6.3 Power, Energy, and Watt’s Law
Key Takeaways
- Watt’s law is P = V × I = I² × R = V² / R; P = V × R is not a valid form.
- A 24 V, 75 mA appliance dissipates 1.8 W; six in parallel dissipate 10.8 W at the loads.
- A 4.7 kΩ EOL on 24 V dissipates about 0.12 W; a 470 Ω mix-up dissipates about 1.23 W and can overheat a ½ W resistor.
- Energy in watt-hours is P × hours: 150 mA at 24 V for 24 hours is 86.4 Wh, which is 3.6 Ah.
- Full secondary-power battery sizing, including a 20% safety factor, is Chapter 9; this section only previews Wh and Ah.
Why power and energy show up on an installer exam
Ohm’s law tells you volts, amps, and ohms. Module 1.III also expects power (how hard a load works, in watts) and energy (power over time, in watt-hours). You will use these numbers to read nameplates, estimate heat in a resistor or in copper, and to preview battery calculations. Full secondary-power arithmetic — 24-hour standby, 5-minute alarm, 20% safety factor, and occupancy exceptions — is Chapter 9. This section teaches the laws those later hours sit on.
Power also explains a design choice you already used: 24 V fire circuits versus 12 V security circuits. For the same wattage of horns, doubling voltage halves current (I = P / V) and therefore halves I × R voltage drop in the same copper. Fire NACs run 24 VDC for a reason.
Watt’s law — three forms, one relationship
Power P is the rate of energy conversion. The unit is the watt (W). One watt equals one joule per second.
P = V × I
P = I² × R
P = V² / R
These three are the same law once Ohm’s law is substituted (because V = I × R). Pick the form that matches the values you already know. P = V × R is not a form of Watt’s law — that product is not power.
Worked example I — P = V × I (one appliance and a NAC)
Horn-strobe: 24 V, 75 mA.
- 75 mA = 0.075 A.
- P = 24 × 0.075 = 1.80 W.
Six such appliances in parallel: 6 × 1.80 = 10.8 W at the loads.
Check with total current from Section 6.2: P = 24 × 0.450 = 10.8 W. Same number.
If those 10.8 W of appliances were fed at 12 V instead of 24 V, current would be I = P / V = 10.8 / 12 = 0.90 A — twice the 0.45 A you had at 24 V. Wire drop and copper heating would both get worse. That is the 24 V advantage in one line of Watt’s law.
Worked example J — P = I²R (heat in the wire)
From Section 6.1: I = 0.450 A, R_wire = 2.556 Ω.
P_wire = (0.450)² × 2.556 = 0.2025 × 2.556 = 0.52 W.
That half-watt is heat along 400 ft of 18 AWG — not a fire by itself, but it is exactly the 1.15 V drop expressed as power:
P = V_drop × I = 1.15 × 0.450 = 0.52 W.
Copper that is too small gets warm and starves the last strobe of voltage. Doubling current quadruples I²R heating. A NAC short is violent compared with 5 mA of EOL supervision for that reason: current may jump from milliamps toward the panel’s short-circuit limit, and heating in the fault and in the copper spikes with the square of I.
Worked example K — P = V² / R (EOL resistor wattage)
EOL 4.7 kΩ on 24 V:
P = (24)² / 4,700 = 576 / 4,700 = 0.123 W.
A typical listed EOL is a ½ W (0.5 W) resistor — about four times this dissipation, which is why substituting a ¼ W part is a poor field habit. The resistor still only sees about 24 V in alarm on a NAC as well; the appliances take the real power. The danger is installing the wrong resistance, not the EOL sharing horn wattage.
Wrong part: a technician grabs 470 Ω (yellow-violet-brown) instead of 4.7 kΩ (yellow-violet-red).
I = 24 / 470 = 0.0511 A = 51.1 mA (looks like a perpetual alarm or a trouble, depending on the panel).
P = (24)² / 470 = 576 / 470 = 1.23 W — more than twice a ½ W resistor’s rating. The part can overheat. Same Ohm’s law, now with Watt’s law telling you the resistor is in trouble.
On a 12 V security EOL of 2.2 kΩ: P = (12)² / 2,200 = 144 / 2,200 = 0.065 W. Still a ½ W part in most kits, with even more thermal margin at 12 V.
Energy, watt-hours, and a battery preview
Energy = power × time. If P is in watts and t is in hours, energy is in watt-hours (Wh).
Wh = V × I × t (hours)
Ah (ampere-hours) = I × t (hours) — the language of battery capacity.
Wh = V × Ah for a constant-voltage estimate.
Alarm batteries are rated in ampere-hours at a stated discharge rate. Chapter 9 converts standby current and alarm current into Ah, then applies a safety factor. Here we only build the energy intuition. Do not treat the following numbers as a finished battery size.
Worked example L — 24-hour standby energy
A FACU draws 150 mA standby from a 24 V battery for 24 hours. 24-hour standby is a common NFPA 72 secondary-power concept for many fire alarm systems; confirm the required hours for the occupancy and system type in Chapter 9 and the adopted NFPA 72 edition (New York’s 2025 Uniform Code references NFPA 72—22). 150 mA is a teaching standby current, not a particular panel’s datasheet.
- Ah_standby = 0.150 A × 24 h = 3.60 Ah.
- Wh_standby = 24 V × 3.60 Ah = 86.4 Wh.
- Or P = 24 × 0.150 = 3.6 W, then 3.6 W × 24 h = 86.4 Wh.
Worked example M — 5-minute alarm energy
Same system, alarm current 2.00 A at 24 V for 5 minutes (5/60 = 0.0833 h). Five minutes of alarm is the duration many fire alarm systems use for secondary-power alarm time; emergency voice/alarm communication systems often use a longer alarm period — again, Chapter 9.
- Ah_alarm = 2.00 × (5/60) = 0.167 Ah.
- Wh_alarm = 24 × 2.00 × (5/60) = 4.00 Wh.
Standby energy (86.4 Wh) dwarfs alarm energy (4 Wh) in this example because 24 hours is long and 5 minutes is short. A panel that is idle but hungry (high standby current from communicators, smoke-detector power, or a hungry keypad on a security panel) kills batteries faster than a loud 5-minute NAC.
Rough combined draw before a safety factor: 3.60 + 0.167 = 3.77 Ah. Chapter 9 will multiply by 1.20 (20% safety factor as industry/NFPA practice) and add all NAC, auxiliary, and communicator loads. 3.77 Ah is not a finished battery size.
Worked example N — do not double-count the EOL
The 4.7 kΩ EOL at 0.123 W for 24 hours: 0.123 × 24 = 2.95 Wh. That energy is already inside the panel’s standby current if supervision current comes from the battery. Do not add 2.95 Wh again in Chapter 9.
Kilowatt-hours (kWh) are utility energy: 1 kWh = 1,000 Wh. A 7 Ah, 24 V battery stores about 24 × 7 = 168 Wh = 0.168 kWh. This exam almost never discusses alarm batteries in kWh; stay in Wh and Ah.
Power, polarity, opens, and shorts
Power in a resistor is always positive (heat). On a battery, current out of the positive terminal is discharge (the battery supplies energy); current into the positive terminal is charge. Chapter 7.2 covers charging; here you only need the sign of energy flow.
Reversed polarity on a polarized appliance means the device dissipates about 0 W (it does not operate) even though voltage is present — a DMM can still show about 24 V. Measuring voltage without considering current is how technicians miss a reverse-polarity NAC.
Open versus short, restated in power language (still a preview of Chapter 7.3):
- Open: I ≈ 0, so P ≈ 0 in the load, even if voltage is present at the source.
- Short: V_load ≈ 0, so P_load ≈ 0 at the load, but power in the remaining resistance and in the source can be very large.
| Quantity | Formula | Use on this exam |
|---|---|---|
| Instantaneous power | P = V × I | Nameplate watts; NAC load |
| Heating in a known R | P = I² × R | Wire dissipation; short-circuit heat |
| Power from V and R | P = V² / R | EOL wattage; wrong-resistor check |
| Energy | E = P × t (hours) | Watt-hours |
| Battery capacity preview | Ah = I × t (hours) | Chapter 9 full calc |
Exam traps
- Using P = V × R.
- Leaving milliamperes unconverted so 24 × 75 becomes 1,800 W instead of 1.8 W.
- Reporting 3.6 Ah as 3.6 Wh (missing the × 24 V).
- Treating the Chapter 9 20% factor as optional decoration rather than part of the later calc.
- Sizing a ½ W EOL, then installing 470 Ω at 24 V.
You now have voltage, current, resistance, series/parallel, power, and energy. Chapter 7 applies them to AC/DC supplies, batteries, and meters. Chapter 9 puts Ah on a job sheet.
A notification appliance draws 75 mA at 24 V. What is its power dissipation?
A control panel draws 150 mA of standby current from a 24 V battery for 24 hours. Ignoring inefficiency, how much energy is taken from the battery in watt-hours?
Watt’s law can be written in all of the following forms except: