PracticeVideosBlogFlashcards
Cheat sheet

MD Boiler Operator Cheat Sheet

Maryland Law: Editorial Revision Group

Not publishedof exam

Grade Horsepower ThresholdsAttendance & Monitoring RulesExam, Renewal & Inspection LawLargest Single Unit Rule

Boilers, Valves & Safety Controls

Not publishedof exam

Boiler Types & ASME CodesSafety Valves & Gauge GlassLow-Water Cutoff & ControlsPumps & Steam Header Valves

Burners, Combustion & Emergencies

Not publishedof exam

Combustion, Draft & PurgeFlame Safeguard SequenceSequential & Emergency OperationsLow-Water vs Tube Rupture

Water Treatment & Blowdown

Not publishedof exam

Scale, Sludge & CarryoverDeaeration & Chemical TreatmentBottom vs Surface BlowdownZeolite Softener Limits

Auxiliaries, Chillers & Electricity

Not publishedof exam

Condensers, NPSH & PumpsChillers & Refrigeration CycleBasic DC & AC ElectricityMotor Overload Protection

Quick Facts

Licensing Board
Maryland Board of Stationary Engineers
Exam Delivery
PSI; qualification approval before scheduling
Scored Outline Count
G5–G4: 60; G3–G1: 80
Possible Additional Items
5–10 experimental, unscored; extra time
Answering Time
120 minutes for scored examination
Passing Score
70%: 42/60 or 56/80
Book Policy
G5–G4 approved open-book; G3–G1 closed-book
Licence Term
Normally two years; statutory stagger exception
Revision Filters
Five editorial groups; official outlines separate

Maryland 5-Grade Horsepower Ladder

30-99 G5/G4, 100-299 G3, 300-499 G2, 500+ G1

G5: 30-99 HP non-publicG4: 30-99 HP any buildingG3: 100-299; G2: 300-499; G1: 500+

Grades 5–4 vs Grades 3–1 PSI Exams

Grades 5 & 4

  • 60 scored-outline items; 120 minutes
  • Open book (approved references)
  • Need 42 correct (70%)

Grades 3, 2 & 1

  • 80 scored-outline items; 120 minutes
  • Closed book examination
  • Need 56 correct (70%)

60 open-book vs 80 closed-book

Maryland License Grade Picker

  1. Statutory heating-boiler definition applies→Stationary-service licensing definition excludes heating boilers(Inspection obligations are a separate question)
  2. Hot-water statutory heating definition→Pressure ≤160 psig OR temperature ≤250°F(Statutory OR; distinct from ASME shorthand)
  3. 30-99 HP in non-public building→Grade 5 Stationary Engineer
  4. 30-99 HP in public building→Grade 4 Stationary Engineer
  5. Largest single unit 100-299 HP→Grade 3 Stationary Engineer
  6. Largest single unit 300-499 HP→Grade 2; 500+ HP Grade 1

Grade Horsepower & Trigger Rules

License Trigger
Over 15 psi AND 30+ HP
30 HP Equivalent
About 1,003,000 Btu per hour
1 Boiler HP
Evaporates 34.5 lb/h from-and-at 212°F≈33,475 Btu/h thermal output
Grade 5 Scope
30-99 HP, non-public building
Grade 4 Scope
30-99 HP, any building
Grade 3 Scope
100-299 HP largest single unit
Grade 2 Scope
300-499 HP largest single unit
Grade 1 Scope
500 HP or more; statutory conditions

2-Year Power Boiler Inspection Extension

Board may extend certificate interval; conditions must all qualify

Power boiler; Board-approved extension onlyContinuous internal treatment; experienced PE supervisesOutage date, time and reason recordsWater analyses: ≤48 operating-hour intervalsAnnual external inspection remains separate

COMAR 09.17 Alarm vs Shutdown Picker

  1. High stack flue gas temperature→Sound alarm AND shut burner
  2. Steam high-pressure or low/high-water condition→Specified monitoring alarm and automatic shutdown
  3. Low steam pressure or burner off→Alarm required; shutdown follows applicable safeguards(Not shutdown triggers under section .07)
  4. Boiler shuts down automatically→Licensee/designee physically inspects before restart(Qualifying system shutdown under section .07)

Attendance: Qualified Monitoring Exceptions

G5, No Qualified Monitoring
Visit every 24 operating hours minimum
G4 Public, No Monitoring
Attend continuously; special school rule applies
G4 School, No Monitoring
School hours; other hours ≥150 occupants
G5, Qualified Monitoring
Weekly visit; 24-hour availability; daily log
G4–G1 Monitored Public
Visit every eight open hours minimum
G3–G1 Monitored Non-Public
Scheduled visits not required; duties remain
Qualifying Monitoring
24-hour computerized monitoring plus automatic controls
300 HP or More
Monitor, indicate AND record specified points
Qualifying Shutdown Manual Reset
Licensee/designee physically inspects before restart
Monitored School G4 Exception
School-hours/≥150-occupant condition still applies
All Monitored Attendance Exceptions
Responsibility, 24-hour availability, daily log remain

Exam, Renewal & Inspection Law

G5-G4 Pass Mark
42 of 60 items correct70%
G3-G1 Pass Mark
56 of 80 items correct70%
Board FAQ: Reapply After Failure
First 30 days; subsequent requests 60
PSI Registration Validity
90 days; fee nonrefundable, nontransferable
Score Validity
Apply for license within 2 years
Expired > 24 Months
Non-renewable; must retest
Covered Power Boiler Inspections
Annual inspections; approved certificate extension possible
Accident Notice
Notify Chief Inspector within 24h
Unauthorized Material During Examination
Reject application; reexamination barred ≥1 year

PSI Outline Counts: Part 1

General knowledge and problem solving
G5–4: 20; G3: 10; G2–1: 5
Basic electricity
G5–4: 5; G3: 5; G2–1: 5
Boiler types and equipment
G5–4: 5; G3: 10; G2–1: 5
Burners and fuel train
G5–4: 5; G3: 10; G2–1: 10
Pumps and valves
G5–4: 5; G3: 10; G2–1: 10
Sequential operations
G5–4: 0; G3: 10; G2–1: 10

PSI Outline Counts: Part 2

Inspections and maintenance
G5–4: 5; G3: 5; G2–1: 10
Central station and chillers
G5–4: 0; G3: 5; G2–1: 5
Water treatment
G5–4: 5; G3: 5; G2–1: 10
Emergency operations
G5–4: 5; G3: 5; G2–1: 5
Auxiliary equipment
G5–4: 5; G3: 5; G2–1: 5

Firetube vs Watertube Boilers

Firetube Boiler

  • Hot gases pass inside tubes
  • Large water volume, slower response
  • Often lower duty; design ratings govern

Watertube Boiler

  • Water circulates inside the tubes
  • Often faster response; design-dependent
  • Handles high pressures and loads

Gas in tubes vs water

Boiler Types, ASME & Fittings

ASME Section I
Power-boiler construction; steam above 15 psig
ASME Section IV
Heating-boiler construction; applicable limits and edition
ASME Section VIII
Pressure-vessel construction; scope and exclusions apply
MAWP and Valve Settings
At least one valve ≤MAWPPower boiler, COMAR .24G
Safety Valve Rule
Direct connection; no shutoff valve
Try-Lever Test
Movement check, not set-pressure calibration
Water Column
Dampens surges; test per approved procedure
Non-Return Valve
Prevents backflow when boiler pressure drops
Existing Power Boiler Additional Valves
Settings ≤103% MAWP; full conditions apply

Operating Control vs High-Limit Control

Operating Control

  • Cycles or modulates burner daily
  • Holds normal operating pressure
  • Normal cycling follows control design

High-Limit Control

  • Independent protective limit on unsafe conditions
  • Setting coordinated with approved relief protection
  • Reset mode follows applicable code/design

Normal cycling vs safety lockout

Three Ts of Complete Combustion

Temperature, Turbulence, and Time with right oxygen

Temperature: ignite fuelTurbulence: mix air-fuelTime: burn before tubes

Low-Water Emergency vs Tube Rupture

Low-Water Condition

  • Secure heat input under emergency procedure
  • Dry/overheated boiler: no water addition
  • Inspect and obtain authorized restart clearance

Tube Rupture

  • Secure heat input under emergency procedure
  • Feedwater decision depends on boiler condition
  • Isolation follows equipment-specific approved procedure

Overheating risk vs rupture-specific response

Boiler Emergency Action Picker

  1. Low water; dry/overheated boiler suspected→Secure heat input; no water addition(Approved shutdown and inspection before restart)
  2. Boiler tube ruptures on line→Approved emergency shutdown; keep personnel clear(Condition/equipment determine feedwater and isolation)
  3. Safety valve lifts repeatedly→Prevent overpressure; investigate controls through procedure(Never gag or obstruct relief)
  4. Burner trips on flame failure→Investigate cause; approved purge before restart(No repeated blind resets)
  5. Boiler accident or explosion occurs→Notify Chief Inspector within 24h

Burners, Draft & Flame Safeguard

3 Ts of Combustion
Temperature, turbulence, and time
Complete Hydrocarbon Combustion
CO₂ and water; other products possible
Incomplete Sign
Carbon monoxide, smoke, or soot
Forced Draft
Fan pushes air toward combustion chamber
Induced Draft
Fan draws combustion gases toward stack
Balanced Draft
Both fans; controlled furnace pressure
Pre-Purge / Post-Purge
Prescribed airflow clears accumulated combustibles
Flame Scanner
Flame-safeguard system trips fuel upon failure

Bottom Blowdown vs Surface Blowdown

Bottom Blowdown

  • Drawn from lowest mud drum
  • Short, intermittent valve operation
  • Removes settled sludge solids

Surface Blowdown

  • Skims just below water line
  • Metered continuous or intermittent design
  • Controls total dissolved solids (TDS)

Settled sludge vs surface TDS

Water Problems: Treatment-Plan Decisions

  1. TDS exceeds approved treatment-plan limit→Adjust blowdown under the approved plan(No universal valve opening or flow)
  2. Sludge settles in mud drum→Approved intermittent bottom-blowdown procedure
  3. Calcium and magnesium hardness present→Verify softener and approved treatment plan
  4. Dissolved oxygen causing tube pitting→Check deaeration and prescribed scavenger treatment(Qualified treatment specialist sets chemical dose)

Water Treatment & Blowdown

Scale
Hard deposits; hardness often contributes
Sludge
Loose settled suspended solids
Dissolved Oxygen
Causes localized tube metal pitting
Deaerator
Heats and vents non-condensable gases
Oxygen Scavenger
Chemically removes residual dissolved O2
Zeolite Softener
Swaps Ca/Mg ions for sodium
Bottom Blowdown
Short intermittent removal of sludge
Surface Blowdown
TDS control; continuous or intermittent design

Four-Step Refrigeration Cycle Order

Compressor, Condenser, Expansion device, Evaporator in loop

Compressor: raises P and TCondenser: rejects heatExpansion drops P; Evaporator cools

Centrifugal vs Positive Displacement Pump

Centrifugal Pump

  • Uses rotating impeller velocity
  • Flow drops as pressure rises
  • Closed discharge can overheat; follow manufacturer

Positive Displacement

  • Moves fixed volume per stroke
  • Builds destructive pressure if blocked
  • Protect blocked discharge with approved relief

Variable flow vs fixed displacement

Auxiliaries, Pumps & Chillers

Elevated Deaerator
Provides NPSH to feed pump
Cavitation
Vapor bubbles form, then collapse
Surface Condenser
Condenses exhaust; supports turbine vacuum
Economizer
Preheats feedwater using flue gas
Compressor
Raises refrigerant pressure and temperature
Condenser (Chiller)
Rejects heat, liquefies refrigerant
Expansion Device
Throttles pressure; refrigerant partly flashes
Evaporator
Absorbs heat from building load

Basic Electricity & Motor Controls

Ohm's Law
Volts equal amps times ohmsE = I × R
DC Electric Power
Watts equal volts times ampsP = E × I; DC
Series Circuit
Same current; voltages add up
Parallel Circuit
Same voltage; branch currents add
Motor Overload
Protects windings from sustained overcurrent
Fuses / Breakers
Protect against short-circuit faults
Lockout / Tagout
Isolate, lock, control stored energy, verify
AC Real Power
Single-phase: V × I × power-factor

Common Traps

Single-Unit Capacity vs Plant Capacity

Licence grade: largest individual regulated unit ≠ Plant total: not the grade calculation

Engineer Licensing vs Equipment Inspection

Title 6.5: engineer grades and attendance ≠ Title 12-9: equipment inspection and certificates

Routine Feedwater vs Overheated Dry Boiler

Normal operation: maintain approved water level ≠ Overheated dry boiler: no water addition

Gauge Indication vs Verified Water Level

Motionless glass: potentially obstructed, not proof ≠ Approved verification: investigate uncertain water level

Softening vs Deaeration

Softener: exchanges calcium and magnesium ions ≠ Deaerator: heats and removes dissolved gases

Ordinary Reciprocity vs Military Recognition

Ordinary route: no out-of-state reciprocity ≠ Qualified military relocation: separate recognition provisions

Last Minute

  1. 1.Trigger: >15 psi AND ≥30 HP
  2. 2.Heating boilers: excluded from licensing definition
  3. 3.Grade: largest single regulated unit
  4. 4.Pass: 70% (42/60; 56/80)
  5. 5.G5–4: approved open-book; G3–1: closed-book
  6. 6.Reapplication: first 30 days; subsequent 60
  7. 7.Power certificate extension: Board-approved, not automatic
  8. 8.Required certification: display licence with photograph
  9. 9.Identification: valid government-issued photo ID available
  10. 10.Boiler accident notice: within 24 hours
  11. 11.Safety relief: no intervening shutoff valve
  12. 12.Dry/overheated boiler: no water addition
  13. 13.Steam admission: equipment-specific approved pressure sequence
  14. 14.Qualifying manual reset: physical inspection first
Same family resources

Explore More Boiler Operator

Continue into nearby exams from the same family. Each card keeps practice questions, study guides, flashcards, videos, and articles in one place.