13.1 Analog and Discrete Signal Types
Key Takeaways
- A 4–20 mA live zero encodes 0% of span at 4 mA and 100% at 20 mA; about 0 mA is an open or unpowered loop, not a valid zero process reading.
- Process value scales on the 16 mA span: PV = LRV + (I − 4)/16 × (URV − LRV), so 12 mA is always 50% of a 4–20 mA calibration.
- A 250 Ω burden converts 4–20 mA to 1–5 V; voltage signals then treat IR drop as measurement error, which is why current is used for long analog runs.
- 3–15 psi pneumatic is the live-zero air analog of 4–20 mA (3 psi = 0%, 15 psi = 100%, 9 psi = 50%); lost air goes toward 0 psig, not 0% process.
- NAMUR NE43 fail bands (about ≤ 3.6 mA or ≥ 21 mA) are industry practice for smart analog transmitters, not an NCEES-supplied handbook table; do not confuse them with NAMUR proximity currents.
Why analog versus discrete is a Signals item
The PE Control Systems Signals domain is 11–17 questions. Specification 4.A opens with analog and discrete types because loop voltage budget, HART overlay, analog-input scaling, and discrete diagnostics all assume you can look at a milliamp, a volt, a psi, a millivolt, or a contact and know what a broken wire would do. Those signals usually terminate in a distributed control system (DCS) or programmable logic controller (PLC) analog or discrete input. Picking the wrong family is a failed design, not a unit-conversion slip.
Live zero: 4–20 mA, and why 0 mA is not 0%
A 4–20 mA current loop encodes 0% of calibrated span at 4 mA and 100% at 20 mA. The 4 mA floor is a live zero (elevated zero). Two reasons both show up on the exam:
- Fault discrimination. An open pair, a dead supply, or a transmitter that has stopped conducting produces about 0 mA. That is a circuit failure, not a process sitting at lower range value. If the span started at 0 mA, a broken wire would look identical to a valid zero reading.
- Two-wire power. A loop-powered transmitter must take operating current from the same pair that carries the signal. The 4 mA floor is the current the electronics are allowed to consume at 0% process; the remaining 16 mA is the modulation span.
Scale linearly on that 16 mA span. If $I$ is loop current in milliamps, LRV is lower range value, and URV is upper range value:
Worked example: 12 mA is 50%
A differential-pressure transmitter is calibrated 4–20 mA = 0–200 inH2O. The analog input reads 12.00 mA.
12 mA is always 50% of a 4–20 mA span, regardless of engineering units. Check a second point: 7.2 mA is $(7.2 - 4)/16 = 0.20$, so the same 0–200 inH2O range reads 40 inH2O. The classic trap is treating 12 mA as $12/20 = 60%$ and reporting 120 inH2O — that ignores live zero.
The 1–5 V signal is the same live-zero idea after Ohm's law. A 250 Ω precision resistor (or analog-input burden) converts 4.00 mA → 1.00 V and 20.00 mA → 5.00 V. Voltage drop in the signal leads then appears as a reading error, which is why current — not voltage — is the long-run analog workhorse.
Other analog families
3–15 psi pneumatic is the live-zero air analog: 3 psig = 0%, 15 psig = 100%, span 12 psi. 9 psi is 50%. A failed air supply or a blown tube heads toward 0 psig, which is not 0% process. Pneumatic still appears on valve actuators, I/P (current-to-pneumatic) transducers, and electrically dead or intrinsically safe areas. Limits are compressibility lag, leaks, freeze-up of wet instrument air, and tubing volume — not induced millivolts.
Thermocouple millivolts are tens of millivolts. They need cold-junction compensation, shielded twisted pair, and usually a local transmitter if the run is long. Ground loops and electromagnetic interference swamp millivolts long before they swamp 4–20 mA.
A resistance temperature detector (RTD) (typically Pt100 = 100 Ω at 0 °C) is a resistance, not a current. Lead-wire resistance is a direct temperature bias on 2-wire connections; 3-wire and 4-wire circuits cancel or measure the leads. An RTD does not “output 12 mA” unless a transmitter is already in the loop.
Pulse / frequency comes from turbine meters, positive-displacement meters, speed probes, and some flow computers. The information is in the count or frequency, not in an analog level. Debounce, pull-up, and the maximum frequency of the high-speed counter card matter. A 4–20 mA analog of the same flow is a different signal with a different error budget.
Discrete: dry contact and NAMUR proximity
A dry contact is a switch with no voltage of its own. The discrete-input card supplies wetting voltage; the field device only closes or opens. Wetting current too low → oxidized contacts and missed closures. Leakage on a wet long cable → false ON. Polarity usually does not matter for a true dry contact, but it does matter if the “contact” is actually a solid-state output.
A NAMUR proximity sensor (IEC 60947-5-6) is a 2-wire current-level discrete, typically powered at about 8.2 V through a switching amplifier. Conventional bands: ≤ about 1.2 mA with the target present (damped), ≥ about 2.1 mA with the target absent. About 0 mA is an open wire; a very high current is a short. That three-way diagnostic (off / on / cable fault) is why NAMUR sensors appear in safety and hazardous-area designs. Do not confuse NAMUR proximity currents with NAMUR NE43 analog-failure currents — different documents, different milliamps.
NAMUR NE43 analog failure currents (practice, not a supplied table)
NAMUR NE43 is a user-association recommendation for how a smart 4–20 mA transmitter should use currents outside 4–20 mA to declare a fault. Typical practice bands:
| Current | Usual meaning (NE43 practice) |
|---|---|
| 3.8–20.5 mA | Valid measurement (3.8–4.0 mA and 20.0–20.5 mA are saturation, still “good”) |
| ≤ 3.6 mA | Fail-low (downscale diagnostic) |
| ≥ 21.0 mA | Fail-high (upscale diagnostic) |
| ~0 mA | Open circuit or unpowered transmitter — not, by itself, a NE43 fail-low |
NCEES does not hand you NE43 as a design-standard table on the Control Systems exam. Treat 3.6 mA / 21 mA as industry practice you should recognize, not as a lookup you can assume is in the electronic handbook. If an item gives the thresholds, use them. If it does not, reason from live zero (0 mA ≠ 0%) rather than inventing a code clause.
Limitations that actually fail loops
- Voltage drop. At 20 mA, every ohm of wire, barrier, isolator, and analog-input burden costs 0.020 V. The transmitter still needs its minimum terminal voltage. Design the loop at 20 mA, not at 4 mA.
- Leakage. Parallel moisture or damaged insulation steals current around a transmitter or holds a dry-contact input ON.
- Polarity. Two-wire transmitters, NAMUR amplifiers, and most analog inputs are polarized. Reverse them and you get 0 mA, a protection-diode drop, or a damaged input — not a negative process value.
- Distance versus noise. Current loops reject induced voltage; millivolt and 1–5 V circuits do not.
| Signal | Typical use | Noise immunity | Practical distance |
|---|---|---|---|
| 4–20 mA (2-wire) | Process variable to DCS/PLC | High (current; induced volts add little) | Hundreds to thousands of feet if the voltage budget holds |
| 1–5 V / 0–10 V | Short panel or same cabinet | Low; IR drop is error | Feet to tens of feet unless converted to current |
| 3–15 psi | I/P, positioner, older loops | Immune to EMI; sensitive to leaks and lag | Limited by volume, lag, and freeze, not EMI |
| Thermocouple mV | Temperature, local or to a transmitter | Very low | Short unless the transmitter is at the head |
| RTD resistance | Temperature | Moderate; lead resistance is bias | 3-wire / 4-wire extends the usable run |
| Pulse / frequency | Flow total, speed | Edges need clean thresholds | Limited by cable quality and maximum frequency |
| Dry contact | Discrete status, shutdown inputs | Bounce; leakage can false-ON | Long runs need wetting current and attention to leakage |
| NAMUR proximity | Discrete plus wire-fault detect, IS | Current-level; suited to IS amplifiers | Set by the amplifier and IS parameters |
[!TIP]
Exam habit
When a stem gives milliamps and a range, convert with $(I-4)/16$. When it gives 0 mA, think open or unpowered, not lower range value.
Why is 4 mA used as 0% of span on a two-wire 4–20 mA transmitter loop rather than 0 mA?
A flow transmitter is calibrated 4–20 mA = 0–500 gpm. What process flow corresponds to a loop current of 12.0 mA?
Which statement about NAMUR NE43 analog failure currents is correct for PE Control Systems preparation?