General Knowledge
10%of exam
Installation Requirements
7-8%of exam
Services + Feeders + Branch
17-18%of exam
Overcurrent Protection
5%of exam
Grounding + Bonding
12-13%of exam
Conductors + Cables
10%of exam
Raceways + Boxes
12-13%of exam
Hazardous Locations
12-13%of exam
Low Voltage + Comms
5%of exam
Lighting + Signs + Equipment
7-8%of exam
Quick Facts
- Exam
- TN LLE
- Provider
- Prov
- Questions
- 40 MCQ
- Time
- 2 hours
- Pass
- 73% (29 of 40)
- Format
- Open book
- Code
- NEC 2017
- Fee
- $53 (Prov)
- License scope
- Under $25,000
- Retakes
- Unlimited, no wait
Ohm's Law Triangle
V on top; I and R below
Series vs Parallel
Series
- One current path
- Resistances add
- Drops sum to source
Parallel
- Shared voltage
- Currents add
- Resistance below smallest
One path vs many
NEC Layout
- Article 90
- Purpose + scope
- Article 100
- Definitions
- Chapters 1-4
- General rules
- Chapter 5
- Special occupancies
- Chapter 6
- Special equipment
- Chapter 7
- Special conditions
- Chapter 8
- Communications
- Chapter 9
- Tables + notes
NEC Chapter Map
90 scope, 100 defs, 110 install, then chapters
Ohm's Law + Power
- V = IR
- Ohm's law
- I = V/R
- Solve current
- P = VI
- Resistive power
- P = I2R
- Power from current
- E = Pt
- Energy over time
- kWh
- Billing energy unit
- milli (m)
- x0.001
Installation + Safety
- Listed
- Third-party approved
- Labeled
- Marked by evaluator
- Working space
- 3 ft typical110.26
- Readily accessible
- Reach without obstacles
- OSHA 1926
- Job-site safety
- Disconnect marking
- Identify purpose
- Guarding
- Protect live parts
GFCI vs AFCI
GFCI
- Shock protection
- Ground-fault current
- Wet + damp areas
AFCI
- Fire protection
- Arc-fault current
- Dwelling living areas
Shock vs fire
GFCI vs AFCI Picker
- Kitchen countertop receptacle→GFCI required(210.8(A)(6))
- Bathroom receptacle→GFCI required(210.8(A)(1))
- Garage or outdoor receptacle→GFCI required(210.8(A)(2)(5))
- Basement or laundry area→GFCI required(210.8(A)(7)(10))
- Dwelling bedroom circuit→AFCI required(210.12(A))
- Shock and arc risk both→Use dual-function device(Combination protection)
- Extend circuit into covered area→AFCI still applies(210.12(A) extension)
- Commercial kitchen countertop→GFCI required(210.8(B))
Load Calculations
- General lighting
- 3 VA/ft2220.12
- Small appliance
- 1500 VA each, min 2
- Laundry circuit
- 1500 VA, one 20A
- Range demand
- Table 220.55
- Dryer demand
- 5000W or nameplate220.54
- Continuous load
- Use 125%
- Service calc
- Standard or optional method
Branch Circuit vs Feeder
Branch circuit
- After final OCPD
- Supplies outlets
- Article 210
Feeder
- Before final OCPD
- Supplies panels
- Article 215
After vs before OCPD
Services + Feeders + Branch
- Article 230
- Service conductors
- Article 215
- Feeder sizing
- Article 210
- Branch circuits
- Service disconnect
- Max 6 handles
- Feeder OCPD
- At least calc load
- Multiwire circuit
- Shared neutral
- Receptacle spacing
- 12 ft rule210.52
GFCI + AFCI Locations
- GFCI
- Kitchen countertops
- GFCI
- Bathrooms
- GFCI
- Garage + outdoor
- GFCI
- Basement + laundry
- AFCI
- Bedrooms + living areas
- Dual-function
- Shock + arc
Ampacity vs OCPD Rating
Ampacity
- Conductor current limit
- Table 310.15(B)(16)
- Heat-based rating
OCPD rating
- Breaker or fuse size
- Table 240.6(A)
- Protects the conductor
Wire limit vs device size
OCPD + Conductor Picker
- Continuous load calculated→Apply 125% factor(210.19(A))
- Conductor size needed→Read Table 310.15(B)(16)(Match ampacity)
- Terminals rated 60C→Use 60C column(Typical 100A or less)
- Terminals rated 75C→Use 75C column(Typical over 100A)
- Ampacity between std sizes→Round up OCPD(240.4(B))
- 14/12/10 AWG copper→Cap at 15/20/30A(240.4(D) overrides)
- Motor branch circuit→Apply Table 430.52(Not general OCPD rule)
- Over 3 current-carrying conductors→Apply adjustment factor(310.15(C)(1))
Overcurrent Protection
- Article 240
- Overcurrent devices
- Standard sizes
- 240.6(A) list
- Next-size-up
- 240.4(B) rounding
- Small conductor rule
- 240.4(D) caps size
- Motor OCPD
- Table 430.52 multiplier
- Tap rule
- 240.21 exceptions
Grounding vs Bonding
Grounding
- Connects to earth
- Stabilizes voltage
- GEC route
Bonding
- Joins metal parts
- Creates fault path
- EGC route
Earth vs continuity
Grounding Electrode Picker
- Metal water pipe 10ft+→Use as electrode(250.52(A)(1))
- Concrete-encased rebar present→Use ufer ground(250.52(A)(3))
- Ground ring 20ft or more→Use as electrode(250.52(A)(4))
- Single rod exceeds 25 ohms→Add second rod(250.53(A)(2))
- Multiple electrodes present→Bond into one system(250.50)
- No qualifying electrode present→Install made electrode(Rod, plate, or ring)
Grounding + Bonding
- GEC sizing
- Table 250.66
- EGC sizing
- Table 250.122
- Water pipe electrode
- 10 ft in earth250.52(A)(1)
- Concrete-encased electrode
- Ufer ground250.52(A)(3)
- Ground rod
- 8 ft minimum
- Rod resistance
- 25 ohm or add rod250.53(A)(2)
- Bonding jumper
- Table 250.102(C)(1)
- Main bonding jumper
- Neutral-to-ground bond
Wire Color Code
White/gray grounded; green/bare ground; black hot
THHN vs THWN
THHN
- Dry locations only
- 90C rated
- Thermoplastic + nylon
THWN
- Wet locations rated
- 75C typical
- Moisture-resistant nylon
Dry vs wet rating
Conductors + Ampacity
- Ampacity table
- 310.15(B)(16)
- 60C terminals
- Typical 100A or less
- 75C terminals
- Typical over 100A
- THHN
- Dry, 90C rated
- THWN
- Wet-rated
- Adjustment factor
- Over 3 current-carrying wires
- White/gray
- Grounded conductor
- Green/bare
- Equipment grounding conductor
Conduit Fill Steps
1 wire 53%; 2 wires 31%; 3+ 40%
Raceway + Conduit Fill
- 1 conductor
- 53% fill
- 2 conductors
- 31% fill
- 3+ conductors
- 40% fill
- EMT
- Thin-wall metal raceway
- PVC
- Nonmetallic raceway
- Burial depth
- Table 300.5
Box Fill Rules
- Box fill
- Table 314.16(B)
- Device yoke
- Counts as 2
- Internal clamp
- Counts as 1
- EGCs
- Counted as 1 total
- Fixture stud/hickey
- Counts as 1
Hazard Class Order
I gas, II dust, III fibers
Hazardous Location Classes
- Class I
- Flammable gas/vapor
- Class II
- Combustible dust
- Class III
- Ignitable fibers/flyings
- Division 1
- Normal hazard presence
- Division 2
- Abnormal/accidental presence
- Seal fitting
- Stops gas migration
- Explosion-proof
- Contains internal ignition
Low Voltage + Comms
- Article 725
- Class 1/2/3 circuits
- Power-limited
- Reduced fire/shock risk
- Article 760
- Fire alarm circuits
- Article 800
- Communications systems
- Separation rule
- Power vs low-voltage
Lighting + Signs + Equipment
- Article 410
- Luminaires
- Storage clearance
- 410.16 minimum
- Article 600
- Electric signs
- Sign disconnect
- 600.6 required
- Article 422
- Fixed appliances
- Listed equipment
- Follow install instructions
Common Traps
Ampacity vs OCPD
Ampacity rates the wire ≠ OCPD sizes the device
Grounding vs Bonding
Grounding connects to earth ≠ Bonding joins metal parts
Continuous vs Noncontinuous Load
Continuous runs 3+ hours ≠ Noncontinuous needs no 125%
Service vs Feeder
Service comes from utility ≠ Feeder follows service equipment
Class I vs Class II
Class I is gas/vapor ≠ Class II is dust
GFCI vs AFCI
GFCI stops shock ≠ AFCI stops arcing fires
Box Fill vs Conduit Fill
Box fill counts volume ≠ Conduit fill uses percent area
Last Minute
- 1.40 questions; 2-hour time limit
- 2.73% passing score (29 of 40)
- 3.NEC 2017 controls all answers
- 4.Open book: NEC + Ugly's + OSHA
- 5.LLE license caps at $25,000
- 6.Unlimited retakes, no waiting period
- 7.GFCI = shock; AFCI = arc
- 8.Continuous loads always get 125%
- 9.Table 310.15(B)(16) sets ampacity
- 10.Table 250.122 sizes grounding conductors
- 11.Table 250.66 sizes grounding electrode conductor
- 12.Conduit fill: 53/31/40 percent
- 13.Motor OCPD uses Table 430.52
- 14.Confirm current NEC edition first
Explore More Tennessee Limited Licensed Electrician
Continue into nearby exams from the same family. Each card keeps practice questions, study guides, flashcards, videos, and articles in one place.
More From This Family
Videos and articles for deeper review.
