7.4 Cross-Connection Control, Hazard Assessment & Backflow Preventers (RPZ, DCVA, PVB, Air Gap)

Key Takeaways

  • A cross-connection is any actual or potential link between a potable water piping system and any source containing unapproved, non-potable, or contaminated substances.
  • Backflow occurs via backsiphonage (negative or sub-atmospheric pressure in the supply) or backpressure (downstream pressure exceeds supply pressure).
  • Hazards are classified as High Hazard (health contamination from toxic chemicals or biological pathogens) or Low Hazard (aesthetic pollution from non-toxic substances).
  • The Reduced Pressure Zone (RPZ) assembly protects against both backpressure and backsiphonage under high and low hazard conditions by maintaining an atmospheric relief zone between two check valves.
  • Under CDPHE Regulation 11.39, public water systems must maintain an active Backflow Prevention and Cross-Connection Control (BPCCC) program with an annual test compliance rate of at least 90%.
Last updated: August 2026

Cross-Connection Control, Hazard Assessment & Backflow Preventers (RPZ, DCVA, PVB, Air Gap)

The municipal water distribution system is designed to convey pure, potable water under continuous pressure to consumer properties. However, physical connections between the drinking water grid and non-potable piping systems can allow hazardous liquids, chemicals, or pathogens to flow backward into the public mains during hydraulic disturbances. Preventing such occurrences through rigorous Cross-Connection Control is a primary regulatory responsibility of certified distribution operators.


1. Regulatory Authority and Fundamental Definitions

Under CDPHE Regulation 11, Section 11.39 (Backflow Prevention and Cross-Connection Control Rule), every public water system in Colorado must establish and enforce a comprehensive Backflow Prevention and Cross-Connection Control (BPCCC) program.

+-------------------------------------------------------------------------+
|                       CORE BACKFLOW DEFINITIONS                         |
+-------------------------------------------------------------------------+
| Cross-Connection: Any actual or potential physical connection or        |
| structural arrangement between a public potable water system and any    |
| source of non-potable water, industrial liquid, gas, or sewage.         |
|                                                                         |
| Backflow: The undesirable reversal of flow of water, mixtures, or      |
| foreign substances into the distribution pipes of a potable supply.     |
|                                                                         |
| Containment Protection: Installing an approved backflow prevention      |
| assembly on the customer's service lateral immediately downstream of    |
| the water meter, isolating the entire facility from the public main.    |
|                                                                         |
| Isolation Protection (Point-of-Use): Installing a backflow device at an |
| individual fixture or piece of equipment inside the customer's building.|
+-------------------------------------------------------------------------+

2. Hydraulic Mechanics of Backflow: Backsiphonage vs. Backpressure

Backflow occurs strictly as a result of hydraulic pressure differentials through one of two distinct physical mechanisms:

Backsiphonage

Backsiphonage is backflow caused by negative or sub-atmospheric pressure ($< 0\text{ psig}$ or $< 14.7\text{ psia}$) within the potable supply main. It operates on the same physical principle as drawing liquid through a drinking straw.

  • Common Causes: Severe distribution main breaks, nearby high-volume firefighting operations, undersized booster pumps pulling negative suction, or line draining during scheduled repairs.

Backpressure

Backpressure occurs when the pressure in a downstream customer piping system exceeds the operating pressure in the incoming potable supply main, forcing non-potable fluids backward into the public grid.

  • Common Causes: High-pressure steam boilers, unvented thermal expansion, customer booster pumps, elevated auxiliary tanks, or private irrigation systems tied into secondary agricultural ditches.
BACKSIPHONAGE:  [ Public Main: -5 psi (Vacuum) ] <===== [ Customer Vat / Sink: 0 psi (Atmospheric) ]
                                (Sub-atmospheric pressure pulls liquid into main)

BACKPRESSURE:   [ Public Main: 50 psi ] <============= [ Customer Boiler / Pump: 85 psi ]
                                (Higher downstream pressure pushes fluid into main)

3. Hazard Assessment: High Hazard (Contamination) vs. Low Hazard (Pollution)

Selecting the correct backflow prevention assembly requires evaluating the degree of public health hazard:

  1. High Hazard (Contamination): An impairment of drinking water quality by sewage, industrial chemicals, toxic heavy metals, or pathogenic biological agents that creates an actual threat to public health through poisoning, acute illness, or death. Examples: Chemical manufacturing facilities, mortuaries, hospitals, electroplating plants, commercial car washes, agricultural chemical injection systems, wastewater treatment facilities, and dedicated auxiliary water supplies.
  2. Low Hazard (Pollution): An aesthetic impairment of drinking water that affects taste, odor, color, or turbidity but does not create an adverse threat to human health. Examples: Food processing steam tables, non-toxic commercial beverage carbonators, aesthetic fountains, and closed-loop hydronic heating systems without chemical additives.
Loading diagram...
Backflow Assembly Hierarchy, Mechanical Action & Hazard Suitability

4. Mechanical Backflow Prevention Assemblies

Backflow prevention assemblies are precision mechanical devices approved by the University of Southern California Foundation for Cross-Connection Control and Hydraulic Research (USC-FCCCHR) or the American Society of Sanitary Engineering (ASSE).

1. Air Gap (AG)

An Air Gap is a non-mechanical, unobstructed vertical physical separation through free atmosphere between the lowest opening of a supply pipe and the flood-level rim of a receiving vessel.

  • Dimension Standard: The vertical air gap distance must be at least twice the effective internal diameter ($2 \times D$) of the supply pipe, and in no case less than 1.0 inch (25 mm).
  • Application: Unconditionally approved for High and Low Hazards, and protects against both Backpressure and Backsiphonage (the most absolute protection available).

2. Reduced Pressure Zone Assembly (RPZ / RP - AWWA C511)

  • Construction: Comprises two independently acting, spring-loaded check valves separated by a hydraulically balanced, intermediate differential pressure relief valve, flanked by two resilient-seated shutoff valves and four test cocks.
  • Operating Principle: The central relief valve is designed to open and vent to atmosphere whenever the pressure in the intermediate zone approaches within 2.0 psi of the supply pressure. If either check valve leaks or backsiphonage occurs, the relief valve discharges water to atmosphere, maintaining the zone at lower pressure than the supply.
  • Application: Approved for High and Low Hazards, protecting against both Backpressure and Backsiphonage.
  • Installation Requirements: Must be installed in a location not subject to flooding (never in an unvented subterranean pit), minimum 12 inches above floor/ground, with an air gap funnel beneath the relief discharge port.

3. Double Check Valve Assembly (DCVA - AWWA C510)

  • Construction: Consists of two independently acting, spring-loaded internal check valves, two resilient-seated shutoff valves, and four test cocks.
  • Application: Approved for LOW HAZARD (Pollution) ONLY, protecting against both Backpressure and Backsiphonage. It cannot be used on high-hazard toxic connections because any particle lodging across both check seats would allow toxic backflow without an atmospheric discharge warning.

4. Pressure Vacuum Breaker (PVB - AWWA C512)

  • Construction: Contains an independently operating, spring-loaded internal check valve and an independently operating, spring-loaded air inlet valve that admits atmospheric air when pressure drops.
  • Application: Approved for High and Low Hazards, but for BACKSIPHONAGE ONLY. Cannot protect against backpressure.
  • Installation Standards: Can operate under continuous supply pressure. Must be installed at least 12 inches above the highest downstream piping, sprinkler head, or outlet.

Backflow Prevention Selection Matrix

Assembly / DeviceHealth Hazard SuitabilityBackpressure Protection?Backsiphonage Protection?Continuous Pressure Allowed?Field Testable?
Air Gap (AG)High & Low HazardYesYesYes (Physical gap)N/A (Visual inspection)
Reduced Pressure Zone (RPZ)High & Low HazardYesYesYesYes (4 test cocks)
Double Check Valve (DCVA)Low Hazard ONLYYesYesYesYes (4 test cocks)
Pressure Vacuum Breaker (PVB)High & Low HazardNOYesYesYes (2 test cocks)
Atmospheric Vacuum Breaker (AVB)High & Low HazardNOYesNO ($< 12\text{ hrs/day}$)NO (No test cocks)

5. CDPHE Regulation 11.39 BPCCC Program Requirements

Colorado public water systems must enforce stringent administrative and technical controls under Regulation 11.39:

  1. Annual Testing Mandate: All backflow prevention assemblies must be tested upon installation, after any repair or relocation, and at least annually (once every 12 months) by an ASSE- or ABPA-certified Cross-Connection Control Tester.
  2. Annual Compliance Tracking Ratio ($\ge 90%$): Public water systems must track all assemblies in their service area and submit an annual BPCCC compliance report to CDPHE demonstrating that at least 90% of all registered assemblies were successfully tested and operational within the calendar year.
  3. Certified Cross-Connection Control Technician: Surveys, hazard evaluations, and testing oversight must be coordinated by personnel holding certified CCWP Cross-Connection Control credentials.
  4. Containment Enforcement: If a commercial or industrial customer refuses to install or test a required containment assembly, the water purveyor is legally mandated under Regulation 11.39 to terminate water service to the property to protect the public distribution grid.

6. Step-by-Step Backflow Scenario Analysis

Worked Example 6.4.1: BPCCC Annual Compliance Calculation

A Colorado municipality has 1,450 registered commercial and industrial cross-connection containment assemblies within its distribution boundary. During the compliance year, the utility's certified cross-connection control database records 1,348 certified annual backflow test reports received and verified. Calculate the annual testing compliance percentage and determine if the utility satisfies CDPHE Regulation 11.39 requirements.

Step 1: Calculate the compliance testing percentage: Compliance Rate (%)=(Number of Assemblies Tested and VerifiedTotal Number of Registered Assemblies)×100%\text{Compliance Rate (\%)} = \left(\frac{\text{Number of Assemblies Tested and Verified}}{\text{Total Number of Registered Assemblies}}\right) \times 100\% Compliance Rate=(1,3481,450)×100%=92.97%\text{Compliance Rate} = \left(\frac{1,348}{1,450}\right) \times 100\% = 92.97\%

Step 2: Compare against Colorado regulatory standard: Regulatory Threshold=90.0%\text{Regulatory Threshold} = 90.0\% Assessment: 92.97%90.0%\text{Assessment: } 92.97\% \ge 90.0\%

Conclusion: The municipality achieved a 92.97% annual testing compliance rate, successfully meeting the CDPHE Regulation 11.39 annual BPCCC compliance standard.

Test Your Knowledge

Which backflow prevention assembly is approved to protect against BOTH backpressure and backsiphonage under HIGH HAZARD (health contamination) conditions?

A
B
C
D
Test Your Knowledge

What is the minimum physical vertical separation required for an approved Air Gap on a 2-inch internal diameter potable water supply pipe discharging into an open tank?

A
B
C
D
Test Your Knowledge

Under CDPHE Regulation 11.39, what minimum annual backflow assembly testing compliance rate must a public water system achieve and document to the State?

A
B
C
D