8.2 Gas Pipe Sizing and Sizing Table Methodology
Key Takeaways
Convert appliance Btu/h input to cubic feet per hour by dividing by the delivered gas heating value; use a stated assumption only for an example.
The longest length (developed length) method sizes all sections of the system based on the distance from the point of delivery to the farthest appliance outlet.
At equal pipe and pressure conditions, higher specific gravity lowers volumetric CFH capacity; energy capacities also depend on heating value.
Sizing tables must match the system’s gas type, inlet pressure, pressure drop and piping material.
Principles of Gas Pipe Sizing
Sizing residential fuel gas piping systems is one of the most critical steps in ensuring the safe and efficient operation of gas-burning appliances. Under IRC Section G2413.1, a gas piping system must be sized so that it can supply the maximum connected load of all appliances operating simultaneously, while maintaining the required pressure at the inlet of each appliance. If the piping is undersized, appliances will experience pressure drops that lead to incomplete combustion, burner instability, flame rollout, or safety shutdowns.
Key Sizing Parameters
To size a gas piping system using the IRC tables, the inspector must identify four key parameters:
- Gas Type and Heating Value: The heating value of natural gas is typically assumed to be 1,000 Btu per cubic foot (Btu/ft³), while propane is typically assumed to be 2,500 Btu/ft³.
- Inlet Pressure: Low-pressure systems operate at 0.5 psi (14 inches w.c.) or less. Systems operating at higher pressures (such as 2 psi) use different tables.
- Pressure Drop: The allowable friction loss across the piping system. For low-pressure systems, a pressure drop of 0.5 inches w.c. is standard, though drops of 1.0 inch w.c. or 3.0 inches w.c. may be permitted depending on the appliance requirements.
- Piping Material: Separate tables exist for Schedule 40 metallic pipe, copper tubing, and CSST (sized by Equivalent Hydraulic Diameter or EHD).
Flow Rate Calculation (CFH)
Appliance input ratings are listed on their nameplates in Btu/h. To use the sizing tables, these values must be converted to Cubic Feet per Hour (CFH) using the formula:
CFH = Appliance Input Rating (Btu/h) / Gas Heating Value (Btu/ft³)
For example, if the supplier documents a heating value of 1,000 Btu/ft³, a 120,000 Btu/h furnace needs 120,000 / 1,000 = 120 CFH. Use the actual gas value for a real design.
Sizing Methodologies (G2413.4)
The IRC recognizes two primary sizing methods for residential gas piping:
- Longest Length Method (G2413.4.1):
- This is the most common and conservative method.
- Step 1: Measure the actual developed length from the point of delivery (e.g., gas meter or second-stage regulator) to the most remote (farthest) appliance outlet in the system.
- Step 2: This single longest length becomes the 'length row' for the entire system lookup. Every section of pipe in the system is sized using this same length row, regardless of how close it is to the meter.
- Step 3: For each section of pipe, sum the load (CFH) of all appliances served by that section. Scan across the chosen length row in the table to find the smallest pipe size with a capacity equal to or greater than the section's load.
- Branch Length Method (G2413.4.2):
- This method allows for smaller branch lines.
- The main run from the point of delivery to the most remote outlet is sized using the longest length.
- Each branch line is sized using the developed length from the point of delivery to the outlet of that specific branch, along with the load of that branch.
Worked Example: Longest Length Method
Let's walk through a sizing scenario for a natural gas system operating below 2 psi, with a 0.5-inch w.c. pressure drop, using Schedule 40 black steel pipe.
- Appliances:
- Furnace: 100,000 Btu/h (100 CFH)
- Water Heater: 40,000 Btu/h (40 CFH)
- Range: 60,000 Btu/h (60 CFH)
- Piping Layout:
- Meter (Point of Delivery) to Tee A (Section 1): 15 feet. (Serves all: 200 CFH)
- Tee A to Range (Section 2 - Branch): 25 feet. (Serves range only: 60 CFH)
- Tee A to Tee B (Section 3 - Trunk): 15 feet. (Serves furnace and water heater: 140 CFH)
- Tee B to Furnace (Section 4 - Branch): 10 feet. (Serves furnace only: 100 CFH)
- Tee B to Water Heater (Section 5 - Branch): 5 feet. (Serves water heater only: 40 CFH)
Step 1: Determine the Developed Length to the Most Remote Outlet We calculate the developed length of all paths from the meter:
- Path to Range: 15 + 25 = 40 feet
- Path to Furnace: 15 + 15 + 10 = 40 feet
- Path to Water Heater: 15 + 15 + 5 = 35 feet
The longest developed length is 40 feet. Therefore, we use the 40-foot length row for all sizing lookups under the longest length method.
Step 2: Table Lookup using Table G2413.4(1) Excerpt (Natural Gas, 0.60 SG, 0.5 in. w.c. drop) Here is the verified 40-foot capacity row for the stated gas/table conditions:
- ½-inch pipe: 81 CFH
- ¾-inch pipe: 170 CFH
- 1-inch pipe: 320 CFH
- 1¼-inch pipe: 657 CFH
Step 3: Size Each Section
- Section 1 (Meter to Tee A): Load is 200 CFH. Looking at the 40-foot row, a ¾-inch pipe has a capacity of 170 CFH, below the 200 CFH load. Use a 1-inch pipe (capacity 320 CFH).
- Section 2 (Tee A to Range): Load is 60 CFH. A ½-inch pipe (capacity 81 CFH) is sufficient.
- Section 3 (Tee A to Tee B): Load is 140 CFH. A ¾-inch pipe (capacity 170 CFH) is sufficient.
- Section 4 (Tee B to Furnace): Load is 100 CFH. A ½-inch pipe (81 CFH) is below the 100 CFH load. Use a ¾-inch pipe (capacity 170 CFH).
- Section 5 (Tee B to Water Heater): Load is 40 CFH. A ½-inch pipe (capacity 81 CFH) is sufficient.
Sizing Tables Comparison and Selection
When preparing for the M1 exam, selecting the correct table is half the battle. If a candidate uses the wrong table, they can choose the wrong pipe size even with correct arithmetic. Read every table heading before a lookup: gas type, specific gravity, inlet pressure, allowed pressure drop, material and nominal pipe size all matter. For this worked example, Table G2413.4(1) corresponds to the 2024 IFGC Table 402.4(2) schedule-40 metallic-pipe natural-gas table. Do not transfer this 40-foot row to another gas or pressure condition.
Under the longest length method (G2413.4.1) for sizing gas piping, how is the length row for looking up capacities in the tables determined?
By summing the lengths of all piping segments in the entire building
By using the length of each individual segment to size that specific segment
By measuring the developed length from the point of delivery to the most remote outlet in the system
By taking the average length of all piping branches from the meter
For the same pipe size and length, inlet pressure and allowed pressure drop, how does greater gas specific gravity affect volumetric flow capacity in cubic feet per hour?
Specific gravity has no effect on flow capacity, which depends solely on pressure
A higher specific gravity (such as propane at 1.50) results in lower flow capacity than a lower specific gravity (such as natural gas at 0.60)
A higher specific gravity increases the flow velocity, resulting in higher flow capacity
A lower specific gravity results in a higher pressure drop, reducing flow capacity
Using the verified 40-foot row of Table G2413.4(1), what Schedule 40 pipe size is needed for 100 CFH if 1/2-inch carries 81 CFH and 3/4-inch carries 170 CFH?
1/2-inch
1-inch
1 1/4-inch
3/4-inch
Sections you finish are checked off in the contents.