14.2 Power, Grounding, Segregation, and EMI
Key Takeaways
- Redundant 24 VDC bulk supplies are commonly diode-auctioneered onto one bus. Subtract the diode forward drop (about 0.3 V Schottky to 0.7 V silicon) from every solenoid and analog-loop voltage budget, and fuse so a field short cannot collapse the whole bus.
- Round-trip voltage drop is Vd = I × 2 × R' × L. A 350 mA solenoid on 600 ft (one way) of 18 AWG at 6.5 Ω/1000 ft drops 2.73 V and sees 21.27 V from a 24.0 V bus — below a 21.6 V (−10%) coil floor.
- Conventional analog 4–20 mA shields are usually grounded at one end, typically the I/O or marshalling end, to avoid a 60 Hz ground loop. VFD and motor-lead shields are bonded at both ends with 360° glands because the noise is high-frequency.
- Keep analog and IS pairs out of VSD/motor-lead trays by distance or a metallic barrier. Ferrites and analog filters are cleanup after the geometry is fixed, not a substitute for segregation.
- Single-point (star) grounding favors analog accuracy at power frequency. Multi-point bonding favors high-frequency EMC. Mixing the two without a plan is how plants create noisy 4–20 mA and circulating shield current.
A loop that is entity-correct and still chatters at 12 mA is not a classification problem. It is a power, grounding, and electromagnetic-compatibility problem. PE Control Systems items in this neighborhood ask whether the 24 V is still 24 V at the load, whether two supplies can share a bus without back-feeding, and whether the analog pair was routed as if it were another motor lead.
UPS, fusing, and diode-auctioneered 24 VDC
Control-room 120 VAC for DCS/PLC processors is usually an online (double-conversion) UPS: incoming AC is rectified and the inverter carries the load continuously, so transfer time is not a ride-through gamble. Line-interactive or standby UPS units that switch after a dropout are a poor match for switch-mode I/O supplies that already dropped out. SIS power is a separate battery-backed source when independence from the BPCS is part of the safety design; a shared UPS that dies for both systems is not “redundant” in the safety sense.
Field I/O more often lives on 24 VDC bulk with battery backup or a DC UPS. Size the battery for the documented ride-through (orderly shutdown versus continuous operation). Treat inrush of analog barriers, solenoids, and network switches as part of the current, not as a surprise after commissioning.
Fusing is coordination, not decoration. Fuse the +24 V feeder to a marshalled group so a shorted solenoid or a crushed tray takes that group, not the entire cabinet. The fuse in a zener barrier is part of the IS certificate — substituting a larger field-replaceable fuse is how a loop stops being the loop on the control drawing. Do not add a second series fuse on the IS field pair unless that fuse is on the drawing; extra resistance and extra opening energy were not in the entity file.
Diode auctioneering (diode-OR) lets two DC supplies feed one bus through steering diodes. The higher source voltage conducts; the lower sits reverse-biased. A silicon diode drops about 0.7 V; a Schottky about 0.3–0.4 V. The bus the loops actually see is Vsupply − Vf, and that drop belongs in every analog and solenoid budget. Diodes must be rated for the full bus current plus inrush; a diode that opens is a single point of failure unless you have monitored parallel paths. If Supply A is 24.5 V and Supply B is 23.8 V, only A carries load until A fails — “both supplies sharing” is not what the circuit does.
Worked numeric voltage drop on a 24 V loop
Instrument copper at about 20 °C is close to 6.5 Ω per 1000 ft for 18 AWG and 4.1 Ω per 1000 ft for 16 AWG. Use those working values unless the problem states NEC Chapter 9 Table 8 (75 °C) resistances, which are higher.
Round-trip drop for a two-conductor run of one-way length L (in kft) and resistance R' (Ω/kft) is:
Vd = I × 2 × R' × L
Worked solenoid (power loop). A 24.0 VDC bulk bus feeds a coil that draws 350 mA holding. The one-way cable length is 600 ft of 18 AWG. Neglect the auctioneering diode for the first pass.
- One-way resistance = 6.5 Ω/kft × 0.600 kft = 3.90 Ω
- Round-trip resistance = 7.80 Ω
- Vd = 0.350 A × 7.80 Ω = 2.73 V
- Voltage at the coil = 24.00 − 2.73 = 21.27 V
A coil specified 24 V ±10% has a 21.6 V floor. 21.27 V is below 21.6 V, so the valve may chatter, pull in weakly, or drop out on a warm day when copper resistance rises. Two honest fixes: 16 AWG on the same route (R_rt = 2 × 4.1 × 0.600 = 4.92 Ω, Vd = 1.72 V, Vcoil = 22.28 V) or a shorter run / local 24 V supply. If you then auctioneer through a 0.4 V Schottky, subtract that from the bus first: 23.6 V at the cabinet already, then 2.73 V of cable, 20.87 V at the coil — the diode you ignored is now the whole problem.
Same cable, analog loop. At 20 mA, that 7.80 Ω round trip drops only 0.156 V. Analog cable drop is usually tenths of a volt. Solenoid and 4-wire transmitter power conductors are where 24 V loops actually fail voltage drop. Still include analog cable in the Section 14.3 compliance budget; it is small, not zero, and it grows with thin wire and long runs.
A 10% voltage-drop rule of thumb (2.4 V on a 24 V bus) is a screening test, not a substitute for the nameplate minimum. Many 24 V solenoids and 2-wire transmitters have a minimum operating voltage tighter than 10%.
Control-signal isolation is the other half of “the 24 V arrived but the milliamp signal is garbage.” When a field device, a cable shield, and a panel analog common sit on different earths, the difference current has nowhere to go except along the signal conductor. Analog isolators, isolated analog-input cards, and galvanic IS isolators break that metallic loop. Isolation is not optional just because both ends say “24 V common.”
Single-point versus multi-point grounding, and shields
Single-point (star) grounding ties analog commons, shield drains, and the cabinet earth bar to one reference so that 50/60 Hz current has no loop area to circulate. It is the default mental model for millivolt thermocouples and quiet 4–20 mA.
Multi-point bonding ties cable shields and armor to earth at more than one place so that high-frequency noise (VFD PWM edges, radio, ESD) has a short path off the shield. At a few hundred kilohertz, a 30 m drain wire to a distant star point is an inductor, not a ground.
Plants use both, on purpose:
- Analog 4–20 mA and millivolt pairs: ground the shield at one end, almost always the control-room / I/O cabinet end. Leave the field end insulated unless the manufacturer’s control drawing says otherwise. Two-end analog shield grounds on a long pair are a 60 Hz loop around the tank farm earth gradient.
- VFD / motor leads: bond the shield (or armor) at both ends with 360° glands, not a pigtail. The standing-wave and common-mode current on a PWM motor cable will not drain through a single pigtail.
- Hybrid: some digital / fieldbus installations ground the shield at the cabinet and capacitor-couple the field end so that AC noise has a path while DC earth current does not. Follow the bus installation guide; do not invent a third earth on a spare drain.
The instrument cylinder ground and the electrical safety ground (PE) must still be bonded as a safety system. “Single-point analog” does not mean floating the cabinet. It means you do not let the analog shield be a parallel PE conductor between two buildings.
Segregation from VSD/motor leads, ferrites, and filters
A variable-speed drive’s motor leads are a fast common-mode noise source. Capacitive coupling into a parallel 4–20 mA pair looks like a wandering process value, a HART modem that will not connect, or a barrier that appears to “noise-trip.” Geometry beats firmware.
- Do not pull analog, IS, or millivolt cable in the same conduit or undivided tray as VSD output or motor leads.
- Separate with distance (a common installation practice is on the order of 300 mm) or a grounded metallic barrier / separate steel tray.
- Cross at right angles when the route must meet.
- Use symmetric, shielded VFD cable, 360° termination, and a motor-end EMC gland. Unshielded THHN bundled with analog is the commissioning failure mode.
- After the route is clean, ferrite sleeves (common-mode chokes) on the analog pair at the cabinet entry, and RC or active filters on the analog input, take residual RF. Ferrites on a still-bundled motor/analog pair treat the symptom.
- Do not hang random capacitors across an IS pair to “filter noise.” That capacitance is Ci on the entity sheet.
| Noise source | What it couples into | Mitigation that belongs on the drawing |
|---|---|---|
| VSD / motor leads (PWM edges) | Analog 4–20 mA, HART, IS pairs | Segregate trays; shielded symmetric motor cable; 360° glands; analog shield one-end |
| 60 Hz earth gradient between buildings | Shield loops, thermocouples | Single-end analog shield ground; isolators; do not use shield as PE |
| Auctioneered 24 V bus ripple / shared returns | Several loops at once | Separate analog commons from solenoid returns; adequate bulk capacitance; star 24 V returns |
| Radio / handhelds / ESD at cabinets | High-impedance millivolt inputs | Ferrites at entry; filtered glands; keep spare analog pairs terminated |
| Lightning / switching surges on long pairs | Transmitter electronics, AI cards | IS-rated SPDs on the control drawing; bonding of barriers and glands |
| Contact bounce / solenoid kickback on the same 24 V | Analog supply droop | Separate fused 24 V for solenoids versus analog; freewheel diodes on coils |
If the value jumped the day the VFD started, move the analog cable before you retune the PID.
A 24.0 VDC bulk supply feeds a 350 mA solenoid through 600 ft (one way) of 18 AWG copper. Use 6.5 Ω per 1000 ft and neglect diode drop. The coil is rated 24 V ±10% (21.6 V minimum). What is the voltage at the coil, and is the 18 AWG run acceptable?
A conventional analog 4–20 mA pair runs across a unit that also has a VFD motor feeder. What shield and bonding practice matches ordinary CSE installation?
Analog 4–20 mA values become noisy the day a nearby VSD is commissioned. Which mitigation is the correct first design move?