8.2 Equipment Grounding Conductors
Key Takeaways
An Equipment Grounding Conductor (EGC), defined in Article 100 and regulated under Article 250 Part VI, connects normally non-current-carrying metal parts of equipment to the system grounded conductor to provide a low-impedance path that facilitates instantaneous overcurrent device operation during ground faults.
Recognized EGC types under NEC 250.118 include copper or aluminum wire, rigid metal conduit (RMC), intermediate metal conduit (IMC), electrical metallic tubing (EMT), and limited lengths (maximum 6 feet) of flexible metal conduits under specific overcurrent limits.
EGCs are sized from Table 250.122 based exclusively on the rating or setting of the upstream overcurrent protective device ahead of the circuit, ranging from 14 AWG copper for 15A devices up to 800 kcmil copper for 6000A devices; an EGC is never required to be larger than the circuit phase conductors.
Under NEC 250.122(B), where ungrounded circuit conductors are increased in size for voltage drop or other reasons, wire-type equipment grounding conductors must be increased proportionally in circular mil area.
Where multiple circuits share a single raceway, trench, or cable tray, NEC 250.122(C) permits a single common EGC sized for the largest overcurrent protective device protecting conductors in that raceway.
Equipment Grounding Conductors
The Equipment Grounding Conductor (EGC) is the primary active line of defense against electrical shock and electrocution in premises wiring. While Grounding Electrode Conductors (GEC) connect electrical systems to the earth for voltage stabilization and lightning protection, EGCs connect equipment metal enclosures, raceways, junction boxes, and appliance chassis back to the system grounded conductor at the service or transformer. During normal operation, the EGC carries zero current and maintains all exposed metal at zero volts relative to ground. When an insulation breakdown occurs, the EGC acts as the low-impedance metallic superhighway carrying immense ground-fault current straight to the source, instantly tripping the circuit breaker or blowing the fuse. On the Kentucky Journeyman Electrician examination, questions involving NEC Table 250.122, proportional upsizing under NEC 250.122(B), and recognized wiring methods under NEC 250.118 are among the most frequent and calculation-intensive.
1. Definition and Purpose of the EGC (Article 100 & Article 250 Part VI)
Under NEC Article 100, the Equipment Grounding Conductor is defined as:
Equipment Grounding Conductor (EGC): A conductive path(s) that is part of an effective ground-fault current path and that connects normally non-current-carrying metal parts of equipment together and to the system grounded conductor or to the grounding electrode conductor, or both.
The Effective Ground-Fault Current Path (Article 100 & 250.4(A)(5))
To clear a fault, the complete circuit must satisfy the definition of an Effective Ground-Fault Current Path:
- It must be intentionally constructed, permanent, and electrically continuous.
- It must possess low impedance sufficient to facilitate the instantaneous operation of the overcurrent protective device (circuit breaker or fuse).
- It must have the ampacity to conduct safely the maximum fault current likely to be imposed upon it without melting, burning open, or igniting surrounding building materials.
+-----------------------------------------------------------------------------------+
| THE COMPLETE GROUND-FAULT CURRENT CIRCUIT |
| |
| 1. Phase Conductor contacts metal junction box or equipment enclosure. |
| 2. Fault Current travels over the Equipment Grounding Conductor (EGC) |
| (wire conductor, EMT, RMC, or IMC). |
| 3. Fault Current reaches the Panelboard Equipment Ground Bus. |
| 4. Fault Current crosses the Main Bonding Jumper (MBJ) at the service entrance. |
| 5. Fault Current transfers to the Grounded Service Conductor (Neutral). |
| 6. Fault Current returns to the Utility Distribution Transformer Secondary. |
| 7. Circuit Loop Closed: Ultra-low impedance forces OCPD instantaneous trip! |
+-----------------------------------------------------------------------------------+
2. Recognized Types of Equipment Grounding Conductors (NEC 250.118)
An EGC does not necessarily have to be a green insulated copper wire. NEC 250.118 recognizes fourteen specific types of equipment grounding conductors, categorized into wire conductors, metallic raceways, and metallic cable assemblies:
Comprehensive Breakdown of Permitted EGC Types (NEC 250.118(A))
| EGC Category | Permitted Wiring Method | NEC Reference | Key Limitations & Conditions |
|---|---|---|---|
| Wire Conductors | Copper, aluminum, or copper-clad aluminum wire | 250.118(A)(1) | Bare, covered, or insulated; solid or stranded |
| Rigid Metal Conduit | Rigid Metal Conduit (RMC) | 250.118(A)(2) | Threaded couplings and connectors made wrench-tight |
| Intermediate Metal Conduit | Intermediate Metal Conduit (IMC) | 250.118(A)(3) | Threaded or threadless fittings made wrench-tight |
| Electrical Metallic Tubing | Electrical Metallic Tubing (EMT) | 250.118(A)(4) | Listed compression or set-screw fittings made tight |
| Flexible Metal Conduit | Listed Flexible Metal Conduit (FMC / Greenfield) | 250.118(A)(5) | Permitted as sole EGC ONLY if: listed fittings used, total length , circuit OCPD , and NOT installed where flexibility is required after installation |
| Liquidtight Flex Metal | Listed Liquidtight Flexible Metal Conduit (LFMC) | 250.118(A)(6) | Permitted as sole EGC ONLY if: listed fittings used, total length , OCPD (for ) or (for ), and NOT installed where flexibility is required after installation |
| Type AC Cable | Armor of listed Type AC Cable (BX) | 250.118(A)(8) | Combined aluminum bonding strip and steel armor provides listed EGC path |
| Type MC Cable | Listed Type MC Cable with metallic sheath | 250.118(A)(10) | Interlocked armor listed as EGC (e.g., MC-AP with aluminum bonding strip) or continuous corrugated/smooth sheath |
| Cable Trays | Metallic Cable Tray systems | 250.118(A)(11) | Complying with NEC 392.60; mechanically and electrically bonded with jumpers |
| Cablebus Framework | Cablebus Framework | 250.118(A)(12) | Listed and bonded per Article 370 |
Critical Exam Nuances for Flexible Conduits (FMC & LFMC)
Journeyman exam questions frequently test the strict limitations on using FMC and LFMC as the equipment grounding conductor:
- The 6-Foot Length Limit: The total ground return path through the flexible conduit cannot exceed 6 feet (1.8 m). If you run 8 feet of FMC, you must install a separate wire-type EGC inside the conduit.
- The 20A / 60A Overcurrent Limit: Standard FMC is permitted as an EGC only where the circuit is protected at 20 amperes or less. LFMC is limited to 20A for 3/8-inch and 1/2-inch trade sizes, and 60A for 3/4-inch through 1-1/4-inch trade sizes.
- Flexibility After Installation: If the flexible conduit is installed to accommodate vibration or movement (such as connecting to an electric motor or vibrating compressor), a separate wire-type EGC must always be installed, regardless of conduit length or breaker rating.
3. Sizing EGCs Using NEC Table 250.122
When a wire-type equipment grounding conductor is installed, its size is determined exclusively from NEC Table 250.122 based on the rating or setting of the overcurrent protective device (circuit breaker or fuse) protecting the circuit ahead of the equipment.
NEC Table 250.122: Minimum Size Equipment Grounding Conductors for Grounding Raceway and Equipment
| Rating or Setting of Automatic Overcurrent Device Ahead of Equipment (Amperes) | Copper Conductor Size (AWG or kcmil) | Aluminum or Copper-Clad Aluminum Conductor Size (AWG or kcmil) |
|---|---|---|
| 15 | 14 AWG | 12 AWG |
| 20 | 12 AWG | 10 AWG |
| 30 | 10 AWG | 8 AWG |
| 40 | 10 AWG | 8 AWG |
| 60 | 10 AWG | 8 AWG |
| 100 | 8 AWG | 6 AWG |
| 200 | 6 AWG | 4 AWG |
| 300 | 4 AWG | 2 AWG |
| 400 | 3 AWG | 1 AWG |
| 500 | 2 AWG | 1/0 AWG |
| 600 | 1 AWG | 2/0 AWG |
| 800 | 1/0 AWG | 3/0 AWG |
| 1000 | 2/0 AWG | 4/0 AWG |
| 1200 | 3/0 AWG | 250 kcmil |
| 1600 | 4/0 AWG | 350 kcmil |
| 2000 | 250 kcmil | 400 kcmil |
Key Takeaway for Exam Candidates: Notice that for overcurrent devices rated 30A, 40A, and 60A, the copper EGC size is identical: 10 AWG copper. Similarly, a 100A breaker requires an 8 AWG copper EGC, a 200A breaker requires a 6 AWG copper EGC, and a 400A breaker requires a 3 AWG copper EGC.
The Upper Limit Rule (NEC 250.122(A))
NEC 250.122(A): In no case shall the equipment grounding conductor be required to be larger than the ungrounded circuit conductors supplying the equipment.
4. Proportional Upsizing for Voltage Drop (NEC 250.122(B))
One of the most challenging calculation questions on the Kentucky Journeyman exam involves NEC 250.122(B): increasing the size of equipment grounding conductors when circuit phase conductors are adjusted or increased in size.
Why Does the Code Mandate Proportional Upsizing?
When branch-circuit or feeder conductors are upsized to counteract voltage drop over long circuit runs (e.g., runs of 200 to 500 feet), the physical length of the circuit introduces significant electrical resistance (). If the ungrounded phase conductors are upsized to reduce resistance but the equipment grounding conductor is left at its minimum Table 250.122 size, the total fault circuit loop impedance may become too high. Under a line-to-ground fault, the reduced fault current might fail to reach the instantaneous trip threshold of the breaker, causing delayed tripping and hazardous overheating of the undersized EGC.
The Proportional Sizing Formula
NEC 250.122(B) mandates that where ungrounded conductors are increased in size from the minimum size that has sufficient ampacity for the intended installation, the wire-type equipment grounding conductor(s) shall be increased in size proportionally according to the circular mil area of the ungrounded conductors:
Reference Values from NEC Chapter 9, Table 8 (Conductor Properties)
| Conductor Size (AWG/kcmil) | Area in Circular Mils (cmil) |
|---|---|
| 14 AWG | 4,110 |
| 12 AWG | 6,530 |
| 10 AWG | 10,380 |
| 8 AWG | 16,510 |
| 6 AWG | 26,240 |
| 4 AWG | 41,740 |
| 3 AWG | 52,620 |
| 2 AWG | 66,360 |
| 1 AWG | 83,690 |
| 1/0 AWG | 105,600 |
| 2/0 AWG | 133,100 |
| 3/0 AWG | 167,800 |
| 4/0 AWG | 211,600 |
Worked Example 1: Branch Circuit Voltage Drop Upsizing
Problem: A , branch circuit supplying outdoor lighting located 250 feet away has an initial minimum required conductor size of 12 AWG copper (6,530 cmil). Due to voltage drop, the electrician increases the circuit conductors to 8 AWG copper (16,510 cmil). What is the minimum size required for the copper equipment grounding conductor?
- Identify minimum required phase conductor area: .
- Identify upsized phase conductor area: .
- Calculate the proportional multiplier:
- Identify base EGC size from Table 250.122 for a 20A breaker: 12 AWG copper (6,530 cmil).
- Calculate required new EGC circular mil area:
- Lookup conductor size in Chapter 9, Table 8: corresponds exactly to 8 AWG copper.
- Answer: The EGC must be upsized to 8 AWG copper.
Worked Example 2: Feeder Circuit Proportional Upsizing
Problem: A 100-ampere feeder is supplied by an overcurrent device rated at 100A. The minimum conductor required for the load is 3 AWG THHN copper (52,620 cmil). To mitigate voltage drop over a 400-foot run, the phase conductors are increased to 1/0 AWG copper (105,600 cmil). What size copper EGC is required?
- Minimum phase conductor area: .
- Upsized phase conductor area: .
- Calculate proportional multiplier:
- Base EGC size from Table 250.122 for a 100A OCPD: 8 AWG copper (16,510 cmil).
- Calculate required new EGC circular mil area:
- Lookup conductor size in Chapter 9, Table 8:
- 6 AWG is 26,240 cmil (less than 33,132 cmil — TOO SMALL!)
- 4 AWG is 41,740 cmil (greater than 33,132 cmil — ADEQUATE!)
- Answer: The copper equipment grounding conductor must be upsized to 4 AWG copper.
5. Multiple Circuits in a Single Raceway (NEC 250.122(C))
In commercial and industrial wiring, multiple branch circuits or feeders are frequently pulled through a common raceway, cable tray, or trench.
- General Rule (NEC 250.122(C)): Where a single equipment grounding conductor is run in a raceway, cable, or cable tray with multiple circuits, it is permitted to install a single common equipment grounding conductor.
- Sizing Requirement: The single common EGC must be sized for the largest overcurrent device protecting any circuit conductors in that raceway.
+-----------------------------------------------------------------------------------+
| MULTIPLE CIRCUITS IN A SINGLE RACEWAY (NEC 250.122(C)) |
| |
| CONDUIT RUN CONTAINING THREE CIRCUITS: |
| +-----------------------------------------------------------------------------+ |
| | Circuit 1: 120V, 20A Lighting Circuit (Phase + Neutral) | |
| | Circuit 2: 240V, 30A Water Heater Circuit (2 Hots) | |
| | Circuit 3: 208V, 60A Kitchen Appliance Feeder (3 Hots + Neutral) | |
| | | |
| | [ SINGLE COMMON EQUIPMENT GROUNDING CONDUCTOR ] | |
| | Sized for the LARGEST OCPD in the conduit: 60A Breaker | |
| | From Table 250.122: Minimum EGC = 10 AWG Copper | |
| +-----------------------------------------------------------------------------+ |
+-----------------------------------------------------------------------------------+
Example: A conduit contains a 20A branch circuit, a 40A branch circuit, and a 100A subfeeder. Instead of pulling three individual ground wires, the electrician may pull a single common copper EGC sized for the 100A breaker, which from Table 250.122 is an 8 AWG copper conductor.
6. Parallel Conductors (NEC 250.122(F))
When feeder or branch-circuit conductors are run in parallel in multiple raceways, a wire-type equipment grounding conductor, where used, must be installed in each raceway. Each one is sized from Table 250.122 using the rating of the overcurrent device that protects the whole feeder or branch circuit, not a share of it. Where parallel conductors share a single raceway or cable tray, one wire-type EGC sized the same way is enough.
Example: A 600-ampere feeder runs as two parallel sets in two conduits. Table 250.122 lists 1 AWG copper for a 600-ampere device, so each conduit gets a 1 AWG copper EGC. Sizing each EGC for 300 amperes (4 AWG) is a common mistake. If the ungrounded conductors were also upsized for voltage drop, 250.122(B) increases each EGC in proportion.
7. Identification of Equipment Grounding Conductors (NEC 250.119)
NEC 250.119 governs the color coding and identification of wire-type equipment grounding conductors:
- Conductors 6 AWG and Smaller: Unless bare, equipment grounding conductors 6 AWG and smaller must have a continuous outer finish that is green or green with one or more yellow stripes.
- PROHIBITION: You are not permitted to pull a white, black, or red wire sized 6 AWG or smaller and re-identify it with green phase tape in the field! The insulation must be factory-colored green.
- Conductors Larger than 6 AWG (4 AWG and Larger): Permitted to be permanently identified as an EGC at the time of installation at every point where the conductor is accessible (e.g., junction boxes, pull boxes, panelboards) by one of the following methods:
- Stripping the insulation from the entire exposed length.
- Coloring the exposed insulation green (using green paint or dye).
- Marking the exposed insulation with green phase tape or green adhesive labels encircling the conductor.
Under NEC Table 250.122, what is the MINIMUM size copper equipment grounding conductor required for a commercial feeder protected by a 400-ampere inverse-time circuit breaker?
6 AWG copper
3 AWG copper
2 AWG copper
4 AWG copper
A 600-ampere feeder is run as two parallel sets of conductors in two separate conduits, and a wire-type equipment grounding conductor is used. Under NEC 250.122(F), what is the minimum copper equipment grounding conductor required?
4 AWG copper in each conduit
1 AWG copper in one conduit only
3 AWG copper in each conduit
1 AWG copper in each conduit
A 50-ampere, 240V branch circuit is protected by a 50A circuit breaker. The minimum required phase conductor size is 8 AWG copper (16,510 cmil). Because of a long run, the phase conductors are increased to 6 AWG copper (26,240 cmil). Under NEC 250.122(B) and Chapter 9, Table 8, what is the MINIMUM size copper equipment grounding conductor?
8 AWG copper
10 AWG copper
6 AWG copper
4 AWG copper
Sections you finish are checked off in the contents.