11.3 Equipment Grounding Conductors (EGC)

Key Takeaways

  • The primary function of the Equipment Grounding Conductor (EGC) is to provide a low-impedance path that conducts ground-fault current safely back to the source to trip the circuit breaker or blow the fuse.

  • NEC 250.118 recognizes specific wiring methods as EGCs, including copper/aluminum wire conductors, Rigid Metal Conduit (RMC), Intermediate Metal Conduit (IMC), and Electrical Metallic Tubing (EMT).

  • EGCs are sized using NEC Table 250.122 based on the ampere rating or setting of the upstream overcurrent protective device (fuse or circuit breaker) protecting the circuit.

  • Under NEC 250.122(B), if ungrounded circuit conductors are increased in size for voltage drop or engineering design, the equipment grounding conductor must be increased proportionally in circular mil area.

  • When conductors are installed in parallel in multiple raceways or cables per NEC 250.122(F), each parallel raceway must contain a full-sized EGC sized according to the rating of the overall upstream overcurrent protective device.

Last updated: October 2026

11.3 Equipment Grounding Conductors (EGC)

The Equipment Grounding Conductor (EGC) is the primary active safety component of any branch circuit or feeder. While the Grounding Electrode Conductor (GEC) connects system neutral to the earth for surge dissipation, the EGC runs alongside circuit phase conductors to connect the exposed non-current-carrying metal enclosures of electrical equipment back to the grounded source neutral. Its sole objective is to conduct massive short-circuit and ground-fault currents back to the electrical source to open upstream fuses or circuit breakers in fractions of a second.


Permitted Types of Equipment Grounding Conductors (NEC 250.118)

Under NEC 250.118, an EGC is not limited to a green insulated wire. The code recognizes 14 distinct wiring methods and materials as qualifying EGCs:

1. Wire Conductors

  • Copper, aluminum, or copper-clad aluminum conductors.
  • May be insulated, covered, or bare.

2. Metallic Raceways

  • Rigid Metal Conduit (RMC) (NEC Article 344) and Intermediate Metal Conduit (IMC) (NEC Article 342): Heavy-wall threaded steel raceways provide an exceptional, rugged, ultra-low-impedance EGC throughout their entire service life.
  • Electrical Metallic Tubing (EMT) (NEC Article 358): Steel or aluminum EMT is fully recognized as an EGC when assembled with listed set-screw or compression fittings made wrench-tight.

3. Flexible Conduits (Strict Limitations!)

Flexible metallic conduits have significantly higher electrical resistance and coiled tape construction that can unravel under severe fault currents. Therefore, Flexible Metal Conduit (FMC) and Liquidtight Flexible Metal Conduit (LFMC) are permitted to serve as the sole EGC only under strict conditional limits (NEC 250.118(5) & (6)):

  • The conduit terminates in listed grounding fittings.
  • The trade size does not exceed 1-1/4 inches.
  • The total combined length of the flexible conduit in the ground return path does not exceed 6 feet (1.8 m).
  • The circuit overcurrent protection is rated at 20 amperes or less for FMC (or 60 amperes or less for 3/4-in. through 1-1/4-in. LFMC).

Warning

Vibration & Motor Rule: Under NEC 250.118(5)(d) and 250.118(6)(e), if flexible conduit is installed to provide flexibility after installation (such as connecting to vibrating motors, transformers, or oscillating machinery), an equipment bonding jumper or wire-type EGC must always be installed, regardless of conduit length or breaker rating!

4. Cable Armor

  • Type AC (BX) Cable: The internal 16 AWG aluminum bonding strip in intimate contact with the interlocking steel armor forms an effective composite EGC.
  • Type MC Cable: Standard interlocking armor Type MC cable is not an EGC by itself and requires an internal insulated green copper EGC. However, listed Type MC-AP (All-Purpose) cable features an aluminum armor with an internal uninsulated aluminum bonding wire in continuous direct contact with the armor, qualifying the sheath assembly as a code-recognized EGC.

Sizing EGCs Using NEC Table 250.122

Unlike Grounding Electrode Conductors (sized from Table 250.66 by conductor size), Equipment Grounding Conductors are sized from NEC Table 250.122 based strictly on the rating or setting of the upstream overcurrent protective device (fuse or circuit breaker) protecting the circuit.

| Rating or Setting of Automatic Overcurrent Device Ahead of Equipment (Amperes) | Minimum Size Copper Conductor (AWG or kcmil) | Minimum Size Aluminum Conductor (AWG or kcmil) | | :---: | :---:: | :---: | | 15 A | 14 AWG | 12 AWG | | 20 A | 12 AWG | 10 AWG | | 30 A | 10 AWG | 8 AWG | | 40 A / 60 A | 10 AWG | 8 AWG | | 100 A | 8 AWG | 6 AWG | | 200 A | 6 AWG | 4 AWG | | 300 A | 4 AWG | 2 AWG | | 400 A | 3 AWG | 1 AWG | | 500 A | 2 AWG | 1/0 AWG | | 600 A | 1 AWG | 2/0 AWG | | 800 A | 1/0 AWG | 3/0 AWG | | 1000 A | 2/0 AWG | 4/0 AWG | | 1200 A | 3/0 AWG | 250 kcmil |

Note

Notice that a 60A breaker requires a 10 AWG copper EGC, while a 100A breaker requires 8 AWG copper, and a 200A breaker requires 6 AWG copper.


Proportional Increase Rule (NEC 250.122(B))

On long branch circuits or feeders, electricians frequently up-size ungrounded phase conductors to compensate for voltage drop (or other engineering design criteria). When this occurs, NEC 250.122(B) enforces a mandatory rule:

NEC 250.122(B): If ungrounded conductors are increased in size for reasons other than ambient temperature or conduit fill adjustment, wire-type equipment grounding conductors shall be increased in size proportionally according to circular mil area of the ungrounded conductors.

Why Proportional Up-Sizing is Mandatory

As a circuit run lengthens (e.g., 250 to 500 feet), circuit resistance increases proportionally (R=ρL/AR = \rho L / A). If an electrician up-sizes the hot wire from 10 AWG to 4 AWG to maintain a 3% voltage drop limit but leaves the EGC at 10 AWG, the total loop impedance under a ground fault (Zloop=Rhot+REGCZ_{loop} = R_{hot} + R_{EGC}) becomes dominated by the small EGC. Under a fault, the elevated impedance chokes fault current below the breaker's instantaneous magnetic trip threshold. The breaker takes several seconds to trip via its thermal element, allowing the undersized 10 AWG EGC to overheat, melt its insulation, and potentially burn down the building.

The Proportional Sizing Formula

To calculate the required up-sized EGC circular mil area:

Multiplier Ratio=Actual Up-Sized Phase Conductor Area (cmil)Minimum Code-Required Phase Conductor Area (cmil)\text{Multiplier Ratio} = \frac{\text{Actual Up-Sized Phase Conductor Area (cmil)}}{\text{Minimum Code-Required Phase Conductor Area (cmil)}}

Required New EGC Area (cmil)=Standard Table 250.122 EGC Area (cmil)×Multiplier Ratio\text{Required New EGC Area (cmil)} = \text{Standard Table 250.122 EGC Area (cmil)} \times \text{Multiplier Ratio}

Step-by-Step Worked Calculation Example

A 30-ampere, 240V branch circuit supplying a commercial refrigeration unit is routed 280 feet from the distribution panelboard:

  1. Determine Minimum Code Phase Size: A 30A circuit breaker requires a minimum phase conductor of 10 AWG copper. From NEC Chapter 9, Table 8, a 10 AWG solid/stranded conductor has an area of 10,380 circular mils10{,}380\text{ circular mils}.
  2. Determine Standard EGC Size: From NEC Table 250.122, a 30A overcurrent device requires a standard EGC of 10 AWG copper (10,380 cmil10{,}380\text{ cmil}).
  3. Examine Actual Installed Phase Size: To maintain voltage drop under 3%, the engineer specifies 4 AWG copper phase conductors. From Chapter 9 Table 8, a 4 AWG conductor has an area of 41,740 circular mils41{,}740\text{ circular mils}.
  4. Calculate Proportional Ratio: Ratio=41,740 cmil10,380 cmil=4.021\text{Ratio} = \frac{41{,}740\text{ cmil}}{10{,}380\text{ cmil}} = 4.021
  5. Calculate Required EGC Circular Mils: New EGC cmil=10,380 cmil×4.021=41,738 cmil\text{New EGC cmil} = 10{,}380\text{ cmil} \times 4.021 = 41{,}738\text{ cmil}
  6. Select Conductor from NEC Chapter 9, Table 8:
    • 6 AWG = 26,240 cmil26{,}240\text{ cmil} (Too small!)
    • 4 AWG = 41,740 cmil41{,}740\text{ cmil} (Satisfies 41,738 cmil41{,}738\text{ cmil} requirement)

Therefore, the wire-type Equipment Grounding Conductor must be up-sized from 10 AWG to 4 AWG copper!


EGC Sizing in Parallel Raceways (NEC 250.122(F))

When large commercial feeders are installed using conductors in parallel in multiple raceways or multi-conductor cables (NEC 310.10(G)), a common trade mistake is attempting to divide the EGC size among the parallel conduits. NEC 250.122(F) strictly prohibits dividing EGC sizes:

NEC 250.122(F)(1): Each parallel raceway or cable shall contain a full-sized wire-type equipment grounding conductor sized based on the ampere rating of the overall overcurrent protective device protecting the circuit per Table 250.122.

The Engineering Physics

Consider an 800-ampere feeder installed in two parallel nonmetallic conduits (Run A and Run B). From Table 250.122, an 800A breaker requires a 1/0 AWG copper EGC:

  • If an electrician improperly splits the EGC by installing a 4 AWG wire (sized for 400A) in each pipe, consider what happens when a phase conductor in Run A faults to ground.
  • Because electromagnetic inductive coupling binds fault current to the specific raceway containing the faulted phase wire, virtually 100% of the 800A fault current returns through the EGC in Run A. Almost no fault current will travel through Run B.
  • The undersized 4 AWG EGC in Run A will instantly vaporize under 800A+ of fault current before the breaker can clear, destroying the raceway and leaving the equipment energized.
  • The Rule: Each of the two conduits must contain a full-sized 1/0 AWG copper EGC.

Conductor Identification (NEC 250.119)

Equipment grounding conductors must be distinctly identifiable to prevent accidental connection to current-carrying phase or neutral buses:

  1. Permitted Colors: Continuous green, green with one or more yellow stripes, or bare.
  2. Conductors 6 AWG and Smaller (NEC 250.119): Must have continuous green or green/yellow insulation from the factory. Field-reidentification using green tape is strictly prohibited on conductors 6 AWG or smaller!
  3. Conductors 4 AWG and Larger (NEC 250.119(A)): Permitted to be permanently marked at each termination and at all accessible points using green tape, green adhesive labels, or green paint.
Loading diagram...
Equipment Grounding Conductor Sizing & Proportional Increase Workflow
Test Your Knowledge

A 100-ampere commercial subpanel feeder is protected by a 100A circuit breaker. If the ungrounded copper conductors are sized at 3 AWG copper, what is the minimum size copper Equipment Grounding Conductor (EGC) required per NEC Table 250.122?

A

12 AWG copper

B

10 AWG copper

C

8 AWG copper

D

6 AWG copper

Test Your Knowledge

A 30-ampere, 240V branch circuit is installed across a long warehouse run. To compensate for voltage drop, the ungrounded phase conductors are up-sized from 10 AWG copper (10,380 circular mils) to 4 AWG copper (41,740 circular mils). Under NEC 250.122(B), what is the minimum required size of the copper Equipment Grounding Conductor (EGC)?

A

10 AWG copper

B

8 AWG copper

C

6 AWG copper

D

4 AWG copper

Test Your Knowledge

An 800-ampere feeder is installed using two parallel nonmetallic conduits. What is the required sizing of the copper Equipment Grounding Conductor (EGC) installed within each of the two conduits per NEC 250.122(F)?

A

A full-sized 1/0 AWG copper EGC must be installed in each of the two parallel conduits

B

A 4 AWG copper EGC must be installed in each conduit, dividing the 800A requirement equally across both raceways

C

A single 1/0 AWG copper EGC installed in only one conduit satisfies code compliance for both runs

D

No EGC is required inside the conduits if the panelboards are bonded to building structural steel

Test Your Knowledge

Under what installation condition does NEC 250.118 permit 1/2-inch Flexible Metal Conduit (FMC) to serve as the sole Equipment Grounding Conductor without an internal wire-type bonding jumper?

A

When installed in lengths up to 25 feet connecting a 50-ampere commercial rooftop air conditioner

B

When the total length of the FMC run does not exceed 6 feet, the circuit is protected by an overcurrent device rated at 20 amperes or less, and the fittings are listed for grounding

C

Whenever liquidtight nonmetallic fittings are installed with external hose clamps

D

When connecting a vibrating heavy industrial motor operating at 480V three-phase

Sections you finish are checked off in the contents.