Free ACI Field Testing I Exam Flashcards

Memorize 50 essential terms and definitions for the ACI Concrete Field Testing Technician Grade I Certification. See the term, recall the definition, then flip to check yourself.

50 Flashcards
8 Topics
100% Free
TermClick to flip

Seven ASTM standards on the ACI Grade I exam

Tap to reveal definition
Card 1 of 50Exam Overview

Filter by Topic

Jump to Card

About These ACI Field Testing I Flashcards

These 50 flashcards are designed to help you memorize key terms and definitions for the ACI Concrete Field Testing Technician Grade I Certification. Each card shows a term on the front and its definition on the back—the classic flashcard format for vocabulary memorization. Use these alongside our practice questions to build both recall and comprehension.

Topics Covered

Exam Overview3 cards
ASTM C172 Sampling6 cards
ASTM C143 Slump8 cards
ASTM C1064 Temperature5 cards
ASTM C231 Air (Pressure)8 cards
ASTM C173 Air (Volumetric)6 cards
ASTM C138 Unit Weight & Yield7 cards
ASTM C31 Specimens7 cards

Complete Flashcard Reference

Review every term in this set. Open any term to reveal its definition.

Seven ASTM standards on the ACI Grade I exam

C172 sampling, C143 slump, C1064 temperature, C138 density/unit weight/yield, C231 pressure air, C173 volumetric air, and C31 making & curing specimens. All test FRESH concrete. C39 (compressive strength) is NOT included.

ACI Grade I written exam: format and passing rule

55 multiple-choice questions, closed book, 1 hour. Must score at least 60% on EACH ASTM method AND at least 70% overall. A high overall score cannot rescue one failed method category.

ACI Grade I performance exam requirement

Closed book. Physically demonstrate six of the seven methods and verbally describe C172 sampling. Scored on a checklist by an ACI examiner; missing a critical step can fail a test. Certification valid 5 years.

C172: how many portions and from where in the batch?

At least two regularly spaced portions taken from the MIDDLE of the discharge — never the very first or very last of the batch. Portions are combined and remixed to form a representative composite sample.

C172: maximum time between first and final sample portions

15 minutes maximum between obtaining the first and last portions of a composite sample. Transport and remixing must be done as quickly as possible to keep the sample representative.

C172: time limit to START slump, temperature, and air tests

Begin within 5 minutes after obtaining the final portion of the composite sample. These quick tests must start fast before hydration and evaporation change the concrete.

C172: time limit to START molding strength specimens

Within 15 minutes after fabricating the composite sample. This ensures cast cylinders/beams represent the concrete at placement and are not affected by delay before consolidation.

C172: minimum composite sample size for strength tests

At least 1 ft^3 (28 L). Smaller samples are allowed for routine slump, temperature, or air tests, but strength specimens require a full cubic foot to be representative.

C172: required treatment of the sample before testing

Remix the combined portions with a shovel the minimum amount needed for uniformity. Protect from sun, wind, evaporation, and contamination. Never add water or sieve out mortar.

C143: slump mold dimensions

Frustum of a cone: 8 in. (200 mm) bottom inside diameter, 4 in. (100 mm) top inside diameter, 12 in. (300 mm) height. The large opening sits on the base plate.

C143: tamping rod specification

Round, straight steel rod, 5/8 in. (16 mm) diameter, 16 in. or 24 in. long, with a hemispherical (rounded) tip of the same 5/8 in. diameter for consistent consolidation.

C143: layers and rod strokes for the slump cone

Fill in 3 layers, each about one-third of the mold's VOLUME (not height), and rod each layer 25 times. Layer heights are roughly 2-5/8 in., 6-1/8 in., then full 12 in.

C143: how deep should the rod penetrate each layer?

Rod throughout the depth of each layer. The bottom layer is rodded without striking the base plate; the middle and top layers penetrate about 1 in. (25 mm) into the layer below.

C143: how is the cone lifted, and how is slump measured?

Raise the mold vertically 12 in. in 5 +/- 2 seconds with no lateral or torsional motion. Slump = vertical distance from the original top of the mold down to the displaced original center of the specimen.

C143: maximum elapsed time for the whole slump test

2-1/2 minutes from the start of filling until the mold is removed, performed without interruption. Exceeding this allows the concrete to begin setting and skews results.

C143: what to do if the concrete shears or falls away

Disregard the test and run a new test on another portion of the sample. Shearing indicates the mix lacks cohesiveness and the standard slump test is not applicable to it.

C143: when is the slump test NOT applicable by aggregate size?

Not applicable when more than 10% of the aggregate is retained on the 1-1/2 in. (37.5 mm) sieve. Such mixes may be wet-sieved over a 1-1/2 in. sieve before testing.

C1064: minimum concrete coverage around the temperature sensor

At least 3 in. (75 mm) of concrete must surround the sensor in all directions so ambient air does not influence the reading. The method applies to aggregate up to 3 in. nominal max size.

C1064: how long must the sensor stay immersed before reading?

Leave embedded until the reading stabilizes — a minimum of 2 minutes and a maximum of 5 minutes after insertion. Reading too early or too late introduces error.

C1064: required device accuracy and verification interval

Accurate to +/- 1 degF (0.5 degC) over 30-120 degF. Verified at least once every 12 months against a reference thermometer traceable to a national standard, and any time accuracy is in doubt.

C1064: time limit to complete the temperature reading

Complete within 5 minutes after obtaining the sample. The reading is recorded only once the embedded sensor has stabilized (2-5 minutes).

C1064: which ACI documents set the temperature limits being checked?

ACI 305 (Hot Weather Concreting) and ACI 306 (Cold Weather Concreting). C1064 readings verify compliance with their placement-temperature limits.

C231 vs C173: when must you use the volumetric method?

C231 (pressure) is NOT valid for lightweight, highly porous, or air-cooled slag aggregate. Use C173 (volumetric / roll-a-meter) for those concretes — no aggregate correction factor is needed.

C231: Type A vs Type B pressure meter

Type A applies a known pressure by lowering a water column and reads air on a standpipe. Type B equalizes a known volume of air at a known pressure with the concrete's air and reads a dial directly. Type B is most common in the field.

C231: filling and consolidating the measuring bowl

3 approximately equal layers, each rodded 25 times with the 5/8 in. rod. After rodding each layer, tap the bowl sides 10-15 times with the mallet to close rod holes and release trapped air.

C231: the aggregate correction factor

Accounts for air trapped in the pores of dense aggregate that the meter reads but is not paste air. It is determined on the project aggregate and SUBTRACTED from the indicated air to get true air content.

C231: Type B step before pumping the air chamber

Close the main air valve, open both petcocks, and inject water through one petcock until it flows out the opposite petcock free of air. Close both petcocks before pumping up the chamber.

C231: reading the gauge and rodding the bottom layer

Lightly tap the gauge to stabilize the needle, then read to the nearest 0.1% air. Rod the bottom layer through its depth without forcibly striking the bottom of the bowl.

C231: calibration frequency for the pressure meter

Calibrate whenever accuracy is in doubt, at least annually, and after rough handling or a significant elevation change. Calibration checks operating pressure and verifies the reading with a known-volume vessel.

C231: why keep flanges and gasket surfaces clean?

Concrete residue or grit on the bowl/cover sealing surfaces prevents an airtight seal, causing leakage during pressurization and a falsely HIGH air reading. Clean thoroughly after every test.

C173: what instrument is used and why it is universal

A volumetric air meter ('roll-a-meter'). It works on ALL concretes including lightweight and porous aggregate because it relies on displacement and agitation, not pressure, so no aggregate correction is needed.

C173: filling the base (bowl)

2 approximately equal layers, each rodded 25 times with the 5/8 in. rod. After rodding each layer, tap the bowl sides 10-15 times with the mallet to close rod holes and release trapped air.

C173: role of isopropyl alcohol

A measured amount of 70%+ isopropyl alcohol is added to suppress foam from entrained air during rolling. The amount used determines a defined alcohol correction applied to the apparent reading.

C173: agitation and the final-reading agreement criterion

Invert and roll/tilt until aggregate is free, then re-agitate at about 1-minute intervals. The reading is final when two consecutive readings agree within 0.25% air content.

C173: what to do if the reading exceeds the neck scale

Re-run the test with a new portion of the sample. A reading above the graduated scale signals abnormally high air or a procedural error and must not be estimated or reported.

C173 vs C231: trade-off

C173 advantage: works with any aggregate, no aggregate correction. C173 drawback: slower — repeated rolling and successive-agreement readings take several minutes versus under a minute for a pressure test.

C138: what does the unit weight test let you calculate?

Density (unit weight), plus calculated yield, relative yield, cement content, and gravimetric air content. Yield verifies that batch quantities match the mix design.

C138: density formula

Density = net mass of concrete (filled measure minus empty measure) divided by the calibrated volume of the measure. Reported in lb/ft^3 (normal-weight concrete ~140-150) or kg/m^3.

C138: consolidation by measure size

Small measures (0.2-0.4 ft^3): 2 layers, 25 rod strokes each. Large measures (0.5-1.0 ft^3): 3 layers, 50 rod strokes each. Aim for ~1 stroke per 2 in^2 of surface; tap sides 10-15 times per layer.

C138: consolidation method vs slump

Slump < 1 in.: must use internal vibration. Slump 1-3 in.: rodding or vibration. Slump > 3 in.: rodding. Match the method to workability to avoid segregation or trapped air.

C138: yield and relative yield

Yield = total mass of all batched materials divided by measured density (volume produced per batch). Relative yield = actual yield / design yield; < 1.00 means under-yielding (less concrete than designed).

C138: gravimetric air content

Compare measured density to the theoretical air-free density computed from mix proportions; the percentage difference is gravimetric air. It is an independent check on C231 or C173 air results.

C138: measure calibration and pre-weighing prep

Calibrate by filling with water at a known temperature and dividing the water mass by water density to get volume (at least annually). Strike off flush with a sawing motion and clean all concrete/water off the exterior before weighing.

C31: standard specimen sizes and aggregate limit

Cylinders are 6x12 in. or 4x8 in.; beams are 6x6 in. (or 4x4 in. when aggregate <= 1 in.). Nominal max aggregate must not exceed 1/3 of the cylinder diameter.

C31: rodding rules for 6x12 vs 4x8 cylinders

6x12 in.: 3 layers, 25 strokes each, 5/8 in. rod. 4x8 in.: 2 layers, 25 strokes each, 3/8 in. rod. Subsequent layers penetrate ~1 in. into the layer below; tap mold 10-15 times per layer.

C31: low-slump consolidation rule

Concrete with slump < 1 in. must be consolidated by internal vibration (rodding not allowed). 1-3 in. allows either method; > 3 in. uses rodding. The vibrator must not touch the mold sides or bottom.

C31: initial curing temperature and duration

Initial curing up to 48 hours, on a level rigid surface free from vibration and protected from moisture loss. Temperature: 60-80 degF for f'c < 6,000 psi; 68-78 degF for f'c >= 6,000 psi.

C31: final (standard) curing condition

After initial curing, standard-cured cylinders are kept at 73.5 +/- 3.5 degF in a moist room (>95% RH) or immersed in lime-saturated water, so strength reflects mix proportions, not variable curing.

C31: demolding and transport timing

Demold standard-cured cylinders 24 +/- 8 hours after casting. Transport to the lab within 4 hours after the end of initial curing, protected from damage, drying, and freezing.

C31: standard-cured vs field-cured cylinders

Standard-cured cylinders are used for ACCEPTANCE (per ACI 318 / IBC, tested per C39). Field-cured cylinders estimate IN-PLACE strength for form removal, shoring release, or post-tensioning — not for acceptance.

Frequently Asked Questions

What is the ACI Concrete Field Testing Technician Grade I certification?

It is ACI's most widely held certification. It validates that a technician can correctly perform seven ASTM tests on freshly mixed concrete: sampling (C172), slump (C143), temperature (C1064), density/unit weight/yield (C138), air content by the pressure method (C231), air content by the volumetric method (C173), and making and curing test specimens (C31). The IBC and ACI 318 require Grade I certified technicians for acceptance testing of structural concrete on most building projects.

How many questions are on the ACI Grade I written exam and how long is it?

The written exam is closed book, lasts 1 hour, and has 55 multiple-choice questions. ACI states there are between five and ten questions on each required ASTM test method or practice, so the exam is heavily weighted toward exact procedures, apparatus, and numerical tolerances rather than theory.

What is the passing score for the ACI Grade I exam?

The written exam has a dual rule: at least 60% correct on each individual ASTM test method or practice AND at least 70% overall. A strong overall score cannot offset failing one method category. Candidates must also pass the closed-book performance exam, which requires demonstrating six of the methods and verbally describing C172 sampling.

Are there prerequisites for the ACI Grade I exam?

No. There are no formal education, experience, age, or ACI membership prerequisites for Grade I certification. However, ACI strongly recommends studying the CP-1 Technician Workbook and the current editions of the seven ASTM standards, and completing a preparation class offered by a local ACI sponsoring group or chapter before testing.

What does the ACI Grade I performance exam involve?

The performance exam is closed book. The candidate must physically demonstrate six of the seven required test methods and practices and give a verbal description of Practice C172 (sampling). An ACI examiner scores each procedure on a checklist; omitting a critical step can cause failure even when other tests are performed correctly. Both the written and performance exams must be passed for certification.

How long is the ACI Grade I certification valid?

Grade I certification is valid for 5 years from the date all requirements are completed. Recertification requires successfully completing both the written and performance examinations again, which keeps technicians current as ASTM standards are periodically revised. The current cited editions are C1064-23, C172-17, C143-20, C138-23, C231-24, C173-24, and C31-24.

Same family resources

Explore More ACI Concrete Certifications

Continue into nearby exams from the same family. Each card keeps practice questions, study guides, flashcards, videos, and articles in one place.