6.3 Conductor Sizing and Ampacity Derating
Key Takeaways
Conductor sizing for photovoltaic systems requires a rigorous two-step calculation method: checking continuous load terminal limitations (typically 75°C) and calculating derated ampacity under ambient conditions (starting from 90°C).
Under NEC 110.14(C), conductors terminated at equipment rated for 75°C cannot carry continuous currents exceeding the 75°C table ampacity, even when 90°C rated conductors (such as PV Wire or THWN-2) are installed.
Derating applies ambient temperature correction (2017 NEC Table 310.15(B)(3)(c)(a)) and the adjustment for more than three current-carrying conductors (2017 NEC Table 310.15(B)(3)(a)); the 2020 and 2023 editions renumbered them as Tables 310.15(B)(1) and 310.15(C)(1).
Since the 2017 NEC, raceways or cables in direct sunlight less than 7/8 inch (23 mm) above a roof get a 33°C (60°F) temperature adder (2017: 310.15(B)(3)(c); 2020/2023: 310.15(B)(3)(c)); at 7/8 inch or more there is no adder, and XHHW-2 is exempt.
Conductor Sizing and Ampacity Derating
Conductors in photovoltaic power systems are subjected to extreme environmental stresses rarely encountered in standard commercial or residential wiring. Outdoor PV array wiring operates under prolonged direct ultraviolet (UV) radiation, severe ambient temperatures, thermal cycling, and continuous maximum DC electrical loading. Sizing these conductors requires balancing two distinct engineering requirements: providing adequate current-carrying capacity (ampacity) to prevent insulation degradation and conductor overheating, while complying with equipment terminal temperature limits under National Electrical Code (NEC) Article 110.14(C).
Failure to properly size and derate conductors leads to insulation brittleness, dangerous hot spots, nuisance overcurrent device tripping, and elevated risk of DC arc faults. Solar professionals must master the standardized two-step sizing method to ensure every conductor satisfies code requirements under both normal and extreme operating conditions.
Important
Code edition for the exam: The PVIP exam provides the 2017 NEC, so this section cites 2017 table numbers. In the 2020 and 2023 NEC, ampacity Table 310.15(B)(16) became Table 310.16, ambient correction Table 310.15(B)(2)(a) became Table 310.15(B)(1) (310.15(B)(1)(1) in 2023), the more-than-three-conductor adjustment Table 310.15(B)(3)(a) became Table 310.15(C)(1), and the rooftop rule 310.15(B)(3)(c) became 310.15(B)(2). The numeric values used below did not change.
1. Conductor Types and Insulation Ratings in PV Systems
Wiring methods in photovoltaic arrays vary depending on whether conductors are exposed to outdoor weather or enclosed within protective raceways.
PV Wire (UL 4703) vs. USE-2 (UL 854)
- PV Wire (Photovoltaic Wire): Specifically developed for solar installations. PV Wire features an extra-heavy, sunlight-resistant cross-linked polyethylene (XLPE) or thermoset insulation jacket rated for wet and dry conditions. It carries listings for , , and , exhibits exceptional low-temperature flexibility (down to ), passes stringent flame tests, and is listed for direct burial. The 2017 NEC 690.31(C)(1) permits PV wire or USE-2 as exposed single conductors in PV source circuits within the array.
- USE-2 (Underground Service Entrance): A service-entrance cable type rated wet and dry and sunlight resistant. The 2017 NEC permits it for exposed PV source circuits within the array, but it is typically rated only 600 V and has thinner insulation than PV wire, so it cannot serve 1000 V or 1500 V arrays. (The 2014 NEC required PV wire on ungrounded arrays; the 2017 NEC deleted that rule.)
Conduit Conductors: THHN/THWN-2 and XHHW-2
Once PV circuits transition from module interconnects into raceways (such as electrical metallic tubing [EMT], rigid PVC, or fiberglass conduit), standard dual-rated building wire is used:
- THWN-2: Thermoplastic insulation with a nylon jacket, rated for in both dry and wet locations. (THHN alone is a dry-location rating, and dual-rated THHN/THWN is only when wet. The interior of a raceway in a wet location above grade is itself a wet location (NEC 300.9), so use a wet-rated conductor such as THWN-2 or XHHW-2 to keep the column available for derating.)
- XHHW-2: Thermoset cross-linked polyethylene insulation, rated wet and dry. XHHW-2 provides superior chemical, moisture, and abrasion resistance compared to THWN-2 and is widely favored in commercial and industrial rooftop applications.
2. Terminal Temperature Limitations (NEC 110.14(C))
One of the most widely misunderstood concepts in electrical sizing is the distinction between conductor insulation rating and equipment terminal rating.
The 75°C Equipment Ceiling
Most commercial and residential electrical equipment—including circuit breakers, fused disconnects, combiner box busbars, and inverter terminals—is tested and listed under UL standards for use with conductors operating at (or for devices rated 100 amperes or less with #14 through #1 AWG conductors, though modern solar components are universally rated for ).
If a -rated conductor (such as #10 AWG THWN-2) carries current up to its full capacity (), the metal conductor itself will heat up toward . When this hot copper is bolted to a terminal lug rated for only , the conducted heat will transfer into the terminal, overheating internal springs, thermal trip elements, and sensing electronics.
Therefore, NEC 110.14(C) dictates that regardless of conductor insulation temperature ratings ( or higher):
The ampacity of a conductor shall be selected and coordinated so as not to exceed the lowest temperature rating of any connected termination, conductor, or device.
The Role of the 90°C Column
Although a conductor terminated at a lug cannot be operated above its ampacity table value under continuous load, NEC 110.14(C) allows the column ampacity to be used as the starting point for derating adjustments (ambient temperature correction and conduit fill). The final derated ampacity must simply be verified against the design current.
3. The Standard Two-Step Conductor Sizing Method
To ensure full compliance with NEC 690.8, the ampacity table, and 110.14(C), solar designers must apply the Two-Step Conductor Sizing Method.
Two-Step Conductor Sizing Criteria:
Step 1 (Terminal Limit): Ampacity_75C >= I_sc * 1.5625 (Continuous load without derating)
Step 2 (Derated Limit): Ampacity_90C * F_temp * F_fill >= I_sc * 1.25 (Under conditions of use)
Step 1: Minimum Ampacity Before Derating (Terminal Protection)
The conductor must have an ampacity before derating sufficient to carry of the maximum circuit current () based on the terminal temperature rating (the column in NEC Table 310.15(B)(16)):
Step 2: Derated Ampacity Under Conditions of Use
The conductor's ampacity adjusted for environmental conditions of use (ambient temperature and conduit fill) must be equal to or greater than the maximum circuit current ():
Where:
- is the unadjusted conductor ampacity from the column of NEC Table 310.15(B)(16).
- is the ambient temperature correction factor from NEC Table 310.15(B)(2)(a) or Table 310.15(B)(16).
- is the conduit fill adjustment factor from NEC Table 310.15(B)(3)(a).
(Note: If the circuit is protected by an overcurrent protective device, the derated ampacity must also be equal to or greater than the OCPD rating, unless the small conductor rules or next-size-up exceptions of NEC 240.4 apply).
4. Temperature Correction and Conduit Fill Adjustment Factors
Ambient Temperature Correction ()
NEC Table 310.15(B)(16) establishes base ampacities referenced to an ambient temperature of (). When conductors operate in warmer environments, heat dissipation from the conduit slows, requiring ampacity to be derated.
| Ambient Temperature () | Ambient Temperature () | Correction Factor for Insulation | Correction Factor for Insulation () |
|---|---|---|---|
| 1.00 | 1.00 | ||
| 0.94 | 0.96 | ||
| 0.88 | 0.91 | ||
| 0.82 | 0.87 | ||
| 0.75 | 0.82 | ||
| 0.67 | 0.76 | ||
| 0.58 | 0.71 |
Conduit Fill Adjustment ()
When multiple current-carrying conductors are bundled together in a raceway or cable tray, the mutual heating between conductors reduces thermal dissipation. NEC Table 310.15(B)(3)(a) specifies the adjustment factors based on the total number of current-carrying conductors:
| Number of Current-Carrying Conductors | Adjustment Factor () |
|---|---|
| 1 to 3 | 1.00 (100%) |
| 4 to 6 | 0.80 (80%) |
| 7 to 9 | 0.70 (70%) |
| 10 to 20 | 0.50 (50%) |
| 21 to 30 | 0.45 (45%) |
Important Grounding Distinction: Equipment Grounding Conductors (EGC) carry current only during abnormal ground-fault events. Under normal operating conditions, the EGC is non-current-carrying and is never counted when determining conduit fill adjustment factors.
5. Rooftop Raceway Height and Temperature Adders
Rooftop surfaces absorb solar radiation and create an intense thermal microclimate directly above the roof deck. Conduits mounted flat against a dark roofing membrane can experience internal temperatures to hotter than ambient air.
Historical NEC Rule vs. the Current 7/8-Inch Rule
- Historical Editions (2008–2014 NEC): Contained a tiered table (Table 310.15(B)(2)(c) in 2008; Table 310.15(B)(3)(c) in 2011 and 2014) assigning temperature adders based on elevation above the roof (e.g., for , for , for , and for ). Commercial testing demonstrated that once conduit is elevated slightly off the roof, convective airflow significantly reduces solar heat gain.
- 2017, 2020, and 2023 NEC: Simplified to the () rule (2017 NEC 310.15(B)(3)(c); renumbered 310.15(B)(2) in 2020 and 2023):
- Raceways installed on or above rooftops exposed to direct sunlight where the distance from the bottom of the raceway to the roof surface is less than () must add a temperature adder of () to the ambient design temperature.
- Raceways supported at least () above the rooftop deck (e.g., using standard strut blocks, pillow blocks, or roof pipe stands) require zero temperature adder.
- XHHW-2 Exception: Type XHHW-2 insulated conductors are not subject to the rooftop temperature adder.
Solar installation professionals universally mount rooftop conduits on supports at least (typically ) above the roof surface to avoid the severe penalty.
6. Comprehensive Step-by-Step Worked Sizing Calculation
A solar installation team is installing a commercial rooftop PV system. Three source circuits are routed in a single continuous electrical metallic tubing (EMT) raceway from the array to a combiner box.
System Parameters
- Module Short-Circuit Current ():
- Number of Source Circuits in Conduit: 3 circuits (each circuit consists of 1 positive and 1 negative conductor, totaling 6 current-carrying conductors).
- Equipment Grounding Conductor: One #8 AWG bare copper wire (non-current-carrying).
- Conductor Insulation: Copper THWN-2 ( rating).
- Terminal Rating: Inverter and combiner terminals are rated for .
- Site Ambient Design Temperature: (, ASHRAE 2% design high dry bulb).
- Raceway Mounting: Elevated on rubber rooftop support blocks at an elevation of above the white TPO membrane roof (, so no rooftop temperature adder applies).
- String Overcurrent Protection: Each string is protected by a fuse.
Step 1: Terminal Ampacity Evaluation (NEC 110.14(C) / 75°C Column)
Calculate the required continuous design current before derating:
Consult NEC Table 310.15(B)(16) under the Copper column:
- #14 AWG Copper: Rated at . ( — Fails Step 1).
- #12 AWG Copper: Rated at . ( — Passes Step 1).
- #10 AWG Copper: Rated at . ( — Passes Step 1).
Step 1 establishes that the conductor must be at least #12 AWG Copper to satisfy terminal temperature limitations.
Step 2: Derating for Ambient Temperature and Conduit Fill (90°C Column)
Determine the adjustment factors:
- Ambient Temperature Correction (): At an ambient temperature of (within the range), NEC Table 310.15(B)(2)(a) specifies a correction factor of for wire.
- Conduit Fill Adjustment (): For 6 current-carrying conductors in a single raceway, NEC Table 310.15(B)(3)(a) specifies an adjustment factor of (80%).
- Combined Derating Factor:
Now, test candidate conductors using their unadjusted table ampacities from NEC Table 310.15(B)(16):
Testing #12 AWG Copper THWN-2
- Base ampacity =
- Derated ampacity:
- Verify against maximum circuit current ():
- Check Overcurrent Protection Compliance: The string is protected by a fuse. Under NEC 240.4(D), the maximum overcurrent protection for #12 AWG copper is strictly capped at . Furthermore, the derated ampacity of cannot protect a fuse. Therefore, #12 AWG is disqualified by overcurrent protection rules.
Testing #10 AWG Copper THWN-2
- Base ampacity =
- Derated ampacity:
- Verify against continuous circuit current:
- Verify against overcurrent protection: Under NEC 240.4(D), the maximum overcurrent protection for #10 AWG copper is . The derated ampacity of safely exceeds the string fuse rating ().
Conclusion
#10 AWG Copper THWN-2 is the minimum code-compliant conductor size. It satisfies the terminal requirement before derating (), provides an adjusted ampacity under conditions of use exceeding circuit current (), and coordinates with the string fuse.
What is the conduit fill adjustment factor from NEC Table 310.15(B)(3)(a) when six current-carrying conductors are installed in the same raceway?
0.90 (90%)
1.00 (100%)
0.80 (80%)
0.70 (70%)
Under modern National Electrical Code provisions (NEC 310.15(B)(3)(c)), under what physical mounting condition must a 33°C (60°F) temperature adder be added to the ambient design temperature for rooftop raceways exposed to direct sunlight?
Only when raceways contain more than nine current-carrying conductors
When the bottom of the raceway is less than 7/8 inch (23 mm) above the roof
Whenever raceways are installed in attics or other enclosed roof spaces, regardless of clearance height
For all metallic conduits installed on commercial low-slope buildings
When sizing a circuit conductor insulated with 90°C rated THWN-2 copper connected to equipment terminal lugs rated for 75°C, how must the conductor ampacity be calculated under the NEC two-step method?
Apply derating to the 90°C ampacity, and check that 125% of the continuous current fits the 75°C terminal ampacity
Derating factors must be applied directly to the 60°C table ampacity to protect the inverter's terminal electronics
The conductor may carry the full 90°C table ampacity because sunlight already raises the terminal temperature above 75°C
Derating factors are applied to the 75°C column while ambient temperature corrections are completely ignored
Sections you finish are checked off in the contents.