4.2 Visual Inspection Requirements

Key Takeaways

  • Visual inspection is the first stage of inspection, completed before any testing begins — it catches defects that testing alone may miss and informs the test plan
  • For initial verification, visual inspection covers 100% of the new work; periodic inspection uses sampling (covered in Chapter 10)
  • Key checks include conductor connections, cable selection and routing, conductor identification per BS 7671 Table 51.1, fire barriers and segregation, earthing and bonding conductor presence and size, RCD presence where required, IP rating for location, and consumer unit enclosure
  • Since Amendment 2 of the 18th Edition, consumer units in domestic premises must be enclosed in a non-combustible enclosure or located in a fire-protected cabinet
  • The schedule of inspections records each visual inspection item as satisfactory or notes defects for remedial action
Last updated: August 2026

Visual Inspection: The First Stage

Visual inspection is the first stage of the inspection process and must be completed before any testing begins. It serves two purposes: it identifies defects that testing alone may not reveal (e.g. damaged cable insulation, wrong cable routing, missing fire barriers), and it informs the test plan by flagging areas that need closer attention.

For initial verification, visual inspection covers 100% of the new work — every connection, accessory, and cable run must be checked. For periodic inspection, sampling is used (covered in Chapter 10), but the principle that visual inspection precedes testing remains the same.

A serious defect found during visual inspection should halt further testing until the defect is corrected — there is no value in testing an installation that is visibly non-compliant.

What the Inspector Checks

The visual inspection is systematic. The inspector works through the installation checking each of the following:

Conductors and Connections

  • Connection of conductors — all conductors are securely and correctly connected at terminals, with no loose strands, no stray conductor outside the terminal, and correct tightening.
  • Cable selection — conductor size and type are appropriate for the design current, voltage drop, and ambient conditions.
  • Cable routing — cables are routed to avoid mechanical damage, heat, and where appropriate are in prescribed zones (e.g. within 150 mm of ceilings or corners — the "safe zones").

Identification and Labelling

  • Conductor identification — colours and markings comply with BS 7671 Table 51.1 (brown for line, blue for neutral, green-and-yellow for protective conductors).
  • Circuit labelling — each circuit is clearly identified at the consumer unit or distribution board.
  • Warning notices — present where required (e.g. the RCD six-monthly test notice required by Reg 514.12.2, "Safety Electrical Connection — Do Not Remove" label on main earthing and bonding terminals).

Protection and Segregation

  • Fire barriers and segregation — cables passing through fire-rated structures are sealed; Band I (ELV) and Band II (LV) circuits are segregated where required by BS 7671 Section 527.
  • Presence of RCDs — where required by BS 7671 (e.g. socket-outlets rated at 32 A or less, bathrooms, outdoors, buried cables in walls).
  • Methods of protection against electric shockbasic protection (insulation, barriers, enclosures, obstacles — IP2X or IPXXB, IP4X or IPXXD) and fault protection (automatic disconnection of supply, double insulation, RCDs).

Earthing and Bonding

  • Presence and size of earthing conductor — checked visually for condition, routing, and connection at the main earthing terminal (MET).
  • Presence and size of main protective bonding conductors — to incoming gas and water services, and other extraneous-conductive-parts.
  • Adequacy of connections — clamps are tight, correctly labelled, and accessible.

Location and Environment

  • IP rating and location suitability — equipment in bathrooms, saunas, swimming pools, and other special locations is correct for the zone (e.g. IPX4 in zone 2 of a bathroom per Section 701).
  • Mechanical damage protection — cables in conduit, trunking, or with adequate mechanical protection where exposed.
  • Accessibility — switchgear, consumer units, and accessories are accessible for operation, inspection, and maintenance per BS 7671 Section 513.

Consumer Unit Enclosure

  • Non-combustible enclosure — since Amendment 2 of the 18th Edition (BS 7671:2018+A2:2022), consumer units and switchgear assemblies in domestic (household) premises must be enclosed in a non-combustible enclosure (e.g. steel), or be located in a fire-protected cabinet. This requirement, now embedded in the main body of BS 7671, remains a key visual inspection check.

Connection to the Schedule of Inspections

The items checked during visual inspection are recorded on the Schedule of Inspections — the formal document that accompanies an Electrical Installation Certificate (EIC) or Electrical Installation Condition Report (EICR). The schedule uses a tick-box format covering:

  • Connection of conductors
  • Cable selection and routing
  • Conductor identification
  • Fire barriers and segregation
  • Protective conductors (earthing and bonding)
  • Protection against electric shock
  • Protection against thermal effects
  • Switchgear and protective devices
  • Labelling and warning notices
  • Location and environment

Each item is recorded as satisfactory or, where a defect is found, noted for remedial action. The schedule is a mandatory part of the EIC — a certificate without its schedule of inspections is incomplete and invalid.

Visual Inspection Checklist

ItemWhat to checkStandard reference
Conductor connectionsSecure, correct, no loose strandsBS 7671 Chapter 53
Cable selectionCorrect size and type for loadBS 7671 Chapter 52
Conductor identificationColours per Table 51.1BS 7671 Table 51.1
Fire barriersSealed penetrations, segregationBS 7671 Section 527
Earthing conductorPresent, correct size, connected at METBS 7671 Chapter 54
Main bondingTo gas, water, extraneous partsBS 7671 Section 544
RCD presenceWhere required (sockets, bathrooms, outdoors)BS 7671 Sections 411, 415
Consumer unit enclosureNon-combustible (domestic)BS 7671 532.6
IP rating and zonesCorrect for locationBS 7671 Sections 701, 702
AccessibilitySwitchgear accessibleBS 7671 513.1
LabellingRCD test notice, circuit schedulesBS 7671 Section 514