3.3 Equipment Grounding Conductors & Enclosure/Raceway Bonding

Key Takeaways

  • NEC 250.118 recognizes 14 distinct types of Equipment Grounding Conductors (EGCs), including copper/aluminum conductors, Rigid Metal Conduit (RMC), Intermediate Metal Conduit (IMC), and Electrical Metallic Tubing (EMT).
  • Flexible Metal Conduit (FMC) is permitted as the sole EGC under NEC 250.118(5) only if the total ground-fault path does not exceed 6 ft, the circuit overcurrent protection does not exceed 20A, listed fittings are used, and the raceway is not installed to provide flexibility after installation.
  • Equipment Grounding Conductors are sized strictly according to the rating or setting of the upstream overcurrent protective device (OCPD) per NEC Table 250.122, not by the size of the circuit conductors.
  • Under NEC 250.122(B), whenever ungrounded phase conductors are increased in size (such as upsized for voltage drop), the wire-type EGC must be increased proportionally in circular mil area.
  • Interior metal water piping systems must be bonded per NEC 250.104(A) using Table 250.102(C)(1) based on service conductor size, whereas other metal piping (such as fuel gas piping) is bonded per 250.104(B) sized per Table 250.122 based on the circuit likely to energize it.
Last updated: September 2026

3.3 Equipment Grounding Conductors & Enclosure/Raceway Bonding

While system grounding connects the neutral to earth for voltage stabilization and surge control, equipment grounding is the active life-safety mechanism that prevents electrocution and clears electrical faults. The Equipment Grounding Conductor (EGC) bonds all non-current-carrying metal enclosures, raceways, frames, and junction boxes together and routes fault current back to the system grounded conductor at the service disconnect or source.

For the Connecticut E-2 licensing examination, candidates must master the 14 recognized EGC types in NEC 250.118, the rules governing flexible conduits, conductor sizing under NEC Table 250.122, the mandatory proportional upsizing rule in 250.122(B), and the bonding of interior water and gas piping under 250.104.


1. The Effective Ground-Fault Current Path (NEC 250.4(A)(5))

Every equipment grounding circuit must fulfill the strict legal and engineering criteria of an effective ground-fault current path:

+-----------------------------------------------------------------------------+
|         THREE MANDATORY ELEMENTS OF AN EFFECTIVE GROUND-FAULT PATH          |
+-----------------------------------------------------------------------------+
| 1. INTENTIONALLY CONSTRUCTED | Low-impedance electrically conductive system |
|                              | designed to facilitate OCPD operation.       |
|------------------------------|----------------------------------------------|
| 2. PERMANENT & CONTINUOUS    | Electrically continuous from point of fault  |
|                              | back to the electrical supply source.        |
|------------------------------|----------------------------------------------|
| 3. AMPLE CURRENT CAPACITY    | Capable of safely conducting the maximum     |
|                              | fault current likely to be imposed on it     |
|                              | without melting, burning, or vaporizing.     |
+-----------------------------------------------------------------------------+

Clearing Faults: The Mechanics of Breaker Operation

When a phase conductor frays and contacts the metal wall of a junction box, the fault current flows along the EGC, through the panel ground bus, across the Main Bonding Jumper, and into the neutral bar to complete the loop back to the transformer. Because this metallic path has minuscule resistance (fractions of an ohm), the fault current surges to thousands of amperes ($I = \frac{E}{Z}$). This massive instantaneous overcurrent enters the instantaneous magnetic trip zone of the circuit breaker, opening the contacts within one-half to two cycles (8 to 33 milliseconds). If the ground-fault path is broken or high-impedance, the current remains low, the breaker never trips, and the entire raceway system remains charged at line voltage.


2. Recognized Equipment Grounding Conductors (NEC 250.118)

Under NEC 250.118, the equipment grounding conductor run with or enclosing the circuit conductors shall be one or more or a combination of the following 14 recognized types:

  1. Wire-Type Conductors: A copper, aluminum, or copper-clad aluminum conductor (bare, covered, or insulated).
  2. Rigid Metal Conduit (RMC) (Article 344).
  3. Intermediate Metal Conduit (IMC) (Article 342).
  4. Electrical Metallic Tubing (EMT) (Article 358).
  5. Listed Flexible Metal Conduit (FMC) (Article 348) — with strict limits.
  6. Listed Liquidtight Flexible Metal Conduit (LFMC) (Article 350) — with strict limits.
  7. Type MC (Metal-Clad) Cableonly specific listed types.
  8. Type AC (Armored) Cable (Article 320).
  9. Cable trays, copper busbars, and other listed metallic raceways.
+-----------------------------------------------------------------------------+
|               CRITICAL LIMITATIONS ON FLEXIBLE RACEWAYS & CABLES            |
+-----------------------------------------------------------------------------+
| RACEWAY / CABLE TYPE  | PERMITTED AS SOLE EGC? | MANDATORY CODE CONDITIONS         |
|-----------------------|------------------------|-----------------------------------|
| Electrical Metallic   | YES - Unrestricted     | All fittings must be listed and   |
| Tubing (EMT)          |                        | made up wrench-tight.             |
|-----------------------|------------------------|-----------------------------------|
| Flexible Metal        | YES - ONLY within      | (1) Length does not exceed 6 ft.  |
| Conduit (FMC)         | strict boundaries      | (2) OCPD rating does not exceed 20A|
| (250.118(5))          |                        | (3) Listed fittings used.         |
|                       |                        | (4) NOT installed for flexibility.|
|-----------------------|------------------------|-----------------------------------|
| Liquidtight Flexible  | YES - ONLY within      | (1) Length does not exceed 6 ft.  |
| Metal Conduit (LFMC)  | strict boundaries      | (2) 3/8" to 1/2": max 20A OCPD.   |
| (250.118(6))          |                        | (3) 3/4" to 1-1/4": max 60A OCPD. |
|                       |                        | (4) NOT installed for flexibility.|
|-----------------------|------------------------|-----------------------------------|
| Standard Interlocked  | NO                     | Requires an internal insulated or |
| MC Cable (330.108)    |                        | bare copper equipment ground wire.|
|-----------------------|------------------------|-----------------------------------|
| MC-AP / Armorlite     | YES                    | Features aluminum armor combined  |
| (Listed Interlocked)  |                        | with full-length bare aluminum    |
|                       |                        | bonding strip in continuous touch.|
+-----------------------------------------------------------------------------+

[!WARNING] The "Flexibility After Installation" Rule: If FMC or LFMC is installed to allow for movement, vibration, or flexibility after installation (such as connecting a vibrating motor, transformer, or pump), an equipment bonding jumper or wire-type EGC MUST be installed regardless of length or amperage! The 6-foot exception applies strictly to fixed, non-vibrating drops (e.g., a stationary troffer luminaire whip).


3. Sizing Equipment Grounding Conductors (NEC Table 250.122)

Unlike Grounding Electrode Conductors (which are sized from service conductor area under Table 250.66), wire-type Equipment Grounding Conductors are sized exclusively based on the rating or setting of the overcurrent protective device (fuse or circuit breaker) protecting the circuit conductors.

NEC Table 250.122 Summary

Rating or Setting of Automatic Overcurrent Device in Circuit Ahead of Equipment (Amperes)Minimum Size Copper Conductor (AWG / kcmil)Minimum Size Aluminum or Copper-Clad Aluminum Conductor (AWG / kcmil)
1514 AWG12 AWG
2012 AWG10 AWG
3010 AWG8 AWG
40 or 6010 AWG8 AWG
1008 AWG6 AWG
2006 AWG4 AWG
3004 AWG2 AWG
4003 AWG1 AWG
5002 AWG1/0 AWG
6001 AWG2/0 AWG
8001/0 AWG3/0 AWG
10002/0 AWG4/0 AWG
12003/0 AWG250 kcmil

Parallel Conductors and EGC Sizing (NEC 250.122(F))

When circuit conductors are installed in parallel in multiple raceways or cables (for example, a 1,200A feeder split across three parallel conduits):

  • Mandatory Rule: A full-sized Equipment Grounding Conductor must be installed in each parallel raceway.
  • Sizing: The EGC in each parallel conduit must be sized based on the full rating of the 1,200A overcurrent device protecting the entire feeder.
  • In this 1,200A feeder example, Table 250.122 mandates a 3/0 AWG copper EGC inside EACH of the three parallel raceways. You are strictly prohibited from dividing the 3/0 AWG cross-sectional area by three!

4. Conductor Upsizing & Proportional EGC Sizing (NEC 250.122(B))

On the Connecticut journeyman exam, questions involving NEC 250.122(B) catch many candidates unprepared. When circuit conductors are upsized to compensate for voltage drop on long branch circuits or feeders, the equipment grounding conductor must also be upsized proportionally.

[!IMPORTANT] NEC 250.122(B) Proportional Upsizing Mandate: Where ungrounded conductors are increased in size from the minimum ampacity requirement, the wire-type equipment grounding conductor, where installed, shall be increased in size proportionally according to the circular mil area of the ungrounded conductors.

Step-by-Step Calculation Procedure:

  1. Determine the Minimum Phase Conductor: Find the minimum size conductor required to carry the load based on NEC Table 310.16 (before considering voltage drop).
  2. Find Circular Mil Area in Chapter 9, Table 8: Look up the circular mil area of the minimum required conductor ($CM_{\text{original}}$).
  3. Look up the Upsized Phase Conductor: Look up the circular mil area of the actual conductor installed for voltage drop ($CM_{\text{upsized}}$).
  4. Calculate Upsizing Multiplier: Multiplier=CMupsizedCMoriginal\text{Multiplier} = \frac{CM_{\text{upsized}}}{CM_{\text{original}}}
  5. Determine Minimum Base EGC: Look up the standard base EGC required by Table 250.122 for the circuit breaker rating and find its circular mil area ($CM_{\text{EGC-base}}$).
  6. Calculate New EGC Circular Mil Area: CMnew-EGC=CMEGC-base×MultiplierCM_{\text{new-EGC}} = CM_{\text{EGC-base}} \times \text{Multiplier}
  7. Select Final EGC: Refer to Chapter 9, Table 8, and select the smallest standard conductor whose area is equal to or greater than $CM_{\text{new-EGC}}$.

Practical Exam Example:

A 30-ampere, 240-volt single-phase branch circuit supplies a remote air conditioning unit located 250 feet away.

  • Minimum conductor required for 30A: 10 AWG THHN Copper ($CM_{\text{original}} = 10,380\text{ cmil}$). Base EGC for 30A per Table 250.122: 10 AWG Copper ($10,380\text{ cmil}$).
  • Due to voltage drop, the electrician increases the branch circuit phase conductors to 4 AWG Copper ($CM_{\text{upsized}} = 41,740\text{ cmil}$).
  • Multiplier: $\frac{41,740\text{ cmil}}{10,380\text{ cmil}} = 4.021$
  • Required New EGC Area: $10,380\text{ cmil} \times 4.021 = 41,740\text{ cmil}$.
  • Checking Chapter 9, Table 8: A 4 AWG copper conductor has 41,740 circular mils. Therefore, the equipment grounding conductor must be upsized from 10 AWG to 4 AWG Copper!

5. Bonding of Piping Systems & Exposed Structural Metal (NEC 250.104)

Metallic systems within or on a building that could become energized during electrical faults must be reliably bonded to establish continuity back to the service ground.

+-----------------------------------------------------------------------------+
|                   BONDING OF PIPING & STRUCTURAL SYSTEMS                    |
+-----------------------------------------------------------------------------+
| SYSTEM TYPE           | GOVERNING CODE ARTICLE      | SIZING CRITERIA              |
|-----------------------|-----------------------------|------------------------------|
| Interior Metal Water  | NEC 250.104(A)              | Sized per NEC Table          |
| Piping System         |                             | 250.102(C)(1) based on       |
|                       |                             | service entrance conductors. |
|-----------------------|-----------------------------|------------------------------|
| Other Metal Piping    | NEC 250.104(B)              | Sized per NEC Table 250.122  |
| (e.g., Fuel Gas)      |                             | based on the rating of the   |
|                       |                             | circuit likely to energize it|
|-----------------------|-----------------------------|------------------------------|
| Exposed Structural    | NEC 250.104(C)              | Sized per NEC Table          |
| Building Steel        |                             | 250.102(C)(1) based on       |
|                       |                             | service entrance conductors. |
+-----------------------------------------------------------------------------+

Interior Metal Water Piping (NEC 250.104(A))

The interior metal water piping system must be bonded to the service equipment enclosure, the grounded conductor at the service, the grounding electrode conductor, or one or more grounding electrodes. The bonding jumper is sized using Table 250.102(C)(1) based on the largest service-entrance conductor. (Note: This is interior piping bonding to prevent touch shock hazards, distinct from using an underground water pipe as an electrode under 250.52(A)(1)).

Other Metal Piping / Gas Piping (NEC 250.104(B))

Metal fuel gas piping systems and other metal piping that may become energized must be bonded. Under NEC 250.104(B), the bonding conductor is sized per Table 250.122 based on the rating of the specific circuit likely to energize the piping. In most residential and light commercial applications, the equipment grounding conductor connected to the electrical circuit supplying an appliance that uses fuel gas (such as a gas boiler, gas furnace, or water heater) satisfies the requirement for bonding the gas piping without installing an external bonding wire.

Loading diagram...
Low-Impedance Effective Ground-Fault Current Path Clearing a Breaker
Test Your Knowledge

A feeder circuit is protected by a 400-ampere inverse-time circuit breaker and supplies a commercial subpanelboard. What is the minimum size copper equipment grounding conductor required for this feeder under NEC Table 250.122?

A
B
C
D
Test Your Knowledge

A 50-ampere branch circuit normally requires 8 AWG THHN copper conductors (16,510 circular mils) with a 10 AWG copper equipment grounding conductor (10,380 circular mils). Because of excessive distance and voltage drop, the phase conductors are upsized to 4 AWG THHN copper (41,740 circular mils). According to NEC 250.122(B), what size copper equipment grounding conductor must be installed?

A
B
C
D
Test Your Knowledge

An electrical service is supplied by 3/0 AWG copper ungrounded service-entrance conductors. An interior metal water piping system requires a bonding jumper to the service equipment enclosure under NEC 250.104(A). Which table must be used to size this bonding jumper, and what is the minimum required copper conductor size?

A
B
C
D
Test Your Knowledge

Under what specific conditions does NEC 250.118(5) permit Flexible Metal Conduit (FMC) to serve as the sole equipment grounding conductor for a circuit?

A
B
C
D