30.3 Using Amprobes, Velometers, Pitot Tubes, Manometers & Gauges
Key Takeaways
- Trade E item 21 is using test equipment: clamp-on ammeters (Amprobe), velometers, pitot tubes, manometers, and gauges. Chapter 22.4 installed TAB; this section is choosing the instrument and reading it without mixing units.
- A clamp-on ammeter measures current from the magnetic field around ONE conductor. Clamping the whole cable (hot and neutral, or all three phases in one jaw) reads near zero because the fields cancel. Compare the reading to RLA/FLA, not to LRA.
- A velometer reads face velocity in fpm at a grille or coil. A pitot tube plus manometer reads velocity pressure in a duct. For standard air, V (fpm) ≈ 4005 × √VP (inches of water). Do not use 4005 × VP.
- Duct static, velocity pressure, and total pressure are inches of water (in. w.c.), not psig. Total pressure = static + velocity pressure. 1 psi ≈ 27.7 in. w.c. — a 0.5 in. w.c. blower ESP is about 0.018 psi, not 'half a pound.'
- Ohm and microfarad tests are LOTO. Clamp-on current and voltage tests are live measurements with a CAT-rated meter. Refrigerant gauges belong to Chapter 29; this cluster is electrical current and air/water pressure instruments.
30.3 Using Amprobes, Velometers, Pitot Tubes, Manometers & Gauges
Trade E’s instrument bullet is using test equipment: the Amprobe (clamp-on ammeter), velometer, pitot tube, manometer, and gauges. Chapter 22.4 already used pitot math in a TAB install. Chapter 29.3 used refrigerant leak detectors and refrigeration gauges. This section is the diagnostic use of the same kit on a Florida service call: current without breaking the circuit, air velocity at a face versus velocity pressure in a duct, and inches of water for static. The CBT books are Refrigeration & Air Conditioning Technology, 9th Edition (2021), the Troubleshooting Handbook, 2nd Edition (2003), and the Trane Ductulator when you translate velocity into cfm. OSHA 1926 still splits the work: LOTO before internals; rated live meters for clamp-on and voltage.
Quick Answer: Clamp-on (Amprobe): one conductor, compare to RLA/FLA. Velometer: face fpm at a grille or coil. Pitot + manometer: duct VP in inches of water, (V \approx 4005 \sqrt{\text{VP}}) for standard air. Static is also in. w.c., not psig. TP = SP + VP.
Amprobe / clamp-on ammeter — current without a break
Amprobe is the brand that became the field word for a clamp-on AC ammeter. The jaw reads current from the magnetic field around a single conductor. That is how you get the 19.8 A versus 14.1 RLA comparison in 30.1 without opening the circuit.
One conductor. If you clamp the entire SO cord — hot and neutral — the fields cancel and the meter reads near zero on a healthy circuit. On three-phase, clamp one leg at a time; do not swallow all three. A ground conductor in the jaw with the hot will also lie. Many techs still use a line-splitter or a plug adapter that separates the conductors at a receptacle for fractional-horsepower indoor units.
Range and inrush. Set a range above FLA, not above LRA, for running load. Use an inrush (peak/hold) function if you actually need LRA; a slow analog needle will not catch it. A compressor that starts at ~70 A and runs at 14 A is doing what LRA and RLA said. A compressor that runs at 22 A on a 14 A RLA is the 30.1 overload story.
True RMS meters belong on VFD and SCR loads; an averaging meter can mis-read electronic fan speeds. CAT rating and insulated jaws still matter on a 480-volt RTU. Clamp-on is a live test: covers as listed, PPE as Chapter 33, no ohm probes on those same terminals while they are hot. Some clamp-ons also read volts and watts; watts on a motor still want the PF discussion from 30.1 — a clamp that multiplies E × I without PF is reporting VA.
Worked clamp-on. Indoor blower nameplate FLA 6.8 A, 230 V, 1φ. You read 9.4 A, supply static +0.55 in. w.c., return −0.40 in. w.c. External static is 0.95 in. w.c. against a 0.50 in. w.c. nameplate ESP. High static, high amps, low airflow — dirty filter, crushed flex, wet coil, closed dampers — not a failed blower motor until the air path is proven. That is how the Amprobe and the manometer talk to each other.
Velometer versus pitot tube — two different velocities
A velometer (the classic Alnor swinging-vane instrument, or a rotating-vane / hot-wire anemometer doing the same job) reads air speed at a plane in feet per minute. Hold it in the plane of the grille, the coil face, or an outdoor-air hood. Average a grid. Cfm ≈ V × Ak, where Ak is the effective (not geometric) area of the grille — the manufacturer’s Ak, not the painted opening you measured with a tape. A rotating vane laid on a filter rack reads face velocity; a 24×24 filter (4 ft²) at 300 fpm is about 1,200 cfm through that filter if the velocity is representative.
A pitot tube is a dual-port probe: the tip faces the flow and sees total pressure; the side taps see static pressure. A manometer between those ports reads velocity pressure (VP). You use a pitot inside a duct, not at a grille face. Traverse (ASHRAE / AABC / NEBB grid), average √VP (average the velocities, not the raw VP if the item is picky), then
(V \approx 4005 \times \sqrt{\text{VP}})
for standard air (0.075 lb/ft³), with V in fpm and VP in inches of water. Cfm = V × inside area (ft²). Hot, wet, or high-altitude air changes density and the constant; Florida comfort ducts are treated as standard air unless the item says otherwise.
Worked pitot (same arithmetic as 22.4, diagnostic use). VP = 0.16 in. w.c.
(V = 4005 \times \sqrt{0.16} = 4005 \times 0.40 = 1{,}602\ \text{fpm})
A 24×12 duct (2.0 ft² inside) is about 3,200 cfm. If the schedule was 2,400 cfm, you are high. If you wrongly compute (4005 \times 0.16 = 641) fpm, you will starve every other branch trying to “fix” a number that was never low.
When to grab which. Velometer: grilles, coils, OA intakes, hood faces — places a pitot cannot sit in developed duct flow. Pitot: duct traverses, fan inlet/outlet where you need VP, SP, and TP. A flow hood (balometer) is a velometer family instrument that integrates face velocity into cfm at a diffuser. None of these replace a tachometer if the fan rpm is wrong, and none of them replace the Amprobe if the motor is over FLA.
Manometers, inches of water, and gauges
A manometer measures low air (and sometimes gas) pressure. Forms: U-tube, inclined, digital, and Magnehelic (diaphragm gauge). The HVAC air unit is inches of water column (in. w.c. or in. WG). Total pressure = static pressure + velocity pressure:
(\text{TP} = \text{SP} + \text{VP})
Static pressure is the push on the duct wall. Velocity pressure is the directed energy of the moving air. A pitot’s total port minus atmosphere is TP; side port minus atmosphere is SP; total minus static is VP.
Inches of water are not pounds per square inch. 1 psi ≈ 27.7 in. w.c. A blower nameplated 0.50 in. w.c. ESP is about 0.018 psi. Calling that “half a pound of static” is how you talk yourself into a hydronic gauge on a duct. Typical comfort-duct static sits in tenths to about 2 in. w.c. Kitchen grease ducts and high-pressure VAV boxes run higher, still in inches of water, not refrigerant psig. Natural-gas manifold pressure is often 3.5 in. w.c. (inches of water again). Hydronic TAB uses psig or feet of head on a differential gauge across a circuit setter — different instrument, different unit.
Worked static. Blower nameplate 0.50 in. w.c. ESP. Return static −0.25, supply +0.30. Total ESP = 0.55 in. w.c. — close to nameplate, amps should be near FLA if the motor is healthy. Same blower, return −0.45, supply +0.55, ESP 1.00 in. w.c.: high static, high amps, low cfm. Open the air path before you replace the motor you just clamp-on tested.
Gauges on this Trade E bullet include the air gauges above and the refrigerant manifold from Chapter 29 (compound suction in psig/in. Hg, high-side psig). Do not put a 500-psig refrigerant gauge on a 1-inch Magnehelic and expect a duct reading, and do not put a Magnehelic on a R-410A liquid line. Vacuum gauges (microns) are a recovery/evacuation instrument (Chapter 31), not a velometer.
| Instrument | Reads | Unit | Exam trap |
|---|---|---|---|
| Clamp-on / Amprobe | Current on one conductor | Amperes vs RLA/FLA | Whole-cable clamp reads ~0 |
| Voltmeter | E at disconnect and motor | Volts | Off-load panel voltage only |
| Velometer / vane / hot-wire | Face velocity | fpm; cfm = V × Ak | Using geometric area instead of Ak |
| Pitot tube | VP, SP, TP in a duct | in. w.c. | 4005 × VP, no square root |
| U-tube / Magnehelic / digital manometer | SP, VP, TP, gas manifold | Inches of water | Calling 0.5 in. w.c. “0.5 psi” |
| Refrigerant manifold | Suction / discharge | psig / in. Hg | Using it as a duct static gauge |
| Hydronic differential gauge | Pressure drop across a setter | psi or ft of head | Mixing with in. w.c. duct static |
Florida HVAC scenario
Sunrise Comfort, certified Class B in Orange County, is balancing a 5-ton changeout (well under 25 tons). The helper clamps the entire outdoor whip, reads 0.2 A, and condemns the compressor as open. Separately he holds a velometer in a 16×8 trunk, treats 800 fpm as if it were a pitot VP of 800 in. w.c., and reports the duct is “800 inches of water — the fan is in surge.” Correct kit: clamp one leg of the whip and compare to RLA; use the pitot and manometer in that trunk (VP will be a few tenths of an inch of water); use the velometer at the supply grilles with Ak. A Magnehelic on the return shows −0.35 in. w.c., not −0.35 psi. The owner’s 30-ton office RTU next door is Class A work; Class B still has to traverse that 30-ton supply duct with a pitot and read inches of water on the exam.
Traps: (1) Clamping hot and neutral together. (2) Comparing running amps to LRA. (3) Using a velometer as if it read VP. (4) (4005 \times \text{VP}) without the square root. (5) Duct static quoted in psig. (6) Refrigerant gauges on ducts. (7) Ohm tests without LOTO, or live clamp-on treated as an excuse to skip LOTO on internals.
A TAB tech needs supply-grille cfm, a duct velocity in a 24×12 trunk, and the air handler’s external static. Which instrument assignment is correct?
Which clamp-on (Amprobe) practice matches Trade E current-draw testing on a single-phase condensing unit?
An indoor blower nameplated 6.8 A FLA and 0.50 in. w.c. ESP draws 9.4 A. Return static is −0.45 in. w.c. and supply static is +0.55 in. w.c. Pitot VP in the supply trunk is 0.16 in. w.c. Which reading of those instruments is correct?