7.1 PV Disconnecting Means and Isolation

Key Takeaways

  • Under 2017 NEC 690.13, the PV system disconnecting means must be readily accessible, be marked "PV SYSTEM DISCONNECT," plainly indicate open or closed, consist of no more than six switches or breakers, and be rated for the current, available fault current, and voltage at its terminals.

  • Under 2017 NEC 690.15, isolating devices or equipment disconnects must be within the equipment or within sight and within 10 feet of it (or remotely operable from within 10 feet), and equipment disconnecting means must be lockable per NEC 110.25.

  • Load-break disconnects use arc chutes or magnetic blowouts to interrupt full dc load current, while an isolating device not rated to interrupt current (such as a mated connector or finger-safe fuse holder) must be marked "Do Not Disconnect Under Load" or "Not for Current Interrupting."

  • DC disconnect contacts differ fundamentally from AC switchgear because direct current lacks natural sinusoidal zero-crossing points, requiring wider air gaps, spring-assisted snap-action opening, and magnetic blowout coils to suppress destructive continuous plasma arcs.

Last updated: October 2026

PV Disconnecting Means and Isolation

Photovoltaic (PV) power systems generate continuous direct-current (DC) electricity whenever sunlight illuminates the array collector surface. Unlike conventional alternating-current (AC) branch circuits that can be completely de-energized by opening an upstream circuit breaker at the main distribution panel, solar modules cannot simply be turned off. As long as photons strike the silicon P-N junctions, an energized photovoltaic circuit maintains high electrical potential and available short-circuit current. Consequently, installing reliable, code-compliant safety disconnects and equipment isolation mechanisms is the single most critical defense protecting installation technicians, maintenance personnel, building occupants, and emergency first responders from high-voltage electric shock and catastrophic DC arc-flash hazards.

The National Electrical Code (NEC) addresses these hazards through two distinct sections: NEC 690.13, which governs the overarching PV System Disconnecting Means, and NEC 690.15, which specifies requirements for Equipment Isolation Disconnecting Means. Understanding the exact functional differences, mechanical standards, ratings, and physical installation requirements of these two code sections is fundamental for every solar professional.


1. NEC 690.13: The PV System Disconnecting Means

The primary function of the PV system disconnecting means is to provide a central, readily accessible isolation point capable of disconnecting the entire photovoltaic power system from all other systems and building wiring.

Core NEC 690.13 Requirements (2017 NEC)

  1. Location (690.13(A)): The PV system disconnecting means must be installed at a readily accessible location. Under NEC Article 100, readily accessible means capable of being reached quickly for operation, renewal, or inspection without climbing over or removing obstacles or using portable ladders. Where a disconnect on a system over 30 volts is readily accessible to unqualified persons, enclosure doors or hinged covers that expose live parts must be locked or require a tool to open. Field Note: Rooftop locations do not qualify as readily accessible because reaching them requires a ladder. Earlier codes also required the disconnect outside or inside nearest the point of conductor entrance; in the 2017 NEC that concern moved to 690.31(G), which requires dc circuits inside a building to run in metal raceway, Type MC cable, or metal enclosures to the first readily accessible disconnecting means.
  2. Marking (690.13(B)): Each PV system disconnecting means must plainly indicate whether it is in the open (off) or closed (on) position and be permanently marked "PV SYSTEM DISCONNECT" or equivalent. Where the line and load terminals may be energized in the open position, it must also be marked: "WARNING – ELECTRIC SHOCK HAZARD – TERMINALS ON THE LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION." Labels must comply with 110.21(B), and the directories required by 690.56 and 705.10 show where every power-source disconnect is located.
  3. Suitable for Use (690.13(C)): If the PV system is connected to the supply side of the service disconnecting means (as permitted by 230.82(6)), the PV system disconnecting means must be listed as suitable for use as service equipment.
  4. Maximum Number of Disconnects (690.13(D)): Not more than six switches or six sets of circuit breakers (or a combination of six), mounted in a single enclosure or a group of separate enclosures. A single PV system disconnect is permitted for the combined ac output of one or more inverters or ac modules in an interactive system.
  5. Ratings (690.13(E)): Ratings must be sufficient for the maximum circuit current, the available short-circuit current, and the voltage at its terminals. On a 600 Vdc circuit, a switch rated only 250 Vdc cannot be used.
  6. Type of Disconnect (690.13(F)): The disconnect must simultaneously disconnect the PV system conductors from all conductors of other wiring systems and must be an externally operable general-use switch, circuit breaker, or other approved means. A dc PV system disconnect must be marked for use in PV systems or be suitable for backfeed operation.

Where is the PV system disconnect? The PV system includes the inverter, so in a typical grid-tied string-inverter system the PV system disconnect is on the ac side, where the inverter output connects to premises wiring. The dc switch at the inverter is an equipment disconnecting means under 690.15. In microinverter and ac-module systems, the ac disconnect or the backfed breaker serves as the PV system disconnect.


2. NEC 690.15: Equipment Isolation Disconnecting Means

While NEC 690.13 provides system-level isolation, NEC 690.15 mandates disconnecting means for individual power conversion equipment. Equipment such as inverters, energy storage batteries, charge controllers, and combiner boxes must be isolated from all energized conductors of all power sources to permit safe servicing and component replacement.

What Must Be Isolated (2017 NEC 690.15)

  • Isolating devices must be provided to isolate PV modules, ac PV modules, fuses, dc-to-dc converters, inverters, and charge controllers from all conductors that are not solidly grounded. An equipment disconnecting means or the PV system disconnect may be used in place of an isolating device.
  • More than 30 amperes: Where the maximum circuit current exceeds 30 A for the output circuit of a dc combiner or the input circuit of a charge controller or inverter, an equipment disconnecting means (not merely an isolating device) is required. One equipment disconnect may isolate an inverter or charge controller from all of its input circuits.

Location (690.15(A))

Isolating devices and equipment disconnects must be located within the equipment, or within sight and within 10 feet (3 m) of it. An equipment disconnect may be remote if it can be remotely operated from within 10 feet of the equipment. (Within sight, as defined in Article 100, means visible and not more than 50 feet away; 690.15(A) adds the 10-foot limit.) Later editions relaxed this: the 2020 NEC permits a disconnect that is not within sight and within 10 feet if it is lockable per 110.25, and the 2023 NEC uses "within sight and readily accessible" or lockable.

Equipment Disconnecting Means (690.15(D))

An equipment disconnecting means must simultaneously open all current-carrying conductors that are not solidly grounded, be externally operable without exposing the operator to live parts, indicate whether it is open or closed, and be lockable in accordance with NEC 110.25. Permitted types are a manually operable switch or circuit breaker, a connector meeting 690.33(E)(1), a load-break fused pull-out switch, or a remote-controlled circuit breaker that is operable locally and opens automatically when control power is lost.

The Strict Standard of NEC 110.25 for Lockable Disconnects

Solar practitioners must understand that NEC 110.25 imposes strict hardware rules on lockable disconnects:

  • The provision for locking or adding a padlock to the disconnecting means must be a permanent component of the switch or enclosure.
  • The locking mechanism must remain in place with or without the padlock installed.
  • Portable, snap-on plastic lockout/tagout (LOTO) clips or removable clamshell breaker lockouts do not comply with NEC 110.25 for permanent code compliance. The switch enclosure must possess an integral padlock hasp or factory-drilled lockout bracket.

Utility Visible-Break Requirements

Many electric utility interconnection agreements enforce rules beyond the National Electrical Code, mandating a dedicated utility AC disconnect switch (UDS). Utilities frequently require this switch to be an outdoor, exterior-mounted, weather-tight, rotary or knife-blade safety switch that provides a visible air gap ("visible break") when opened, allowing line utility crews to visually verify physical disconnection prior to executing grid maintenance.


3. Load-Break vs. Non-Load-Break Disconnects

Not all disconnect switches are engineered to interrupt active electrical current. The NEC draws a sharp distinction between load-break rated devices and non-load-break isolation switches.

Load-Break Rated Disconnects

A load-break rated disconnect is engineered, tested, and listed (under standards such as UL 98, UL 98B, or UL 489) to safely open and interrupt full operating load current at rated voltage without sustaining damage or posing an arc hazard to the operator. Load-break switches feature heavy-duty spring mechanisms that snap open instantly regardless of how slowly the technician moves the external handle, rapidly extinguishing the resulting arc.

Non-Load-Break Isolation Switches

A non-load-break disconnect (or isolating switch) is intended solely for electrical isolation after the circuit has been de-energized by an upstream load-break device or an automated inverter shutdown command. Opening a non-load-break switch while current is flowing will initiate an intense electrical arc that can destroy the switch and severely burn the technician.

Under 2017 NEC 690.15(C), an isolating device is not required to have an interrupting rating or to open all conductors simultaneously. It must be one of the following:

  1. A connector meeting 690.33 that is listed and identified for use with the specific equipment (for example, mated module connectors);
  2. A finger-safe fuse holder;
  3. An isolating switch that requires a tool to open; or
  4. An isolating device listed for the intended application.

An isolating device must either be rated to open the maximum circuit current under load or be marked "Do Not Disconnect Under Load" or "Not for Current Interrupting." Common examples are finger-safe fuse holders in dc combiner boxes and mated PV connectors.


4. Physics of Direct-Current Arc Suppression vs. Alternating-Current Contacts

One of the most catastrophic mistakes in solar electrical design is substituting standard alternating-current (AC) rated switches or circuit breakers into direct-current (DC) photovoltaic circuits. While AC and DC switches may appear identical externally, their internal contact physics and arc-quenching mechanics are radically different.

The AC Natural Zero-Crossing Phenomenon

In a standard 60 Hz alternating-current circuit, current and voltage reverse direction periodically, naturally crossing through zero potential 120 times every second (twice per electrical cycle):

I(t)=Ipeaksin⁡(2πft)I(t) = I_{peak} \sin(2\pi f t)

When AC switch contacts open under load, an electrical arc ignites through the ionized air gap. However, as the AC wave reaches its next natural zero-crossing (I(t)=0I(t) = 0), the electrical current momentarily stops. At this instant, the surrounding air de-ionizes, cooling rapidly and preventing the arc from reigniting across the separating contact gap. As a result, AC switches can extinguish substantial fault currents with relatively simple contacts and small physical travel gaps.

The Continuous DC Arc Plasma Torch

Direct current maintains constant polarity and steady voltage. DC waveforms have zero natural zero-crossing points (I(t)=constantI(t) = \text{constant}). When contacts open in a 600 Vdc, 1000 Vdc, or 1500 Vdc photovoltaic circuit under load, the electric field ionizes the air, creating a superheated conductive plasma channel reaching temperatures between 3000∘C3000^\circ\text{C} and 6000∘C6000^\circ\text{C}. Because current flow never ceases, the plasma arc behaves like a continuous welding torch. If an AC-rated switch is opened in a high-voltage DC circuit, the arc will not extinguish; it will bridge the opening contacts, melt the copper blades, vaporize the plastic enclosure, and create an explosive line-to-ground or line-to-line arc flash.

DC Disconnect Engineering Solutions

To safely extinguish direct-current arcs, DC-rated disconnect switches (listed to UL 98B) incorporate specialized physical and magnetic mechanisms:

  1. Magnetic Blowout Coils and Permanent Magnets: DC switchgear places strong permanent magnets or series electromagnetic coils adjacent to the contact parting zone. When the contacts open, the moving charge carriers in the DC plasma arc experience a transverse Lorentz force (F⃗=q(v⃗×B⃗)\vec{F} = q(\vec{v} \times \vec{B})). This magnetic force physically propels the plasma arc sideways away from the contacts, stretching its length.
  2. De-Ionizing Arc Chutes (Arc Splitter Plates): The magnetically propelled arc is driven into a stack of insulated, parallel metallic splitter plates (arc chutes). The arc chutes slice the single long arc into a series of smaller micro-arcs. This rapidly cools the plasma, extracts thermal energy, and raises the total arc sustainment voltage far above the system operating voltage, forcing the arc to collapse within milliseconds.
  3. Quick-Make, Quick-Break Spring Action: DC disconnects incorporate internal over-center mechanical spring drives. The operating handle charges an internal spring; once the spring trips past its center point, the contacts snap open at extreme velocity (>5 m/s> 5\text{ m/s}), preventing a slow manual draw of the arc.
  4. Multi-Pole Series Wiring: To achieve high DC voltage ratings (such as 1000 Vdc or 1500 Vdc), manufacturers configure two, three, or four contact poles in series inside a single multi-pole switch. Wiring poles in series multiplies the physical air gap across which the arc must bridge, ensuring reliable circuit interruption.

5. Disconnect Comparison and Application Matrix

The following matrix summarizes the distinct classes of disconnecting means utilized throughout residential, commercial, and utility photovoltaic systems:

Disconnect TypeGoverning NEC SectionLoad-Break Rated?Primary Location CriteriaRequired Markings & Features
PV System Disconnecting MeansNEC 690.13YesReadily accessible; usually the ac disconnect or backfed breaker in grid-tied systemsMarked "PV SYSTEM DISCONNECT"; open/closed indication; max 6 disconnects
Equipment Disconnect or Isolating DeviceNEC 690.15Equipment disconnect: yes; isolating device: not requiredWithin the equipment, or within sight and within 10 ft (or remotely operable from within 10 ft)Equipment disconnects lockable per 110.25 and open all non-solidly-grounded conductors; isolating devices marked if not load-break
Utility AC Disconnect (UDS)Utility Interconnection / NEC 705YesAdjacent to utility revenue meter; exterior accessible 24/7Visible air-gap knife switch; lockable open; red engraved label denoting solar generation source
String Combiner DC DisconnectNEC 690.15 / UL 1741YesIntegrated directly on DC combiner enclosure exteriorInterlocked with door latch; isolates combined DC output bus from homerun circuit conductors
Inverter Integrated DC DisconnectNEC 690.15YesIntegrated onto or within inverter chassisRotary DC load-break switch listed under UL 98B; isolates DC input stages from internal inverter electronics
Finger-Safe Fuse HolderNEC 690.15(C)NoInside combiner box or inverter input cabinetTool-operated or finger-safe hinged drawer; marked "DO NOT DISCONNECT UNDER LOAD" unless rated load-break
Loading diagram...
PV Disconnecting Means and Equipment Isolation Hierarchy
Test Your Knowledge

Under the 2017 NEC 690.13(A), which location requirement applies to the PV system disconnecting means?

A

It must be mounted inside the main service panel directly beside the utility revenue meter

B

It must be on the roof within 3 feet of the array so firefighters can reach it quickly

C

It must be in a locked electrical vault that is reached only by a portable ladder

D

It must be at a readily accessible location that can be reached without ladders or removing obstacles

Test Your Knowledge

Why does opening an alternating-current (AC) rated switch under direct-current (DC) photovoltaic load present a severe arc-flash and fire hazard?

A

AC disconnect switches lack grounding lugs required to clear DC phase-to-ground faults

B

Direct current has no zero crossing, so an arc across separating contacts can keep burning instead of going out

C

DC conductors have higher inductive reactance than AC conductors, generating high reverse back-EMF voltage spikes

D

Direct current reverses polarity sixty times per second, which rapidly overheats the switchgear operating springs

Test Your Knowledge

Under the 2017 NEC 690.15(A), where may an inverter's equipment disconnecting means be located?

A

Anywhere within sight of the inverter up to 50 feet away, with no other distance requirement

B

Inside the main service panel at any distance, as long as a padlock hasp is attached to it

C

Anywhere on the same property, provided a label at the inverter states where the disconnect is

D

Within the inverter, or within sight of and within 10 feet of it, or remotely operable from within 10 feet

Sections you finish are checked off in the contents.