4.2 Overcurrent Protection & Surge Protection (Articles 240 and 242)
Key Takeaways
Under NEC 240.4(B), the next higher standard OCPD rating is permitted only up to 800 amperes; above 800 A, 240.4(C) requires conductor ampacity at least equal to the OCPD rating.
NEC 240.4(D) limits 14, 12, and 10 AWG copper to 15-, 20-, and 30-ampere overcurrent protection unless 240.4(E) or (G) applies.
A 25-foot feeder tap needs an ampacity of at least one-third of the feeder OCPD rating and must end in a single breaker or set of fuses (NEC 240.21(B)(2)).
Overcurrent devices must be readily accessible, with the handle grip no more than 6 feet 7 inches above the floor (NEC 240.24(A)).
Type 1 surge-protective devices may connect on the line or load side of the service disconnect; Type 2 devices connect on the load side (Article 242).
Overcurrent Protection & Surge Protection (Articles 240 and 242)
Article 240 decides how big an overcurrent device may be, where it goes, and when a conductor may run unprotected for a short distance as a tap. Article 242 covers surge-protective devices (SPDs). Tap rules and the small-conductor limits are favorite calculation questions, and 240.4 is one of the most-cited sections in the code.
1. Protecting Conductors (240.4)
The basic rule: conductors must be protected at their ampacity (Article 310). Then come the modifiers:
| Subsection | Rule |
|---|---|
| 240.4(A) Power loss hazard | Where opening the circuit creates a greater hazard (for example, a fire pump or material-handling magnet), overload protection is not required, but short-circuit protection is |
| 240.4(B) 800 A or less | If the ampacity doesn't match a standard rating, the next higher standard rating is allowed. The device must be 800 A or less, and the conductors may not be part of a branch circuit supplying more than one receptacle for cord-and-plug-connected portable loads |
| 240.4(C) Over 800 A | The conductor ampacity must be equal to or greater than the OCPD rating. No rounding up |
| 240.4(D) Small conductors | Maximum OCPD, regardless of table ampacity, unless 240.4(E) or (G) applies: 14 Cu 15 A, 12 Cu 20 A, 10 Cu 30 A, 12 Al/CCA 15 A, 10 Al/CCA 25 A, 16 Cu 10 A, 18 Cu 7 A |
| 240.4(E) Taps | Tap conductors protected per 210.19 (cooking), 240.5 (cords), 240.21, 368.17 (busway), 430.53, and others |
| 240.4(G) Specific applications | Table 240.4(G) sends conductors for A/C (440), motors (430), welders (630), fire alarm (760), Class 1 circuits (724), capacitors (460), and others to their own articles |
Worked check: Four 3/0 copper THWN conductors in a raceway have an ampacity of 200 A at 75°C.
- A 200-A breaker matches exactly.
- If adjustment reduced the ampacity to 176 A, 240.4(B) would allow the next standard size up, 200 A.
- At 900 A of conductor ampacity, 240.4(C) would forbid a 1000-A device.
2. Standard Ratings and Device Rules (240.6–240.8, 240.15)
- Standard ratings (240.6(A)) include 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250, 300, 350, 400, 450, 500, 600, 700, 800, 1000, 1200, 1600, 2000, 2500, 3000, 4000, 5000, and 6000 A. There are additional fuse ratings below 15 A.
- Adjustable-trip breakers (240.6(B), (C)): The rating is the maximum possible setting. The lower setting counts only if access to the adjustment is restricted (a sealed cover, locked room, or password).
- Parallel devices (240.8): Fuses or breakers may not be paralleled unless they are factory-assembled and listed as a unit.
- Ungrounded conductors (240.15): Each ungrounded conductor gets an OCPD. Individual single-pole breakers with identified handle ties may protect each ungrounded conductor of a multiwire branch circuit serving only line-to-neutral loads, or of a 240-V single-phase circuit.
3. Location in the Circuit: The Tap Rules (240.21)
The OCPD normally goes where the conductor receives its supply. Feeder taps (240.21(B)) are the main exceptions:
| Tap | Conditions |
|---|---|
| 10-ft tap (240.21(B)(1)) | Tap ampacity at least the calculated load and at least the rating of the device it terminates in. For field taps that leave the enclosure, the ampacity must be at least 1/10 of the feeder OCPD rating. Enclosed in a raceway when not in the same enclosure, and terminating in a single breaker or set of fuses |
| 25-ft tap (240.21(B)(2)) | Tap ampacity at least 1/3 of the feeder OCPD rating. Terminates in a single breaker or set of fuses that limits the load to the tap ampacity. Protected from physical damage |
| Transformer feeder tap (240.21(B)(3)) | Primary plus secondary total no more than 25 ft. Primary ampacity at least 1/3 of the feeder OCPD rating, with secondary conductors matching on the transformer's voltage ratio |
| Outside taps (240.21(B)(5)) | Outdoors, of unlimited length, if protected from physical damage and terminating in a single OCPD at or in the building disconnect |
Transformer secondary conductors (240.21(C)) have parallel rules:
- a 10-ft rule;
- two 25-ft rules, one general and one for industrial installations;
- an outside rule; and
- the case where a 2-wire single-phase or delta-delta 3-wire secondary is protected by the primary OCPD.
Worked example: 25-ft tap. A 400-A feeder is tapped to supply a 150-A panel 20 feet away.
- Minimum tap ampacity = 400 ÷ 3 = 133.3 A.
- The tap must also carry the 150-A device it terminates in. 1/0 copper at 75°C has an ampacity of 150 A, so it meets both requirements.
- The tap ends in a 150-A main breaker.
4. Location in the Premises (240.24)
- (A) Accessibility: OCPDs must be readily accessible. The center of the operating-handle grip at its highest position may be no more than 6 feet 7 inches (2.0 m) above the floor or working platform. Exceptions include busway plug-ins, supplementary devices, and devices next to the motors or appliances they serve.
- (B) Occupancy: Each occupant must have ready access to the OCPDs protecting that occupant's conductors. Service and feeder devices may be excepted under building-management supervision.
- (C) Physical damage: Not where exposed to damage.
- (D) Ignitible material: Not near easily ignitible material, such as in clothes closets.
- (E) Bathrooms: Not in bathrooms of dwelling units, dormitory units, or hotel and motel guest rooms and suites.
- (F) Stairways: Not over the steps of a stairway.
5. Interrupting Ratings, Fault Current, and Arc Energy
- 110.9: Every device intended to interrupt fault current must have an interrupting rating at least equal to the available fault current at its line terminals.
- 110.10: Equipment short-circuit current ratings must also be adequate.
- Unmarked ratings: A breaker without a marked interrupting rating is rated 5,000 A (240.83(C)). Class H cartridge fuses are rated 10,000 A. Current-limiting fuses such as Class J and RK1 are commonly 200,000 A.
- 110.24: In other than dwelling units, service equipment must be field-marked with the available fault current and the date it was calculated. The marking is updated when conditions change.
- Arc energy reduction (240.87 and 240.67): Breakers and fuses rated 1200 A or more need an arc energy reduction method, such as zone-selective interlocking, a differential relay, an energy-reducing maintenance switch, or an active arc-flash mitigation system.
- Plug fuses (240.50–240.54): Allowed only where the circuit does not exceed 125 V between conductors, or 150 V to ground on a grounded neutral system. Edison-base fuses are for replacement only. New work uses Type S fuses with nontamperable adapters, in size classes 0–15, 16–20, and 21–30 A.
6. Surge-Protective Devices (Article 242, Part II)
Article 242 combined the former surge arrester and SPD articles in the 2020 edition. For systems of 1000 V or less:
| SPD type | Where it connects |
|---|---|
| Type 1 | Permanently connected. May go on the line side or load side of the service disconnect |
| Type 2 | Permanently connected on the load side of the service disconnect OCPD, including in the service equipment or at a downstream panel |
| Type 3 | Point-of-utilization devices, such as plug-in units and SPD receptacles, on the load side of branch-circuit OCPD. Where the manufacturer's instructions require it, they must be at least 30 ft of conductor from the service disconnect |
| Type 4 | Component SPDs used inside equipment |
- Listing and ratings: SPDs must be listed. Their voltage rating may not be less than the system's maximum continuous phase-to-ground voltage.
- Ungrounded systems: SPDs are not used on ungrounded or impedance-grounded systems unless listed for them.
- Conductors: Keep SPD conductors as short as practicable, avoiding unnecessary bends, because lead length adds let-through voltage.
- Where SPDs are required: 230.67 (dwelling-type services), 215.18 (feeders to those occupancies), 695.15 (fire pump controllers), 700.8 (emergency system switchboards and panelboards), and 708.20 (critical operations power).
Note
Nebraska's statute exempts 230.67(A), the dwelling service SPD, by applying the 2017 text. It does not name 215.18. On the PSI exam, use the code book.
7. Common Exam Traps
- Rounding up over 800 A: The next-size-up rule of 240.4(B) stops at 800 A.
- 25-ft tap ratio: The 25-ft tap needs 1/3 of the feeder OCPD rating. The 1/10 ratio belongs to the field-installed 10-ft tap.
- Handle height: The limit is 6 feet 7 inches to the center of the handle grip at its highest position.
- Small conductors: 12 AWG copper is limited to a 20-A OCPD even though Table 310.16 shows 25 A at 75°C.
A 600-ampere feeder is tapped with conductors 22 feet long that end in a single main breaker in a panelboard. Under NEC 240.21(B)(2), what is the minimum ampacity of the tap conductors?
300 amperes, one-half of the feeder protection
200 amperes, one-third of the feeder protection
600 amperes, equal to the feeder protection
60 amperes, one-tenth of the feeder protection
A parallel conductor set has an adjusted ampacity of 950 amperes. Under NEC 240.4, what is the largest standard fixed-rating overcurrent device that may protect it?
1000 amperes, the next higher standard rating
1200 amperes, because large feeders may be protected at 125 percent
Any rating, because 240.4(B) permits rounding up
800 amperes
Under NEC 240.24(A), how high may the center of the grip of a circuit breaker's operating handle be, in its highest position, above the floor or working platform?
6 feet
5 feet 6 inches
6 feet 7 inches
7 feet