8.2 Water Distribution Design: Flow and Pressure Criteria, Fixture Supplies & Pipe Sizing

Key Takeaways

  • Table 604.3 minimum flow pressures: 8 psi for most faucets, 20 psi for shower and tub mixing valves and tank water closets, 25 psi for urinal flush valves, 35 psi for siphonic flushometer water closets and 45 psi for blowout flushometer water closets.

  • Table 604.5 minimum fixture supply sizes: lavatory, bidet, drinking fountain and flush-tank water closet 3/8 inch; most sinks, tubs and showers 1/2 inch; urinal flushometer valve 3/4 inch; and water closet flushometer valve 1 inch.

  • A fixture supply pipe must end no more than 30 inches from its connection to the fixture (604.5).

  • In Appendix E Table E103.3(2), a private flush-tank water closet is 2.2 wsfu, a public flushometer-valve water closet 10 wsfu, and a private lavatory 0.7 wsfu total.

  • From Table E103.3(3), 10 wsfu demands 14.6 gpm in a flush tank system but 27 gpm in a flushometer valve system; the two curves meet at about 1,000 wsfu (208 gpm).

Last updated: October 2026

Design criteria (IPC 604.1 to 604.4)

  • 604.1 and 604.2: the design must follow accepted engineering practice, and sizing methods must be approved. Appendix E gives one method. The IPC appendices are informative unless a jurisdiction adopts them, so the building official decides which method is approved.
  • 604.3: pipe must be sized so that, under peak demand, each fixture supply outlet receives at least the flow and pressure in Table 604.3. Fixtures not listed use the manufacturer's values.

Table 604.3: required capacity at fixture supply outlets

Fixture supply outletFlow rate (gpm)Flow pressure (psi)
Bathtub, balanced-pressure, thermostatic or combination valve420
Bidet, thermostatic mixing valve220
Combination fixture48
Dishwasher, residential2.758
Drinking fountain0.758
Laundry tray48
Lavatory, private0.88
Lavatory, public0.48
Shower2.58
Shower with balanced-pressure, thermostatic or combination valve2.520
Sillcock, hose bibb58
Sink, residential1.758
Sink, service38
Urinal, valve1225
Water closet, blowout, flushometer valve2545
Water closet, siphonic, flushometer valve2535
Water closet, flushometer tank1.620
Water closet, tank, close coupled320
Water closet, tank, one piece620

Table 604.3 sets the minimum supply at the outlet. Table 604.4 sets the maximum consumption of the fixture (for example, 1.6 gallons per flush or 2.5 gpm at 80 psi). Do not confuse the two.

Fixture supplies (IPC 604.5) and manifolds (IPC 604.10)

Table 604.5 minimum fixture supply pipe sizes:

FixtureMinimum size
Lavatory, bidet, drinking fountain3/8 inch
Water closet, flush tank or flushometer tank3/8 inch
Water closet, one piece1/2 inch
Bathtub, shower, kitchen sink, laundry, domestic dishwasher, service sink, hose bibb, wall hydrant, urinal flush tank1/2 inch
Sink, flushing rim; urinal, flushometer valve3/4 inch
Water closet, flushometer valve1 inch
  • The fixture supply pipe must end no more than 30 inches from the point of connection to the fixture. A reduced-size flexible connector between the supply and the fixture must be an approved type, and the supply pipe must extend to the floor or wall next to the fixture.
  • Footnote: in a parallel (manifold) system, where the distribution line is 50 feet or less and the pressure at the meter is at least 35 psi, each line may be one size smaller than the table.
  • 604.10.1 manifold sizing (Table 604.10.1): a manifold is sized by total gpm. A 1/2-inch manifold handles 2 gpm at 4 feet per second and 5 gpm at 8 feet per second; 3/4 inch handles 6 and 11 gpm; 1 inch, 10 and 20 gpm. 604.10.2: valves at the manifold are identified by fixture. 604.10.3: manifolds with valves need access.

The fixture unit method (IPC Appendix E)

Hunter's probability method assigns each fixture water supply fixture units (wsfu), then converts the total wsfu to a design flow in gpm. The method accounts for the fact that not all fixtures run at once.

Table E103.3(2): selected wsfu values (cold / hot / total)

FixtureOccupancySupply controlColdHotTotal
Bathroom groupPrivateFlush tank2.71.53.6
Bathroom groupPrivateFlushometer valve6.03.08.0
BathtubPrivate / PublicFaucet1.0 / 3.01.0 / 3.01.4 / 4.0
Kitchen sinkPrivate / Hotel, restaurantFaucet1.0 / 3.01.0 / 3.01.4 / 4.0
LavatoryPrivate / PublicFaucet0.5 / 1.50.5 / 1.50.7 / 2.0
Shower headPrivate / PublicMixing valve1.0 / 3.01.0 / 3.01.4 / 4.0
Service sinkOfficesFaucet2.252.253.0
UrinalPublic1-inch / 3/4-inch flushometer valve10.0 / 5.0—10.0 / 5.0
Washing machine (8 lb)Private / PublicAutomatic1.0 / 2.251.0 / 2.251.4 / 3.0
Water closetPrivateFlush tank2.2—2.2
Water closetPrivateFlushometer valve6.0—6.0
Water closetPublicFlush tank5.0—5.0
Water closetPublicFlushometer valve10.0—10.0
Water closetPublic or privateFlushometer tank2.0—2.0

The total for a fixture with hot and cold supply is less than cold plus hot, because both are not drawn at full flow at the same time. Use the cold column to size cold-only piping, the hot column for hot piping, and the total for the service and main up to the water heater branch.

Table E103.3(3): estimating demand

Load (wsfu)Flush tank systems (gpm)Flushometer valve systems (gpm)
59.415.0
1014.627.0
2019.635.0
5029.150.0
10043.567.5
20065.090.0
500124.0143.0
1,000208.0208.0

A flushometer valve opens fully and draws about 25 gpm for a few seconds (Table 604.3), so even a few flushometers need a large design flow. A flush tank refills slowly. As a system grows, the chance of many simultaneous draws evens out, and the two curves meet at about 1,000 wsfu.

The pressure budget

Appendix E sizes pipe by finding the pressure available for friction:

  1. Start with the minimum available pressure at the source (604.6: design for the minimum).
  2. Subtract elevation: 0.433 psi per foot of rise. One psi lifts water 2.31 feet.
  3. Subtract fixed losses: the water meter, backflow preventer, PRV, softener and filters, using manufacturers' data at the design flow.
  4. Subtract the pressure required at the most remote, highest outlet (Table 604.3, or the manufacturer's value).
  5. Divide what remains by the developed length plus an allowance for fittings to get the allowable friction loss per 100 feet.
  6. Choose pipe sizes from friction-loss charts for the design gpm of each section, and check velocity.

Example: the street has a minimum of 60 psi. The highest flushometer valve water closet (siphonic) is 25 feet above the main, and the meter and backflow assembly lose a combined 12 psi at design flow. Available for friction: 60 − (25 × 0.433 = 10.8) − 12 − 35 = 2.2 psi. That is very little, so the designer must either use larger pipe or add a booster system (604.7).

Velocity

Apart from the manifold table and the general water hammer rule (604.9), the IPC does not set a maximum velocity. The Copper Development Association recommends about 8 feet per second maximum for cold water, about 5 feet per second for hot water up to about 140°F, and 2 to 3 feet per second where water routinely exceeds 140°F, to limit erosion-corrosion and noise. A handy formula is:

V=0.408×Qd2V = \frac{0.408 \times Q}{d^2}

where V is velocity in feet per second, Q is flow in gpm, and d is the inside diameter in inches. Example: 10 gpm in tube with a 0.785-inch inside diameter: V = 0.408 × 10 ÷ 0.616 ≈ 6.6 feet per second.

Loading diagram...
Sizing a water distribution system
Test Your Knowledge

Under IPC Table 604.3, what minimum flow pressure must be available at a siphonic flushometer valve water closet?

A

20 psi

B

40 psi

C

35 psi

D

8 psi

Test Your Knowledge

Under IPC Table 604.5, what is the minimum fixture supply pipe size for a water closet with a flushometer valve?

A

1 inch

B

3/4 inch

C

1/2 inch

D

3/8 inch

Test Your Knowledge

Using Appendix E Table E103.3(3), what is the estimated demand for a 10-wsfu load in a system supplying predominantly flush tanks, and in a system with flushometer valves?

A

8 gpm and 27 gpm

B

14.6 gpm and 35 gpm

C

19.6 gpm and 27 gpm

D

14.6 gpm and 27 gpm

Sections you finish are checked off in the contents.