Ton of Refrigeration
The standard unit of cooling capacity: 12,000 Btu/hr, based on the heat required to melt one ton of ice in 24 hours.
Filter by Topic
Jump to Card
About These RETA CARO Flashcards
These 50 flashcards are designed to help you memorize key terms and definitions for the RETA Certified Assistant Refrigeration Operator. Each card shows a term on the front and its definition on the back—the classic flashcard format for vocabulary memorization. Use these alongside our practice questions to build both recall and comprehension.
Topics Covered
Complete Flashcard Reference
Review every term in this set. Open any term to reveal its definition.
Ton of Refrigeration
The standard unit of cooling capacity: 12,000 Btu/hr, based on the heat required to melt one ton of ice in 24 hours.
Btu (British Thermal Unit)
The amount of heat required to raise the temperature of 1 pound of water by 1°F. The base heat-measurement unit used throughout refrigeration calculations.
Lockout/Tagout
Control hazardous energy during servicing. Follow the written isolation and verification procedure and account for stored pressure, electrical, mechanical and thermal energy.
Sensible vs. Latent Heat
Sensible heat changes temperature. Latent heat changes phase at a fixed saturation pressure without changing temperature.
Superheat
Measured vapor temperature minus the saturation temperature at the same pressure. DX systems use outlet superheat to regulate feed and reduce liquid carryover.
Subcooling
Saturation temperature at the liquid pressure minus measured liquid temperature. Subcooling provides a margin against the formation of flash gas in the liquid line.
Vapor-Compression Cycle Flow Order
Compressor (raises pressure/temp) → Condenser (rejects heat) → Expansion device (drops pressure) → Evaporator (absorbs heat) → back to the compressor.
Expansion Device (Metering Device)
Meters refrigerant flow into the low side and drops pressure from condensing to evaporating pressure, causing a portion of the liquid to flash into vapor and cool the remaining liquid.
Condenser Heat Rejection Balance
For a simple steady-state circuit with no other heat rejection, the condenser rejects the evaporator heat plus the energy added by the compressor.
Cascade Refrigeration System
Two separate circuits exchange heat in a cascade heat exchanger. The higher-temperature circuit evaporates refrigerant there while the lower-temperature circuit condenses refrigerant.
Ammonia’s Refrigerant Designation
R-717 is ASHRAE’s designation for ammonia (NH₃).
First Aid for Ammonia Eye Exposure
Leave the exposure area. Immediately irrigate the eyes with copious tepid water for at least 15 minutes and seek medical attention.
Ammonia Flammability in Air
NIOSH lists an approximate flammable range of 15% to 28% by volume in air. Toxic exposure can occur at concentrations far below the lower flammable limit.
Can released ammonia stay near the ground?
Yes. Warm ammonia vapor is lighter than air at the same conditions, but a cold release can form a cloud that initially stays low. Use instrument readings to assess exposure.
Reading an Ammonia Saturation Table
Match the pressure units first. RETA R-717 anchors are −28°F at about 0 psig, 0°F at 15.6 psig and 68°F at 109.3 psig. At −40°F, read about 8.7 in Hg vacuum or 10.38 psia.
Twin-Screw Compressor
Two meshing helical rotors trap vapor and reduce its volume as it moves toward the discharge port. The machine is a positive-displacement compressor.
Compression Ratio
Absolute discharge pressure divided by absolute suction pressure. Use psia on both sides. With other conditions fixed, a higher ratio generally raises discharge temperature.
Reciprocating Compressor Volumetric Efficiency
Actual suction vapor volume admitted divided by piston swept volume. At higher compression ratios, clearance gas re-expands farther before the suction valve opens, reducing fresh intake.
Unloaders
Devices that hold reciprocating compressor suction valves open to prevent pumping on selected cylinders, reducing starting load or providing stepped capacity control.
Screw Compressor Slide Valve
A capacity slide unloads part of the trapped suction gas to modulate capacity. Some models use a separate or coordinated mechanism to vary the built-in volume ratio (Vi).
Liquid Slugging
Liquid entering the compression chamber can generate destructive forces. Floodback from the evaporator or liquid carryover after defrost can contribute.
Compressor Discharge Temperature
With other conditions unchanged, higher compression ratio or higher suction superheat can increase discharge temperature. Excess heat can degrade oil. Compare readings with the compressor maker’s limits.
Short Cycling
A compressor starting and stopping too frequently. Common causes include a faulty low-pressure control, an oversized compressor for the load, or a low refrigerant charge.
Ammonia–Oil Separation
Common mineral and other immiscible oils separate from liquid ammonia and settle at low points because they are denser. Use the oil approved for the specific compressor and system.
Oil Separator
Removes oil entrained in the compressor discharge gas. The oil can return to the compressor or a dedicated oil reservoir through the system’s oil-return arrangement.
Net Oil Pressure
On a reciprocating compressor, subtract crankcase pressure from oil-pump discharge pressure. That differential drives oil flow through the lubrication system.
Oil Logging
Oil accumulating in low-side vessels or coils coats heat-transfer surfaces and reduces cooling. Oil collected in the low side is handled under the site’s written procedure.
Safe Oil Draining
Only authorized operators drain oil using the equipment-specific written procedure. The procedure controls ammonia exposure and identifies the required protective equipment.
Reciprocating Compressor
A piston draws in vapor through a suction valve and reduces its volume in a cylinder. A separate discharge valve opens when cylinder pressure exceeds discharge-side pressure.
Oil Starvation Symptoms
Low net oil pressure, a compressor tripping on its low-oil-pressure safety switch, unusual bearing or piston noise, and rising bearing or discharge temperatures.
Centrifugal Compressor
An impeller accelerates the refrigerant vapor. A diffuser slows the vapor and converts part of its velocity into pressure. This is dynamic compression.
DX (Direct Expansion) Evaporator
The TXV meters refrigerant to control outlet superheat. An external equalizer can sense outlet pressure where coil pressure drop matters.
Flooded Evaporator
Liquid refrigerant wets the heat-transfer surfaces. A surge drum can maintain a controlled liquid level and separate liquid from the vapor returning to the compressor.
Ammonia Machinery-Room Low Alarm
IIAR’s machinery-room guidance describes a 25 ppm initial audible and visual alarm. The site emergency plan governs the operator’s response.
Accumulator (Suction Trap)
A vessel installed ahead of the compressor suction line that traps any liquid ammonia carryover from the evaporator, protecting the compressor from slugging.
Frost Buildup and Defrost
Frost restricts airflow and insulates the coil. Hot-gas defrost uses heat released as high-pressure refrigerant vapor condenses in the coil.
Evaporative Condenser
Air moves across water-wetted tubes. Evaporation of some of the spray water lets the condenser reject heat toward outdoor wet-bulb conditions.
Air-Cooled Condenser
Rejects heat to outdoor air without evaporating spray water. The dry-bulb temperature limits the condensing temperature it can approach.
Condenser Approach Temperature
Condensing temperature minus entering air wet-bulb temperature for an evaporative condenser, or dry-bulb temperature for an air-cooled condenser.
High-Pressure Receiver
A vessel that stores liquid ammonia after the condenser, buffering the system's refrigerant charge to handle varying loads and maintain a steady liquid feed to the low side.
King Valve
The main liquid outlet (shutoff) valve on the high-pressure receiver, used to isolate the receiver's liquid ammonia from the rest of the system.
Pressure Relief Valve
Automatically limits vessel overpressure. The device and discharge system must have adequate relief capacity and comply with the applicable code.
Non-Condensables
Air or other gases trapped in an ammonia system that will not condense at normal condenser conditions. They raise head pressure and reduce condenser efficiency even when charge and airflow are otherwise normal.
Automatic Purger
Collects non-condensables at high-side purge points, separates and recovers most of the ammonia, and discharges the residual gas through the designed outlet.
Ammonia PEL (Permissible Exposure Limit)
OSHA's 8-hour time-weighted average exposure limit for ammonia: 50 ppm.
NIOSH Ammonia Short-Term Exposure Limit
35 ppm averaged over 15 minutes. NIOSH’s time-weighted recommended exposure limit is 25 ppm. The federal OSHA 8-hour PEL is 50 ppm.
Ammonia IDLH
NIOSH sets the immediately dangerous to life or health value at 300 ppm. IDLH describes acute danger or conditions that could impair escape.
OSHA PSM and EPA RMP Thresholds
For anhydrous ammonia in a covered process, OSHA PSM applies at 10,000 lb or more. EPA RMP applies above 10,000 lb.
Respirators for IDLH Entry
OSHA permits full-face pressure-demand SCBA or a qualifying pressure-demand supplied-air respirator with independent escape air. OSHA treats an unmeasured concentration as IDLH when exposure cannot be reasonably estimated.
IIAR Ammonia Standards
IIAR 2 covers safe design of closed-circuit systems, IIAR 6 covers inspection/testing/maintenance, IIAR 7 covers developing operating procedures, and IIAR 9 covers minimum safety criteria for existing systems.
Frequently Asked Questions
What is the RETA CARO exam pass rate?
RETA does not publicly disclose first-time pass-rate data for the CARO exam. To pass, candidates must score at least 70 (the minimum passing score) out of 100 scored questions; the exam includes 110 total questions (100 scored plus 10 unscored pilot items) and a 3-hour time limit.
How many questions are on the RETA CARO exam?
CARO has 110 multiple-choice questions total: 100 scored questions plus 10 unscored pilot questions used to evaluate future exam content. Candidates get 3 hours to complete the exam, and the minimum passing score is 70.
Do I need work experience to take RETA CARO?
No. RETA CARO is designed as an entry-level credential with no minimum experience requirement, intended for operators who work under the supervision of a more experienced technician. RETA's more advanced CIRO credential requires two years of industrial refrigeration experience.
What ammonia exposure limits should I know for the CARO exam?
OSHA’s 8-hour time-weighted PEL is 50 ppm. NIOSH recommends a 25 ppm time-weighted limit and a 35 ppm short-term limit over 15 minutes. NIOSH’s IDLH value is 300 ppm. Odor cannot establish exposure level or safe entry.
What regulatory threshold triggers OSHA PSM and EPA RMP for ammonia refrigeration?
For a covered process with anhydrous ammonia, OSHA PSM applies at 10,000 lb or more under 29 CFR 1910.119 and Appendix A. EPA RMP applies when the process contains more than 10,000 lb under 40 CFR Part 68. The EPA rule has a separate listing for qualifying aqueous ammonia.
Is ammonia flammable?
Yes. NIOSH lists lower and upper explosive limits of about 15% and 28% by volume in air. Ammonia can still present an acute inhalation hazard at concentrations well below that range.
What is the RETA CARO retake policy?
The 2026 handbook gives a two-week minimum between testing sessions, allowing for U.S. mail. One reduced-fee retake is available within one year of the initial test, with a new application and fee. A third exam is full price. Schedule and complete the retest within 90 days after approval and payment.
Explore More RETA Refrigeration Operator Certifications
Continue into nearby exams from the same family. Each card keeps practice questions, study guides, flashcards, videos, and articles in one place.
More From This Family
Videos and articles for deeper review.