Safety
15%of exam
Electrical Testing Fundamentals and Theory
25%of exam
Component Testing
55%of exam
Systems and Commissioning
5%of exam
Quick Facts
- Exam
- NETA ETT Level 2
- Credential
- Certified Assistant Technician
- Items
- 100 multiple-choice
- Time
- 2 hours
- Pass
- 410 scaled (200-500)
- Format
- Closed-book, onsite proctored
- Delivery
- Pearson VUE
- Scheduling
- Set testing periods; schedule early
- Practice exam
- $100, one hour, 60-day review
- Eligibility
- 2 years, NAC employed
- Training
- 40 safety, 160 electrical hours
- Supervision
- Under Level 3 or 4
Ground Lead Order
Ground end first, remove it last
Level 2 vs Level 3
Level 2
- Limited testing work
- Direct supervision required
- 15/25/55/5 weights
Level 3
- Supervises Levels 1-2
- Performs power switching
- 13/23/47/17 weights
Assist vs supervise
Shock Boundary Picker
- 208 V panel, fixed parts→3 ft 6 in limited
- 480 V, qualified entry→1 ft 0 in restricted
- 13.8 kV gear, fixed parts→5 ft 0 in limited
- 13.8 kV qualified entry→2 ft 2 in restricted
- 25 kV gear, fixed parts→6 ft 0 in limited
- Overhead movable conductor→10 ft 0 in limited
- Unqualified person present→Qualified escort required
- Need arc flash boundary→Calculate it(Not a voltage table)
Approach Boundaries
- Limited approach
- Unqualified needs qualified escort
- Restricted approach
- Qualified plus shock PPE
- Arc flash boundary
- 1.2 cal/cm2 incident energy
- Prohibited boundary
- Deleted in 2015 editionNFPA 70E
- 50-150 V fixed
- 3 ft 6 in limited
- 151-750 V fixed
- 3 ft 6 in limited
- 151-750 V restricted
- 1 ft 0 in
- 751 V-15 kV fixed
- 5 ft 0 in limited
- 751 V-15 kV restricted
- 2 ft 2 in
- 15.1-36 kV restricted
- 2 ft 7 in
- Movable conductor
- 10 ft through 72.5 kV
- Boundary table
- NFPA 70E 130.4(E)(a)
PPE Cal Ladder
Four, eight, twenty-five, forty
Limited vs Restricted Boundary
Limited
- Outer shock boundary
- Unqualified needs escort
- Fixed by voltage
Restricted
- Inner shock boundary
- Qualified plus shock PPE
- Documented work plan
Escort vs shock PPE
PPE and Glove Classes
- PPE Category 1
- 4 cal/cm2 minimum rating
- PPE Category 2
- 8 cal/cm2 minimum rating
- PPE Category 3
- 25 cal/cm2 minimum rating
- PPE Category 4
- 40 cal/cm2 minimum rating
- Category limits exceeded
- Incident energy analysis required
- Glove Class 00
- 500 V ac maximumASTM D120
- Glove Class 0
- 1,000 V ac maximum
- Glove Class 2
- 17,000 V ac maximum
- Glove Class 4
- 36,000 V ac maximum
- Glove retest
- Every 6 monthsOSHA 1910.137
- Sleeve and blanket retest
- Every 12 months
- Leather protectors
- Mechanical shield, not insulation
LOTO and ESWC
- OSHA 1910.147
- Machine servicing energy control
- OSHA 1910.333
- Electrical safety-related work practices
- OSHA 1910.269
- Utility generation, transmission, distribution
- NFPA 70E Article 120
- Electrically safe work condition
- Visual verification
- See the open gap
- Stored energy release
- Springs and capacitors
- Live-dead-live
- Prove tester before and after
- Temporary protective grounds
- Applied after voltage verified
- Equipotential zone
- Ground both work-zone ends
- Energized work permit
- Justifies infeasible de-energization
Meter Safety Ratings
- CAT II
- Receptacle-connected single-phase loadsIEC 61010
- CAT III
- Building distribution, three-phase equipment
- CAT IV
- Service entrance, outdoor conductors
- Higher category
- Higher transient withstand
- Voltage alone
- Never proves meter suitability
- Meter fuses
- High-interrupt rated only
- Non-contact tester
- Never proves absence
- Known live source
- Needed to prove tester
Ohm's Law and Power
- V = I x R
- Ohm's law
- P = V x I
- Real power, watts
- P = I^2 x R
- Heating in loose joints
- P = V^2 / R
- Resistive load power
- Series circuit
- Resistances add, current equal
- Parallel circuit
- Below smallest branch resistance
- 1 ohm
- 1,000,000 microhms
- 1 megohm
- 1,000,000 ohms
- Contact resistance units
- Microhms
- Winding resistance units
- Milliohms
- Insulation resistance units
- Megohms or gigohms
Three-Phase Relationships
- Wye line voltage
- sqrt(3) x phase voltage
- Wye line current
- Equals phase current
- Delta line voltage
- Equals phase voltage
- Delta line current
- sqrt(3) x phase current
- 480 V wye
- 277 V to neutral
- Apparent power S
- sqrt(3) x VLL x IL
- Real power P
- S x power factor
- Power factor
- Watts over volt-amperes
- Voltage unbalance
- Max deviation over average
- Delta ground reference
- Needs grounding transformer
ANSI Device Numbers
- 27
- UndervoltageIEEE C37.2
- 46
- Negative sequence, phase balance
- 49
- Thermal overload
- 50
- Instantaneous overcurrent
- 51
- Time overcurrent
- 52
- AC circuit breaker
- 59
- Overvoltage
- 67
- Directional overcurrent
- 86
- Lockout auxiliary relay
- 87
- Differential
- Suffix N or G
- Ground element
- Suffix V
- Voltage-restrained element
Drawings and Curves
- One-line
- Power path, sources, ratings
- Three-line
- Each phase and secondary
- DC schematic
- Trip and close logic
- Connection diagram
- Terminal-by-terminal wiring
- TCC curve
- Operating time versus current
- Pickup
- Minimum operating current
- Time dial
- Shifts the 51 curve
- Coordination
- Downstream device clears first
- Short-circuit study
- Available fault current source
Level 2 Domain Weights
Safety 15, Theory 25, Parts 55, Systems 5
ATS vs MTS
ANSI/NETA ATS
- Before initial energization
- New installations
- Acceptance criteria
ANSI/NETA MTS
- In-service equipment
- Maintenance intervals
- Trend against baseline
New install vs upkeep
IR Test Voltage Picker
- Manufacturer data exists→Manufacturer value(Tables are fallback)
- 600 V switchgear bus→1,000 V dc(100 Mohm)
- 5 kV class apparatus→2,500 V dc(1,500 Mohm)
- 15 kV class apparatus→2,500 V dc(5,000 Mohm)
- 480 V dry transformer→1,000 V dc(500 Mohm)
- 4,160 V liquid transformer→2,500 V dc(1,000 Mohm)
- 480 V motor stator→500 V dc(Table 100.11)
- 13.8 kV stator winding→5,000-10,000 V dc(Table 100.11)
- Reading below minimum→Investigate(Do not hipot)
IR Test Voltages
- 250 V class
- 500 V dc25 Mohm
- 600 V class
- 1,000 V dc100 Mohm
- 5,000 V class
- 2,500 V dc1,500 Mohm
- 15,000 V class
- 2,500 V dc5,000 Mohm
- Table 100.1 role
- Used absent manufacturer data
- Select voltage by
- Equipment rating, not supply
- Below the minimum
- Investigate before energizing
- Guard terminal
- Diverts surface leakage current
- Temperature rule
- Halves per 10 C rise
CT Open, PT Short
CT open kills; PT short kills
Insulation Resistance vs Hipot
Insulation resistance
- Lower dc voltage
- Nondestructive
- Megohm reading
Hipot
- High applied stress
- Pass or fail
- Can break insulation
Measure vs stress
Which Test For What
- Suspect wet stator→Polarization index(10 over 1)
- Ten minutes unavailable→DAR(60 over 30)
- Bolted joint suspect→Micro-ohmmeter(Four-wire Kelvin)
- Tap changer suspect→TTR on all taps(0.5 percent)
- Shorted transformer turns→Excitation current test
- Service-aged MV cable→VLF withstand(Not dc hipot)
- Rank cable replacement→Tan delta(Diagnostic)
- Lost vacuum suspected→Vacuum bottle integrity(Megger cannot see)
- CT accuracy in doubt→Saturation test(Knee point)
- Breaker did not trip→Primary injection(Whole loop)
- Isolated ground rod→Fall-of-potential(Disconnect electrode)
- Multi-grounded system→Clamp-on tester(Parallel path needed)
- Surface contamination suspected→Guarded IR reading
PI, DAR and IEEE 43
- PI
- 10-minute over 1-minute
- DAR
- 60-second over 30-second
- PI minimum
- 2.0 for Class BIEEE 43
- PI near 1.0
- Moisture or contamination
- PI not required
- IR above 5,000 Mohm
- Ratios need no correction
- Same temperature both readings
- Form-wound after 1970
- 100 Mohm minimum
- Older and field windings
- kV + 1 Mohm
- Random-wound stators
- 5 Mohm minimum
- IEEE 43 base
- Corrects to 40 C
- NETA conversion base
- Corrects to 20 C
- Step-voltage test
- Disproportionate drop reveals aging
PI and DAR Times
PI ten over one; DAR sixty over thirty
DLRO vs Megohmmeter
DLRO
- Microhm range
- Four-wire Kelvin
- Conducting path
Megohmmeter
- Megohm range
- High dc voltage
- Insulating path
Through vs across
Transformer Testing
- TTR tolerance
- Within 0.5 percentANSI/NETA
- Test every tap
- Defects hide on unused
- Turns ratio a
- V1/V2 = I2/I1
- Impedance transforms
- By the ratio squared
- Subtractive polarity
- Reads less than applied
- Additive polarity
- Reads more than applied
- Additive permitted
- 200 kVA and below
- Excitation current pattern
- Center leg reads lower
- Liquid-filled, 0-600 V
- 1,000 V dc, 100 MohmTable 100.5
- Dry-type, 0-600 V
- 1,000 V dc, 500 Mohm
- Liquid-filled, 601-5,000 V
- 2,500 V dc, 1,000 Mohm
- Winding resistance
- Finds loose or open
PI vs DAR
PI
- 10 min / 1 min
- IEEE 43 minimum 2.0
- Full charging curve
DAR
- 60 s / 30 s
- Quick screening ratio
- No IEEE minimum
Long vs short ratio
Cable Testing
- VLF frequency
- About 0.1 Hz
- Why VLF works
- Charging current drops sharply
- DC hipot on XLPE
- Injects trapped space charge
- DC still acceptable on
- PILC laminated dielectrics
- Tan delta
- Loss over charging current
- Tip-up
- Loss rises with voltage
- Withstand test
- Go or no-go
- Diagnostic test
- Grades and trends condition
- Shield continuity
- Over 10 ohms per 1,000 ft
- Post-hipot grounding
- Drain trapped charge first
Bonding vs Grounding
Bonding
- Joins metal parts
- Carries fault current
- Operates the breaker
Grounding
- Reference to earth
- Lightning and static
- Poor fault path
Clears faults vs references
Breaker Testing
- MCCB
- Sealed, fixed instantaneous trip
- ICCB
- Drawout, short-time capability
- LVPCB
- Maintainable, short-time withstand rating
- Thermal-magnetic trip
- Fixed curve, ambient sensitive
- Electronic trip
- Adjustable LSIG functions
- LSIG
- Long, short, instantaneous, ground
- Contact resistance current
- 100 A dc minimumIEEE C37.09
- Pole deviation limit
- 50 percent above lowest
- Primary injection
- Proves the whole loop
- Secondary injection
- Proves trip unit only
- Vacuum bottle integrity
- Overpotential across open gap
- Vacuum test hazard
- X-rays at high voltage
Primary vs Secondary Injection
Primary
- Whole current loop
- Finds bad CTs
- Commissioning test
Secondary
- Trip unit only
- Proves settings
- Misses sensors
Loop vs logic
Instrument Transformers
- Open CT secondary
- Lethal voltage, core saturates
- Before lifting CT lead
- Install the shorting screw
- Short PT secondary
- Damaging fault current
- Back-feed a PT
- Full primary on terminals
- 600:5 CT
- 120:1 ratio
- Polarity marks
- H1 in, X1 out
- Reversed CT polarity
- Differential trips on load
- C400 class
- 400 V at 100 AIEEE C57.13
- C-class error limit
- 10 percent ratio error
- Saturation test
- Finds the knee point
- Burden
- Total secondary circuit load
Withstand vs Diagnostic
Withstand
- Go or no-go
- VLF or hipot
- May fault it
Diagnostic
- Condition number
- Tan delta, partial discharge
- Trendable
Can energize vs remaining life
Grounding and Batteries
- Bonding
- Low-impedance fault return path
- Grounding
- Voltage reference to earth
- Earth as fault path
- Poor, will not clear
- Grounded conductor
- Neutral, carries load current
- Equipment grounding conductor
- Carries fault current only
- Fall-of-potential
- Three-point, 62 percent rule
- Clamp-on ground test
- Needs parallel return path
- Flooded cell
- Specific gravity, temperature corrected
- VRLA cell
- No hydrometer, ohmic trending
- IEEE 450
- Vented lead-acid maintenance
- IEEE 1188
- VRLA battery maintenance
- Capacity proof
- Discharge test only
CT vs PT Secondary
CT secondary
- Never open it
- Short before lifting
- Behaves as current source
PT secondary
- Never short it
- Never back-feed it
- Fused, voltage source
Open kills vs short kills
Test Order Rule
Components first, system function last
Restore and Report
- All component tests pass→System function test
- Relay element picks up→Verify breaker trips
- Before any adjustment→Record as-found
- After the work→Record as-left
- Grounds still applied→Remove conductor end first
- Ready to energize→Confirm settings match study
Commissioning and Records
- System function test
- After all component tests
- As-found data
- Recorded before any adjustment
- As-left data
- Baseline for next interval
- ATS functional test
- Simulate normal source loss
- NFPA 110 monthly
- 30 minutes under load
- Monthly load target
- 30 percent nameplate kW
- Annual supplemental test
- 50 percent then 75 percent
- Level 1 triennial
- 4 hours or class duration
- GFP performance test
- Required when first installedNEC 230.95
- Troubleshooting
- Find cause, not symptom
Common Traps
Boundary vs arc flash
Shock boundaries from table ≠ Arc flash is calculated
Category vs severity
Category is PPE rating ≠ Not a hazard score
De-energized vs safe
De-energized only means opened ≠ Safe adds test and ground
Wrong OSHA rule
1910.147 covers machines ≠ 1910.333 covers electrical work
Prefix mistakes
Contact resistance in microhms ≠ Insulation in megohms
Wrong correction base
IEEE 43 uses 40 C ≠ NETA table uses 20 C
Resistance vs withstand
Megohmmeter measures resistance ≠ Hipot applies dielectric stress
Wrong injection test
Secondary proves trip unit ≠ Primary proves whole loop
Only one tap tested
TTR needs every tap ≠ Unused taps hide defects
Vacuum vs insulation test
Megger misses lost vacuum ≠ Overpotential across open gap
Neutral vs ground
Neutral carries load current ≠ EGC carries fault current
Last Minute
- 1.Pass is 410 scaled, 200-500
- 2.100 items, 2 hours, closed-book
- 3.Component Testing is 55 percent
- 4.Safety 15, Theory 25, Systems 5
- 5.600 V class: 1,000 V dc
- 6.5 kV class: 2,500 V dc
- 7.PI = 10 min / 1 min
- 8.DAR = 60 s / 30 s
- 9.Minimum PI is 2.0
- 10.TTR within 0.5 percent, every tap
- 11.Contact resistance at 100 A
- 12.Never open a CT secondary
- 13.Never back-feed a PT
- 14.Ground end first, conductor last
- 15.Arc flash boundary: 1.2 cal/cm2
- 16.PPE cal: 4, 8, 25, 40
- 17.Restricted at 480 V: 1 foot
- 18.Record as-found before adjusting
- 19.Function test after component tests
- 20.Practice exam: $100, one hour
Explore More NETA ETT Certifications
Continue into nearby exams from the same family. Each card keeps practice questions, study guides, flashcards, videos, and articles in one place.
More From This Family
Videos and articles for deeper review.