Cheat sheet

NETA ETT Level 2 Cheat Sheet

Quick Facts

Exam
NETA ETT Level 2
Credential
Certified Assistant Technician
Items
100 multiple-choice
Time
2 hours
Pass
410 scaled (200-500)
Format
Closed-book, onsite proctored
Delivery
Pearson VUE
Scheduling
Set testing periods; schedule early
Practice exam
$100, one hour, 60-day review
Eligibility
2 years, NAC employed
Training
40 safety, 160 electrical hours
Supervision
Under Level 3 or 4

Ground Lead Order

Ground end first, remove it last

Apply: ground then conductorRemove: conductor then groundBoth ends: equipotential zoneVerify absence first

Level 2 vs Level 3

Level 2

  • Limited testing work
  • Direct supervision required
  • 15/25/55/5 weights

Level 3

  • Supervises Levels 1-2
  • Performs power switching
  • 13/23/47/17 weights

Assist vs supervise

Shock Boundary Picker

  1. 208 V panel, fixed parts3 ft 6 in limited
  2. 480 V, qualified entry1 ft 0 in restricted
  3. 13.8 kV gear, fixed parts5 ft 0 in limited
  4. 13.8 kV qualified entry2 ft 2 in restricted
  5. 25 kV gear, fixed parts6 ft 0 in limited
  6. Overhead movable conductor10 ft 0 in limited
  7. Unqualified person presentQualified escort required
  8. Need arc flash boundaryCalculate it(Not a voltage table)

Approach Boundaries

Limited approach
Unqualified needs qualified escort
Restricted approach
Qualified plus shock PPE
Arc flash boundary
1.2 cal/cm2 incident energy
Prohibited boundary
Deleted in 2015 editionNFPA 70E
50-150 V fixed
3 ft 6 in limited
151-750 V fixed
3 ft 6 in limited
151-750 V restricted
1 ft 0 in
751 V-15 kV fixed
5 ft 0 in limited
751 V-15 kV restricted
2 ft 2 in
15.1-36 kV restricted
2 ft 7 in
Movable conductor
10 ft through 72.5 kV
Boundary table
NFPA 70E 130.4(E)(a)

PPE Cal Ladder

Four, eight, twenty-five, forty

Cat 1: 4 cal/cm2Cat 2: 8 cal/cm2Cat 3: 25 cal/cm2Cat 4: 40 cal/cm2

Limited vs Restricted Boundary

Limited

  • Outer shock boundary
  • Unqualified needs escort
  • Fixed by voltage

Restricted

  • Inner shock boundary
  • Qualified plus shock PPE
  • Documented work plan

Escort vs shock PPE

PPE and Glove Classes

PPE Category 1
4 cal/cm2 minimum rating
PPE Category 2
8 cal/cm2 minimum rating
PPE Category 3
25 cal/cm2 minimum rating
PPE Category 4
40 cal/cm2 minimum rating
Category limits exceeded
Incident energy analysis required
Glove Class 00
500 V ac maximumASTM D120
Glove Class 0
1,000 V ac maximum
Glove Class 2
17,000 V ac maximum
Glove Class 4
36,000 V ac maximum
Glove retest
Every 6 monthsOSHA 1910.137
Sleeve and blanket retest
Every 12 months
Leather protectors
Mechanical shield, not insulation

LOTO and ESWC

OSHA 1910.147
Machine servicing energy control
OSHA 1910.333
Electrical safety-related work practices
OSHA 1910.269
Utility generation, transmission, distribution
NFPA 70E Article 120
Electrically safe work condition
Visual verification
See the open gap
Stored energy release
Springs and capacitors
Live-dead-live
Prove tester before and after
Temporary protective grounds
Applied after voltage verified
Equipotential zone
Ground both work-zone ends
Energized work permit
Justifies infeasible de-energization

Meter Safety Ratings

CAT II
Receptacle-connected single-phase loadsIEC 61010
CAT III
Building distribution, three-phase equipment
CAT IV
Service entrance, outdoor conductors
Higher category
Higher transient withstand
Voltage alone
Never proves meter suitability
Meter fuses
High-interrupt rated only
Non-contact tester
Never proves absence
Known live source
Needed to prove tester

Ohm's Law and Power

V = I x R
Ohm's law
P = V x I
Real power, watts
P = I^2 x R
Heating in loose joints
P = V^2 / R
Resistive load power
Series circuit
Resistances add, current equal
Parallel circuit
Below smallest branch resistance
1 ohm
1,000,000 microhms
1 megohm
1,000,000 ohms
Contact resistance units
Microhms
Winding resistance units
Milliohms
Insulation resistance units
Megohms or gigohms

Three-Phase Relationships

Wye line voltage
sqrt(3) x phase voltage
Wye line current
Equals phase current
Delta line voltage
Equals phase voltage
Delta line current
sqrt(3) x phase current
480 V wye
277 V to neutral
Apparent power S
sqrt(3) x VLL x IL
Real power P
S x power factor
Power factor
Watts over volt-amperes
Voltage unbalance
Max deviation over average
Delta ground reference
Needs grounding transformer

ANSI Device Numbers

27
UndervoltageIEEE C37.2
46
Negative sequence, phase balance
49
Thermal overload
50
Instantaneous overcurrent
51
Time overcurrent
52
AC circuit breaker
59
Overvoltage
67
Directional overcurrent
86
Lockout auxiliary relay
87
Differential
Suffix N or G
Ground element
Suffix V
Voltage-restrained element

Drawings and Curves

One-line
Power path, sources, ratings
Three-line
Each phase and secondary
DC schematic
Trip and close logic
Connection diagram
Terminal-by-terminal wiring
TCC curve
Operating time versus current
Pickup
Minimum operating current
Time dial
Shifts the 51 curve
Coordination
Downstream device clears first
Short-circuit study
Available fault current source

Level 2 Domain Weights

Safety 15, Theory 25, Parts 55, Systems 5

Safety: 15%Theory: 25%Component: 55%Systems: 5%

ATS vs MTS

ANSI/NETA ATS

  • Before initial energization
  • New installations
  • Acceptance criteria

ANSI/NETA MTS

  • In-service equipment
  • Maintenance intervals
  • Trend against baseline

New install vs upkeep

IR Test Voltage Picker

  1. Manufacturer data existsManufacturer value(Tables are fallback)
  2. 600 V switchgear bus1,000 V dc(100 Mohm)
  3. 5 kV class apparatus2,500 V dc(1,500 Mohm)
  4. 15 kV class apparatus2,500 V dc(5,000 Mohm)
  5. 480 V dry transformer1,000 V dc(500 Mohm)
  6. 4,160 V liquid transformer2,500 V dc(1,000 Mohm)
  7. 480 V motor stator500 V dc(Table 100.11)
  8. 13.8 kV stator winding5,000-10,000 V dc(Table 100.11)
  9. Reading below minimumInvestigate(Do not hipot)

IR Test Voltages

250 V class
500 V dc25 Mohm
600 V class
1,000 V dc100 Mohm
5,000 V class
2,500 V dc1,500 Mohm
15,000 V class
2,500 V dc5,000 Mohm
Table 100.1 role
Used absent manufacturer data
Select voltage by
Equipment rating, not supply
Below the minimum
Investigate before energizing
Guard terminal
Diverts surface leakage current
Temperature rule
Halves per 10 C rise

CT Open, PT Short

CT open kills; PT short kills

CT: short the secondaryPT: fuse the secondaryPT: never back-feedBoth mistakes are lethal

Insulation Resistance vs Hipot

Insulation resistance

  • Lower dc voltage
  • Nondestructive
  • Megohm reading

Hipot

  • High applied stress
  • Pass or fail
  • Can break insulation

Measure vs stress

Which Test For What

  1. Suspect wet statorPolarization index(10 over 1)
  2. Ten minutes unavailableDAR(60 over 30)
  3. Bolted joint suspectMicro-ohmmeter(Four-wire Kelvin)
  4. Tap changer suspectTTR on all taps(0.5 percent)
  5. Shorted transformer turnsExcitation current test
  6. Service-aged MV cableVLF withstand(Not dc hipot)
  7. Rank cable replacementTan delta(Diagnostic)
  8. Lost vacuum suspectedVacuum bottle integrity(Megger cannot see)
  9. CT accuracy in doubtSaturation test(Knee point)
  10. Breaker did not tripPrimary injection(Whole loop)
  11. Isolated ground rodFall-of-potential(Disconnect electrode)
  12. Multi-grounded systemClamp-on tester(Parallel path needed)
  13. Surface contamination suspectedGuarded IR reading

PI, DAR and IEEE 43

PI
10-minute over 1-minute
DAR
60-second over 30-second
PI minimum
2.0 for Class BIEEE 43
PI near 1.0
Moisture or contamination
PI not required
IR above 5,000 Mohm
Ratios need no correction
Same temperature both readings
Form-wound after 1970
100 Mohm minimum
Older and field windings
kV + 1 Mohm
Random-wound stators
5 Mohm minimum
IEEE 43 base
Corrects to 40 C
NETA conversion base
Corrects to 20 C
Step-voltage test
Disproportionate drop reveals aging

PI and DAR Times

PI ten over one; DAR sixty over thirty

PI: 10 min / 1 minDAR: 60 s / 30 sMinimum PI: 2.0No temperature correction

DLRO vs Megohmmeter

DLRO

  • Microhm range
  • Four-wire Kelvin
  • Conducting path

Megohmmeter

  • Megohm range
  • High dc voltage
  • Insulating path

Through vs across

Transformer Testing

TTR tolerance
Within 0.5 percentANSI/NETA
Test every tap
Defects hide on unused
Turns ratio a
V1/V2 = I2/I1
Impedance transforms
By the ratio squared
Subtractive polarity
Reads less than applied
Additive polarity
Reads more than applied
Additive permitted
200 kVA and below
Excitation current pattern
Center leg reads lower
Liquid-filled, 0-600 V
1,000 V dc, 100 MohmTable 100.5
Dry-type, 0-600 V
1,000 V dc, 500 Mohm
Liquid-filled, 601-5,000 V
2,500 V dc, 1,000 Mohm
Winding resistance
Finds loose or open

PI vs DAR

PI

  • 10 min / 1 min
  • IEEE 43 minimum 2.0
  • Full charging curve

DAR

  • 60 s / 30 s
  • Quick screening ratio
  • No IEEE minimum

Long vs short ratio

Cable Testing

VLF frequency
About 0.1 Hz
Why VLF works
Charging current drops sharply
DC hipot on XLPE
Injects trapped space charge
DC still acceptable on
PILC laminated dielectrics
Tan delta
Loss over charging current
Tip-up
Loss rises with voltage
Withstand test
Go or no-go
Diagnostic test
Grades and trends condition
Shield continuity
Over 10 ohms per 1,000 ft
Post-hipot grounding
Drain trapped charge first

Bonding vs Grounding

Bonding

  • Joins metal parts
  • Carries fault current
  • Operates the breaker

Grounding

  • Reference to earth
  • Lightning and static
  • Poor fault path

Clears faults vs references

Breaker Testing

MCCB
Sealed, fixed instantaneous trip
ICCB
Drawout, short-time capability
LVPCB
Maintainable, short-time withstand rating
Thermal-magnetic trip
Fixed curve, ambient sensitive
Electronic trip
Adjustable LSIG functions
LSIG
Long, short, instantaneous, ground
Contact resistance current
100 A dc minimumIEEE C37.09
Pole deviation limit
50 percent above lowest
Primary injection
Proves the whole loop
Secondary injection
Proves trip unit only
Vacuum bottle integrity
Overpotential across open gap
Vacuum test hazard
X-rays at high voltage

Primary vs Secondary Injection

Primary

  • Whole current loop
  • Finds bad CTs
  • Commissioning test

Secondary

  • Trip unit only
  • Proves settings
  • Misses sensors

Loop vs logic

Instrument Transformers

Open CT secondary
Lethal voltage, core saturates
Before lifting CT lead
Install the shorting screw
Short PT secondary
Damaging fault current
Back-feed a PT
Full primary on terminals
600:5 CT
120:1 ratio
Polarity marks
H1 in, X1 out
Reversed CT polarity
Differential trips on load
C400 class
400 V at 100 AIEEE C57.13
C-class error limit
10 percent ratio error
Saturation test
Finds the knee point
Burden
Total secondary circuit load

Withstand vs Diagnostic

Withstand

  • Go or no-go
  • VLF or hipot
  • May fault it

Diagnostic

  • Condition number
  • Tan delta, partial discharge
  • Trendable

Can energize vs remaining life

Grounding and Batteries

Bonding
Low-impedance fault return path
Grounding
Voltage reference to earth
Earth as fault path
Poor, will not clear
Grounded conductor
Neutral, carries load current
Equipment grounding conductor
Carries fault current only
Fall-of-potential
Three-point, 62 percent rule
Clamp-on ground test
Needs parallel return path
Flooded cell
Specific gravity, temperature corrected
VRLA cell
No hydrometer, ohmic trending
IEEE 450
Vented lead-acid maintenance
IEEE 1188
VRLA battery maintenance
Capacity proof
Discharge test only

CT vs PT Secondary

CT secondary

  • Never open it
  • Short before lifting
  • Behaves as current source

PT secondary

  • Never short it
  • Never back-feed it
  • Fused, voltage source

Open kills vs short kills

Test Order Rule

Components first, system function last

As-found before adjustingAs-left after workFunction proves interaction

Restore and Report

  1. All component tests passSystem function test
  2. Relay element picks upVerify breaker trips
  3. Before any adjustmentRecord as-found
  4. After the workRecord as-left
  5. Grounds still appliedRemove conductor end first
  6. Ready to energizeConfirm settings match study

Commissioning and Records

System function test
After all component tests
As-found data
Recorded before any adjustment
As-left data
Baseline for next interval
ATS functional test
Simulate normal source loss
NFPA 110 monthly
30 minutes under load
Monthly load target
30 percent nameplate kW
Annual supplemental test
50 percent then 75 percent
Level 1 triennial
4 hours or class duration
GFP performance test
Required when first installedNEC 230.95
Troubleshooting
Find cause, not symptom

Common Traps

Boundary vs arc flash

Shock boundaries from table Arc flash is calculated

Category vs severity

Category is PPE rating Not a hazard score

De-energized vs safe

De-energized only means opened Safe adds test and ground

Wrong OSHA rule

1910.147 covers machines 1910.333 covers electrical work

Prefix mistakes

Contact resistance in microhms Insulation in megohms

Wrong correction base

IEEE 43 uses 40 C NETA table uses 20 C

Resistance vs withstand

Megohmmeter measures resistance Hipot applies dielectric stress

Wrong injection test

Secondary proves trip unit Primary proves whole loop

Only one tap tested

TTR needs every tap Unused taps hide defects

Vacuum vs insulation test

Megger misses lost vacuum Overpotential across open gap

Neutral vs ground

Neutral carries load current EGC carries fault current

Last Minute

  1. 1.Pass is 410 scaled, 200-500
  2. 2.100 items, 2 hours, closed-book
  3. 3.Component Testing is 55 percent
  4. 4.Safety 15, Theory 25, Systems 5
  5. 5.600 V class: 1,000 V dc
  6. 6.5 kV class: 2,500 V dc
  7. 7.PI = 10 min / 1 min
  8. 8.DAR = 60 s / 30 s
  9. 9.Minimum PI is 2.0
  10. 10.TTR within 0.5 percent, every tap
  11. 11.Contact resistance at 100 A
  12. 12.Never open a CT secondary
  13. 13.Never back-feed a PT
  14. 14.Ground end first, conductor last
  15. 15.Arc flash boundary: 1.2 cal/cm2
  16. 16.PPE cal: 4, 8, 25, 40
  17. 17.Restricted at 480 V: 1 foot
  18. 18.Record as-found before adjusting
  19. 19.Function test after component tests
  20. 20.Practice exam: $100, one hour
Same family resources

Explore More NETA ETT Certifications

Continue into nearby exams from the same family. Each card keeps practice questions, study guides, flashcards, videos, and articles in one place.