3.4 Grounding Systems & Impedance Grounding
Key Takeaways
Grounded vs. grounding: the 'grounded conductor' is the current-carrying neutral bonded to ground at the service; the 'grounding conductor' (EGC) bonds non-current-carrying metal parts and carries fault current only during a fault.
System grounding types: solid, low-resistance, high-resistance, reactance, and ungrounded — each trades fault-current magnitude against service continuity and equipment damage.
High-resistance grounding limits ground-fault current to about 5-10 A (alarm, do not trip); low-resistance grounding limits it to roughly 200-400 A (trip selectively).
The equipment grounding conductor (EGC) provides the low-impedance metallic return path that lets overcurrent devices clear a ground fault quickly.
Never open the secondary of an energized current transformer — the developing high voltage can break down insulation and injure personnel; short the secondary first if a burden must be removed.
Grounded vs. Grounding: The NEC Distinction
Quick Answer: The grounded conductor is the current-carrying conductor bonded to ground at the service (usually the neutral). The grounding conductor (equipment grounding conductor, EGC) bonds non-current-carrying metal parts together and to ground; it carries current only during a fault.
NEC Article 100 and 250 make this distinction because the two conductors serve different purposes:
- Grounded conductor: carries normal load current (unbalanced neutral current in a 3φ 4-wire system) and is bonded to the grounding electrode system at the service disconnect (main bonding jumper). It is a current-carrying conductor that happens to be grounded.
- Equipment grounding conductor (EGC): bonds equipment enclosures, raceways, and cable trays together and to the system grounding point. It carries fault current only when a phase-to-ground fault occurs, and its low impedance is what allows the overcurrent device to trip quickly.
On a 480Y/277 V service, the neutral is the grounded conductor; the green/bare bond wire in the conduit is the EGC. Mixing these up on the exam is a guaranteed wrong answer.
System Grounding Types
| Type | Ground-Fault Current | Typical Use | Action on First Ground Fault |
|---|---|---|---|
| Solid | High (full available fault) | Commercial/industrial services, 480Y/277, 208Y/120 | Trip immediately |
| Low-resistance | ~200-400 A | Medium-voltage industrial (4.16 kV, 13.8 kV) | Trip selectively |
| High-resistance | ~5-10 A | Critical continuous-process plants, generators | Alarm, do not trip |
| Reactance | Limited (reactor in neutral) | Large generators, utilities | Trip or alarm |
| Ungrounded | ~0 (capacitive charging only) | Old installations, high continuity needs | Alarm; locate before second fault |
Why Limit Ground-Fault Current?
A solidly grounded 13.8 kV system can deliver 20,000+ A into a ground fault. That current does three damaging things:
- Arc burn at the fault point: melts cable, switches, and bus at the arc location.
- Mechanical stress on the equipment: the magnetic forces from high fault current can deform bus bars and damage transformer windings.
- Thermal damage to the neutral resistor/reactor and winding: sustained ground-fault current overheats the iron and copper.
Impedance grounding inserts a resistor or reactor between the transformer neutral and ground so the ground-fault current is predictable and limited. Industrial 4.16 kV and 13.8 kV systems often use low-resistance grounding (~400 A) to allow selective relaying while reducing damage. High-resistance grounding (~5-10 A) is used where continuity of service is critical (refineries, hospitals, data centers) — the system alarms, the operator locates the fault, and the process keeps running until a planned shutdown.
The Ground-Fault Current Path and the EGC
On a solidly grounded system, a ground fault on a piece of equipment sends current from the source, through the phase conductor, through the fault to the equipment enclosure, through the EGC back to the service neutral-ground bond, and through the grounded neutral to the source. The EGC's impedance determines how much current flows and how fast the breaker trips. A high-impedance EGC (loose connection, undersized wire, corroded bond) means low fault current and a slow (or no) trip — exactly the condition that starts fires and shocks workers. This is why NETA testing includes the ground-fault circuit impedance test and visual inspection of bonding and grounding connections.
Ground-Fault Detection
Three common detection schemes:
- Residual (wye-connected CTs): the three phase CT secondaries are summed. In a balanced system the sum is zero; a ground fault produces residual current. Simple and common on 51N/50G relays.
- Zero-sequence (core-balance) CT: all three phase conductors (and the neutral if present) pass through one CT. Any imbalance indicates ground-fault current. Sensitive — used for GFPE and high-resistance grounded system alarms.
- Neutral CT or shunt: a CT on the neutral-to-ground bond directly measures ground-fault current. Used on resistance-grounded systems where the fault current returns through the resistor.
On a high-resistance grounded system the neutral resistor is sized so the available ground-fault current equals or slightly exceeds the system's total charging current (so the zero-sequence capacitive current is canceled and the alarm is meaningful). A 13.8 kV system with 15 A charging current might use a 15-20 A neutral resistor.
The Open-CT Hazard Rule (Critical Safety)
A current transformer is a constant-current source (within its accuracy range) on the secondary side. The secondary current is fixed by the primary current and the turns ratio: Isec = Iprim / N. The voltage developed across the secondary is Vsec = Isec × Zburden. If you remove the burden (open the secondary), Zburden approaches infinity and Vsec rises until the core saturates — but saturation still leaves a high, dangerous peak voltage that can:
- Break down the CT's secondary insulation.
- Produce a lethal shock hazard at the open terminals.
- Drive the CT into saturation that ruins its accuracy until demagnetized.
Rule: never open the secondary of an energized CT. If you must remove a relay or meter, short the CT secondary first with a CT shorting block or jumper, then disconnect the burden. Many test sets and switchgear CT terminal blocks include built-in shorting bars that engage before the burden lifts. NETA field work routinely involves isolating CTs for injection testing — the shorting sequence is non-negotiable and a frequent exam question.
The same rule does not apply to potential transformers (PTs) — a PT secondary can be opened (like any voltage source) but must never be shorted, and PT secondaries should be fused and grounded.
Exam Trap
A common trap confuses 'solidly grounded' with 'low-impedance grounded.' Solid grounding means the neutral is bonded to ground with no intentional impedance — the fault current is limited only by the source and transformer impedances. Low-resistance and high-resistance grounding add a deliberate resistor in the neutral. If a question says 'resistance-grounded,' do not treat it as solidly grounded for fault calculations — the resistor dominates Z0.
An 'impedance-grounded' medium voltage system uses a resistor or reactor in the neutral to:
Increase available ground-fault current
Boost excitation current
Limit ground-fault current to a reduced, predictable value
Reduce line-to-line voltage under normal conditions
Before disconnecting a relay from the secondary of an energized current transformer, you must:
Open the CT secondary first to de-energize it
Short the CT secondary first, then disconnect the relay
Remove the CT primary fuse
Increase the primary load to reduce CT current
Sections you finish are checked off in the contents.