voltage, rated-frequency open-circuit test?

Core loss from hysteresis and eddy currents. With the other winding open, the small excitation current makes winding copper loss comparatively small.

When is a supercapacitor a better fit than a battery for a given storage duty?

When the duty calls for frequent, short bursts of high power and rapid recharging. Supercapacitors generally store less energy per unit mass than batteries.

What happens to the energy stored in a capacitor if its voltage doubles at fixed capacitance?

It quadruples. Stored energy is ½CV², so the voltage enters as a square.

What does a bypass diode do when a shaded PV substring is driven sufficiently into reverse bias?

It carries string current around the affected substring. This limits the reverse voltage across the substring and reduces the risk of hot-spot damage.

How do R and X contribute to approximate line-to-line drop on a balanced three-phase feeder with a lagging load?

ΔV ≈ √3 I(R cos φ + X sin φ). I is RMS line current, R and X are total series values per phase for the one-way run, and φ is the angle by which load current lags voltage.

How many capacitive kvar are needed to bring an 80 kW load from 0.80 to 0.95 lagging power factor?

About 33.7 kvar. Use Qc = P(tan φbefore − tan φafter), with each φ equal to arccos of its power factor. The capacitor reduces the reactive power drawn from the source.

Why can a balanced three-phase, four-wire feeder carry third-harmonic current in its neutral?

The third-harmonic currents in the three phases are in phase with one another and add in the neutral. Balanced fundamental currents cancel.

What is the symmetrical RMS current for a bolted three-phase fault at an 11.4 kV bus with a positive-sequence Thévenin impedance magnitude of 0.36 Ω?

About 18.3 kA per line. Treating 11.4 kV as the prefault line-to-line RMS voltage, divide 11.4 kV/√3 by 0.36 Ω. A balanced fault uses the positive-sequence network.

Why can zero-sequence current circulate in a closed delta winding without appearing in its line leads?

Equal in-phase winding currents can circulate around the delta. Each line current is the difference of two winding currents, so the zero-sequence contributions cancel at each terminal.

What does transient rotor-angle stability ask after a major disturbance such as a short circuit?

Whether the interconnected synchronous machines remain in synchronism through the disturbance and its aftermath. Large rotor-angle swings can cause a machine or group to lose synchronism.

What distinguishes protective relay functions 50 and 51?

Function 50 is instantaneous overcurrent, with no intentional delay. Function 51 is time overcurrent and operates according to a time characteristic after pickup.

What does current differential protection measure to detect an internal fault?

It compares currents at the zone boundaries using a common sign convention. A net current into the zone above the relay’s operating threshold indicates a possible internal fault.

What electrical quantity does a distance relay use to judge fault reach?

Apparent impedance calculated from the appropriate fault-loop voltage and current. The relay compares the result with its configured reach characteristic.

Why does a distribution recloser close again after interrupting fault current?

A temporary fault may clear while the line is deenergized, so reclosing can restore service. A persistent fault can cause repeated trips and eventual lockout under the programmed sequence.

What current must a breaker’s interrupting rating cover?

At the applicable voltage, it must cover at least the maximum available fault current at its installation point. The continuous ampere rating describes normal current carrying capability.

What should happen to the upstream breaker when a downstream fault is selectively coordinated?

It should stay closed while the protective device feeding the fault clears it. Unaffected branches remain powered.

What extra condition does directional overcurrent protection check before tripping?

It checks whether the fault is in the selected direction relative to the relay. This helps a relay distinguish faults on opposite sides where current can be supplied from more than one direction.

Frequently Asked Questions

How long is the PE Power exam and how many questions are there?

The year-round computer-based exam has 80 questions and 8 hours of answering time. The 9-hour appointment also allows 2 minutes for the nondisclosure agreement, 8 minutes for the tutorial, and 50 minutes for an optional scheduled break. The 80 questions include unidentified, unscored pretest items.

What score do I need to pass PE Power?

NCEES does not publish a passing score. It scales the number of correct answers to account for differences in exam-form difficulty and reports pass or fail. There is no deduction for a wrong answer. Alternative item types receive no partial credit.

What is the PE Power pass rate?

In the NCEES July 2026 update for the January–June cohort, 62% of 1,344 first-time examinees and 42% of 721 repeat examinees passed. These percentages describe the two groups’ results.

Which references are available during PE Power?

NCEES supplies the searchable PE Power Reference Handbook and the standards on the October 2025 specification. They include NFPA 70-2020 (NEC), NFPA 70E-2021 and ANSI C2-2017 (NESC), plus NFPA 30B-2023, NFPA 497-2021 and NFPA 499-2021. Use the listed editions for exam questions and get the handbook through MyNCEES. Personal reference copies are prohibited.

Do I need board approval to register for PE Power?

Start with the licensing board for your jurisdiction. NCEES describes the PE exam as designed for engineers with at least four years of post-college experience. Your board determines when you can sit, whether a separate application or approval is needed, and what is required for licensure.

How soon can I retake the PE Power exam?

NCEES permits one attempt per calendar quarter and no more than three attempts in any 12-month period. If you reach the cap, choose an unused testing window when an earlier attempt has dropped out of the 12-month count. Check your board’s policy for additional restrictions.

How are these flashcards weighted?

The set uses the midpoints of the nine question ranges in the NCEES specification effective October 2025, scaled to 50 cards. Use the published ranges when planning practice. The exact mix of questions can vary by exam form.

Same family resources

Explore More PE Exams

Continue into nearby exams from the same family. Each card keeps practice questions, study guides, flashcards, videos, and articles in one place.