11.1 Mechanical (IMC) and Fuel Gas (IFGC) Plan Review

Key Takeaways

  • Table 403.3.1.1 dictates mechanical ventilation rates based on occupancy and square footage.
  • Type I hoods are required for grease/smoke-producing commercial cooking, whereas Type II hoods handle steam/odor.
  • Combustion air requires 50 cubic feet per 1,000 Btu/h for fuel gas appliances, otherwise outdoor air openings must be provided.
  • Category I vent systems are non-condensing, negative-pressure, while Category IV are condensing, positive-pressure.
  • Fuel gas piping must undergo pressure testing at a minimum of 1.5 times working pressure, and not less than 3 psig.
Last updated: July 2026

11.1 Mechanical (IMC) and Fuel Gas (IFGC) Plan Review

Key Concept: Mechanical and fuel gas plan review ensures buildings maintain safe occupant environments, protect fire-resistance-rated assemblies, and provide adequate combustion air to prevent carbon monoxide poisoning and backdrafting.

The plan review process for mechanical systems relies on the International Mechanical Code (IMC) and the International Fuel Gas Code (IFGC). These codes interface with the International Building Code (IBC) to regulate mechanical ventilation, kitchen exhaust systems, duct design, smoke dampers, and fuel gas piping systems.

Mechanical Ventilation: Natural vs. Mechanical

Plan reviewers must confirm that all occupied spaces are provided with ventilation in accordance with IMC Chapter 4.

Natural Ventilation

Under IMC Section 402, natural ventilation requires that the openable area to the outdoors be at least 4 percent of the floor area being ventilated. The outdoor air must come directly from openings to the outdoors, which can include windows, doors, louvers, or skylights.

Mechanical Ventilation

For mechanical ventilation systems, the plan reviewer must audit design calculations against IMC Table 403.3.1.1. The design must account for both the occupancy-based ventilation rate (Rp in CFM per person) and the area-based ventilation rate (Ra in CFM per square foot). The total outdoor airflow rate (Vot) is calculated as: Vot = (Rp * Pz) + (Ra * Az), where Pz is the zone population and Az is the zone floor area.

Outdoor air intakes must be strategically located to prevent the recirculation of contaminants. Under IMC Section 401.4, outdoor air intakes must be positioned at least 10 feet away from hazardous or noxious sources such as plumbing vents, chimneys, mechanical exhaust outlets, streets, alleys, and loading docks. In addition, intakes must be placed at least 3 feet below or 10 feet away from any plumbing vent that terminates above the intake level.

Commercial Kitchen Exhaust Systems

Commercial kitchen hoods represent a high-risk mechanical system due to grease accumulation and fire hazards. Under IMC Chapter 5, the plan reviewer must identify the type of hood required based on the cooking appliances:

  • Type I Hoods: Required where cooking appliances produce grease or smoke. This includes deep fat fryers, griddles, charbroilers, and ovens cooking meats. Type I systems require commercial grease filters, liquid-tight welded duct construction (minimum 16-gauge steel or 18-gauge stainless steel), structural shafts for vertical duct enclosures, and automatic fire suppression systems complying with UL 300.
  • Type II Hoods: Required where cooking appliances produce steam, heat, vapor, or odors without producing grease. Examples include dishwashers, steam tables, and light-duty ovens. They do not require fire suppression or heavy-gauge welded ducts.

Makeup Air Integration

A critical plan review item is makeup air. Under IMC Section 508, makeup air systems must be interlocked with the exhaust system to run simultaneously. The makeup air flow rate must be approximately equal to the exhaust air flow rate (within 10 percent). Neglecting makeup air creates negative pressure, causing backdrafting of fuel-fired appliances and preventing egress doors from opening properly.

Duct Construction, Dampers, and Detectors

Duct systems (IMC Chapter 6) must be reviewed for materials, pressure classification, and support spacing. Duct smoke detectors are a vital life-safety integration:

  • Equipment Shutdown: IMC Section 606 requires duct smoke detectors in the supply air systems of mechanical units with a design capacity exceeding 2,000 CFM. If a return air system has a design capacity exceeding 15,000 CFM and serves more than one story, detectors must be installed at each story's connection to the return air riser. Upon detection of smoke, the controls must automatically shut down the associated HVAC equipment.
  • Fire and Smoke Dampers: Required where ducts penetrate fire-resistance-rated assemblies (such as fire walls, fire barriers, and shaft enclosures). The plan reviewer must verify that dampers are rated in accordance with UL 555 (fire dampers) and UL 555S (smoke dampers), and that access panels are provided for inspection and testing.

Fuel Gas Piping and Pressure Testing

The International Fuel Gas Code (IFGC) governs the design and installation of fuel gas piping systems. Plan reviewers must verify piping materials, sizing calculations, and pressure-testing protocols:

  • Materials: Acceptable piping includes schedule 40 black steel, copper tubing (if the gas is non-corrosive), and Corrugated Stainless Steel Tubing (CSST). CSST systems require electrical bonding to the electrical service grounding electrode system to prevent damage from lightning strikes. Plastic piping is permitted only for underground installations outdoors.
  • Sizing: Piping sizing must be verified using the longest length method or branch length method, ensuring that pressure drop is kept within allowable limits (typically 0.5 inches water column for low-pressure systems) to deliver adequate fuel to appliances.
  • Pressure Testing: Under IFGC Section 406, fuel gas piping must be pressure-tested before being placed into service. The minimum test pressure must be not less than 1.5 times the maximum working pressure, but under no circumstances less than 3 psig. The test duration must be at least 10 minutes for residential systems and longer for commercial installations.

Combustion Air Requirements

Fuel gas appliances require oxygen to support complete combustion. IFGC Chapter 3 establishes rules to prevent hazardous incomplete combustion and carbon monoxide production:

  • Confined vs. Unconfined Space: A space is considered unconfined (roomy enough to provide combustion air from normal infiltration) if its volume is at least 50 cubic feet per 1,000 Btu/h of the aggregate input rating of all appliances. If the volume is less than this threshold, it is confined, and additional combustion air must be brought into the space.
  • Indoor Combustion Air: If drawing from adjacent indoor spaces, two permanent openings are required, each having a free area of not less than 1 square inch per 1,000 Btu/h.
  • Outdoor Combustion Air: If drawing from outdoors, the plan reviewer must verify the sizing of openings. The two-permanent-openings method requires one high opening and one low opening. If venting directly to the outdoors, each opening must have a free area of 1 square inch per 4,000 Btu/h. The one-permanent-opening method requires a single opening with a free area of 1 square inch per 3,000 Btu/h, located within the upper 12 inches of the enclosure.

Venting Systems and Appliance Categories

Venting systems must safely exhaust combustion products to the outdoors. Under IFGC Chapter 5, gas appliances are classified into four categories based on vent operating temperature and pressure:

  • Category I: Operates with a non-positive vent static pressure and a vent gas temperature high enough to avoid condensation in the vent. These appliances rely on natural draft and use Type B or Type L double-wall vents.
  • Category II: Operates with a non-positive vent static pressure and a vent gas temperature low enough to cause condensation.
  • Category III: Operates with a positive vent static pressure and a vent gas temperature high enough to avoid condensation. These require airtight metallic vents.
  • Category IV: Operates with a positive vent static pressure and a vent gas temperature low enough to cause condensation. These are high-efficiency condensing appliances and typically vent through PVC or CPVC piping.

Mechanical Equipment Access and Clearances

Plan reviewers must ensure that all mechanical equipment is designed with safe and code-compliant access for maintenance and repair. Under IMC Section 306, appliances must be accessible without requiring the removal of permanent construction. Equipment installed in attics must have an access opening of not less than 22 inches by 30 inches, and a continuous passageway at least 22 inches wide and 30 inches high. Appliances installed on roofs must have a level working platform (not less than 30 inches by 30 inches) and must be located no closer than 15 feet from the edge of the roof, unless a standard 42-inch guardrail is installed to prevent falls.

Test Your Knowledge

Under the International Mechanical Code (IMC), what is the minimum distance required between an outdoor air intake and a hazardous or noxious contaminant source such as a plumbing vent terminating above the intake?

A
B
C
D
Test Your Knowledge

An appliance operates with a positive vent static pressure and a vent gas temperature low enough to cause condensation. According to the International Fuel Gas Code (IFGC), which category of appliance venting system does this represent?

A
B
C
D