13.1 Analog and Discrete Signal Types

Key Takeaways

  • A 4–20 mA live zero encodes 0% of span at 4 mA and 100% at 20 mA; about 0 mA is an open or unpowered loop, not a valid zero process reading.

  • Process value scales on the 16 mA span: PV = LRV + (I − 4)/16 × (URV − LRV), so 12 mA is always 50% of a 4–20 mA calibration.

  • A 250 Ω burden converts 4–20 mA to 1–5 V; voltage signals then treat IR drop as measurement error, which is why current is used for long analog runs.

  • 3–15 psi pneumatic is the live-zero air analog of 4–20 mA (3 psi = 0%, 15 psi = 100%, 9 psi = 50%); lost air goes toward 0 psig, not 0% process.

  • NAMUR NE43 fail bands (about ≤ 3.6 mA or ≥ 21 mA) are industry practice for smart analog transmitters, not an NCEES-supplied handbook table; do not confuse them with NAMUR proximity currents.

Last updated: August 2026

Why analog versus discrete is a Signals item

The PE Control Systems Signals domain is 11–17 questions. Specification 4.A opens with analog and discrete types because loop voltage budget, HART overlay, analog-input scaling, and discrete diagnostics all assume you can look at a milliamp, a volt, a psi, a millivolt, or a contact and know what a broken wire would do. Those signals usually terminate in a distributed control system (DCS) or programmable logic controller (PLC) analog or discrete input. Picking the wrong family is a failed design, not a unit-conversion slip.

Live zero: 4–20 mA, and why 0 mA is not 0%

A 4–20 mA current loop encodes 0% of calibrated span at 4 mA and 100% at 20 mA. The 4 mA floor is a live zero (elevated zero). Two reasons both show up on the exam:

  1. Fault discrimination. An open pair, a dead supply, or a transmitter that has stopped conducting produces about 0 mA. That is a circuit failure, not a process sitting at lower range value. If the span started at 0 mA, a broken wire would look identical to a valid zero reading.
  2. Two-wire power. A loop-powered transmitter must take operating current from the same pair that carries the signal. The 4 mA floor is the current the electronics are allowed to consume at 0% process; the remaining 16 mA is the modulation span.

Scale linearly on that 16 mA span. If II is loop current in milliamps, LRV is lower range value, and URV is upper range value:

fraction of span=I−420−4=I−416\text{fraction of span} = \frac{I - 4}{20 - 4} = \frac{I - 4}{16} PV=LRV+I−416 (URV−LRV)\text{PV} = \text{LRV} + \frac{I - 4}{16}\,(\text{URV} - \text{LRV})

Worked example: 12 mA is 50%

A differential-pressure transmitter is calibrated 4–20 mA = 0–200 inH2O. The analog input reads 12.00 mA.

12−416=816=0.50⇒PV=0+0.50×200=100 inH2O\frac{12 - 4}{16} = \frac{8}{16} = 0.50 \quad \Rightarrow \quad \text{PV} = 0 + 0.50 \times 200 = 100\text{ inH2O}

12 mA is always 50% of a 4–20 mA span, regardless of engineering units. Check a second point: 7.2 mA is (7.2−4)/16=0.20(7.2 - 4)/16 = 0.20, so the same 0–200 inH2O range reads 40 inH2O. The classic trap is treating 12 mA as 12/20=60%12/20 = 60\% and reporting 120 inH2O — that ignores live zero.

The 1–5 V signal is the same live-zero idea after Ohm's law. A 250 Ω precision resistor (or analog-input burden) converts 4.00 mA → 1.00 V and 20.00 mA → 5.00 V. Voltage drop in the signal leads then appears as a reading error, which is why current — not voltage — is the long-run analog workhorse.

Other analog families

3–15 psi pneumatic is the live-zero air analog: 3 psig = 0%, 15 psig = 100%, span 12 psi. 9 psi is 50%. A failed air supply or a blown tube heads toward 0 psig, which is not 0% process. Pneumatic still appears on valve actuators, I/P (current-to-pneumatic) transducers, and electrically dead or intrinsically safe areas. Limits are compressibility lag, leaks, freeze-up of wet instrument air, and tubing volume — not induced millivolts.

Thermocouple millivolts are tens of millivolts. They need cold-junction compensation, shielded twisted pair, and usually a local transmitter if the run is long. Ground loops and electromagnetic interference swamp millivolts long before they swamp 4–20 mA.

A resistance temperature detector (RTD) (typically Pt100 = 100 Ω at 0 °C) is a resistance, not a current. Lead-wire resistance is a direct temperature bias on 2-wire connections; 3-wire and 4-wire circuits cancel or measure the leads. An RTD does not “output 12 mA” unless a transmitter is already in the loop.

Pulse / frequency comes from turbine meters, positive-displacement meters, speed probes, and some flow computers. The information is in the count or frequency, not in an analog level. Debounce, pull-up, and the maximum frequency of the high-speed counter card matter. A 4–20 mA analog of the same flow is a different signal with a different error budget.

Discrete: dry contact and NAMUR proximity

A dry contact is a switch with no voltage of its own. The discrete-input card supplies wetting voltage; the field device only closes or opens. Wetting current too low → oxidized contacts and missed closures. Leakage on a wet long cable → false ON. Polarity usually does not matter for a true dry contact, but it does matter if the “contact” is actually a solid-state output.

A NAMUR proximity sensor (IEC 60947-5-6) is a 2-wire current-level discrete, typically powered at about 8.2 V through a switching amplifier. Conventional bands: ≤ about 1.2 mA with the target present (damped), ≥ about 2.1 mA with the target absent. About 0 mA is an open wire; a very high current is a short. That three-way diagnostic (off / on / cable fault) is why NAMUR sensors appear in safety and hazardous-area designs. Do not confuse NAMUR proximity currents with NAMUR NE43 analog-failure currents — different documents, different milliamps.

NAMUR NE43 analog failure currents (practice, not a supplied table)

NAMUR NE43 is a user-association recommendation for how a smart 4–20 mA transmitter should use currents outside 4–20 mA to declare a fault. Typical practice bands:

CurrentUsual meaning (NE43 practice)
3.8–20.5 mAValid measurement (3.8–4.0 mA and 20.0–20.5 mA are saturation, still “good”)
≤ 3.6 mAFail-low (downscale diagnostic)
≥ 21.0 mAFail-high (upscale diagnostic)
~0 mAOpen circuit or unpowered transmitter — not, by itself, a NE43 fail-low

NCEES does not hand you NE43 as a design-standard table on the Control Systems exam. Treat 3.6 mA / 21 mA as industry practice you should recognize, not as a lookup you can assume is in the electronic handbook. If an item gives the thresholds, use them. If it does not, reason from live zero (0 mA ≠ 0%) rather than inventing a code clause.

Limitations that actually fail loops

  • Voltage drop. At 20 mA, every ohm of wire, barrier, isolator, and analog-input burden costs 0.020 V. The transmitter still needs its minimum terminal voltage. Design the loop at 20 mA, not at 4 mA.
  • Leakage. Parallel moisture or damaged insulation steals current around a transmitter or holds a dry-contact input ON.
  • Polarity. Two-wire transmitters, NAMUR amplifiers, and most analog inputs are polarized. Reverse them and you get 0 mA, a protection-diode drop, or a damaged input — not a negative process value.
  • Distance versus noise. Current loops reject induced voltage; millivolt and 1–5 V circuits do not.
SignalTypical useNoise immunityPractical distance
4–20 mA (2-wire)Process variable to DCS/PLCHigh (current; induced volts add little)Hundreds to thousands of feet if the voltage budget holds
1–5 V / 0–10 VShort panel or same cabinetLow; IR drop is errorFeet to tens of feet unless converted to current
3–15 psiI/P, positioner, older loopsImmune to EMI; sensitive to leaks and lagLimited by volume, lag, and freeze, not EMI
Thermocouple mVTemperature, local or to a transmitterVery lowShort unless the transmitter is at the head
RTD resistanceTemperatureModerate; lead resistance is bias3-wire / 4-wire extends the usable run
Pulse / frequencyFlow total, speedEdges need clean thresholdsLimited by cable quality and maximum frequency
Dry contactDiscrete status, shutdown inputsBounce; leakage can false-ONLong runs need wetting current and attention to leakage
NAMUR proximityDiscrete plus wire-fault detect, ISCurrent-level; suited to IS amplifiersSet by the amplifier and IS parameters

Tip

Exam habit

When a stem gives milliamps and a range, convert with (I−4)/16(I-4)/16. When it gives 0 mA, think open or unpowered, not lower range value.

Loading diagram...
Live-zero 4–20 mA loop versus 0 mA fault
Test Your Knowledge

Why is 4 mA used as 0% of span on a two-wire 4–20 mA transmitter loop rather than 0 mA?

A

Live zero distinguishes an open or unpowered loop (about 0 mA) from a valid 0% process reading, and the 4 mA floor supplies operating current to the transmitter electronics.

B

Ohm's law requires 4 mA so that a 250 Ω resistor produces 10 V at 0% process.

C

0 mA would saturate NAMUR NE43 fail-high diagnostics that the NCEES handbook tabulates for every analog input.

D

4 mA is reserved for pulse/frequency totalizers; analog process variables must never use the bottom of the current range.

Test Your Knowledge

A flow transmitter is calibrated 4–20 mA = 0–500 gpm. What process flow corresponds to a loop current of 12.0 mA?

A

150 gpm

B

250 gpm

C

300 gpm

D

375 gpm

Test Your Knowledge

Which statement about NAMUR NE43 analog failure currents is correct for PE Control Systems preparation?

A

NE43 is an NCEES-supplied design standard, so 3.6 mA and 21 mA can be looked up in the exam handbook tables.

B

A 12 mA reading is the NE43 fail-low declaration for a smart transmitter.

C

NAMUR proximity sensors use the same 3.6 mA and 21 mA bands as analog transmitters.

D

NE43 practice treats currents at or below about 3.6 mA or at or above about 21 mA as transmitter faults, while about 0 mA still means open or unpowered; the recommendation is industry practice, not a table NCEES hands you.

Sections you finish are checked off in the contents.