2.8 Pretreatment: Presedimentation, Aeration, Algae Control & Taste-and-Odor Management
Key Takeaways
- Presedimentation removes heavy sand and silt ahead of coagulation, protecting pumps and reducing coagulant demand during high-turbidity runoff events.
- Aeration adds oxygen and strips volatile compounds, so it removes carbon dioxide, hydrogen sulfide, methane, radon, and volatile organics and oxidizes iron and manganese.
- Potassium permanganate is fed at the intake or raw water line so oxidation is complete before filtration, and overdosing produces pink water and manganese greensand breakthrough.
- Powdered activated carbon is dosed as early as possible for contact time but must not be fed at the same point as an oxidant or free chlorine, because each destroys the benefit of the other.
- Geosmin and 2-methylisoborneol are detectable at nanograms per liter, are not health hazards, and are best removed by activated carbon or ozone rather than by chlorination.
Everything that happens before coagulation
Pretreatment is the set of unit processes applied to raw water before the main coagulation, flocculation, sedimentation, and filtration train. Its purpose is to reduce the load on the plant, remove constituents that the main train handles badly, and stabilize a variable source so process control downstream can be steady.
Presedimentation and roughing
Presedimentation is plain gravity settling of raw water, with no coagulant, in a basin or reservoir ahead of the plant. It is standard practice on rivers carrying heavy sand and silt, and its value in Colorado shows up during spring runoff and after wildfire when raw turbidity can jump from 5 NTU to several hundred in hours.
Benefits are concrete:
- Removes abrasive sand that would otherwise destroy pump impellers, chemical feed check valves, and meter internals.
- Cuts coagulant demand, because the coagulant no longer has to sweep out the fraction that settles on its own.
- Buffers turbidity spikes, giving the operator time to adjust dose.
- Provides equalization storage during intake interruptions.
Roughing filters — coarse gravel or crushed rock beds operated at low rates — do the same job where basin space is unavailable, and are common ahead of slow sand filters.
Screening ahead of everything removes trash, leaves, and aquatic organisms. Bar racks with 1 to 3 inch openings handle debris; traveling water screens with fine mesh remove leaves, fish, and mussels; microstrainers with 20 to 60 micron fabric remove algae.
Aeration
Aeration transfers gases in both directions across the air and water interface. It adds oxygen and strips volatile gases. That single sentence explains everything it can do:
| Aeration accomplishes | Mechanism |
|---|---|
| Oxidize dissolved iron and manganese | Adds O2 |
| Remove carbon dioxide (raises pH) | Strips CO2 |
| Remove hydrogen sulfide (rotten-egg odor) | Strips H2S |
| Remove methane and radon | Strips dissolved gas |
| Remove volatile organic compounds | Strips VOCs |
| Reduce some tastes and odors | Strips volatile compounds |
It cannot remove nonvolatile material: hardness, nitrate, arsenic, fluoride, and total dissolved solids pass straight through.
Three families of equipment appear on the exam:
- Waterfall or gravity aerators — cascade, tray (often with coke or ceramic media), and spray nozzles. Water is broken into thin films or droplets falling through air. Tray aerators are the classic groundwater iron and manganese unit.
- Diffused aerators — compressed air released through diffusers at the bottom of a contact basin. Effective and enclosed, so off-gas can be controlled, but energy intensive.
- Packed tower (air stripping) aerators — water distributed over high-surface-area packing with a countercurrent air stream. This is the workhorse for VOC and radon removal, and the air-to-water ratio is the main control variable.
Aeration side effects an operator must anticipate: stripping CO2 raises pH, which can shift the corrosion balance and change coagulation chemistry; adding oxygen makes the water more corrosive to iron pipe; open aerators are an entry point for airborne contamination, so they need screening and housekeeping; and in cold Colorado weather, exposed cascade aerators ice up.
Oxidation for iron, manganese, and taste and odor
Where aeration is too slow — manganese in particular oxidizes very slowly with oxygen alone below pH 9 — a chemical oxidant is fed at the intake or raw water line so reaction and precipitation are complete before the filters.
| Oxidant | Typical use | Cautions |
|---|---|---|
| Chlorine | Iron oxidation, disinfection credit, algae control | Reacts with TOC to form THMs and HAAs; destroys PAC capacity |
| Potassium permanganate (KMnO4) | Manganese and iron, taste and odor | Overdose gives pink water and manganese passing filters; feed point must allow full reaction |
| Chlorine dioxide | Manganese, taste and odor, low THM formation | Chlorite and chlorate byproducts are regulated |
| Ozone | Taste and odor, color, manganese, disinfection | Forms bromate where bromide is present; requires biologically active filtration downstream |
| Oxygen (aeration) | Iron; manganese only at high pH | Slow for manganese |
Potassium permanganate deserves particular attention because it is heavily tested. It is a purple crystalline solid mixed into solution and fed by metering pump. Correct dosing turns the raw water faintly pink, and the color must disappear before the water reaches the filters. Persistent pink water leaving a filter means the dose is too high — excess permanganate is passing through and will produce pink water complaints and, on manganese greensand, will bleed manganese. Underdosing leaves soluble manganese that oxidizes later in the distribution system and produces black water complaints. Manganese greensand filters are regenerated with permanganate, either continuously or intermittently.
Taste and odor
The two compounds responsible for most earthy and musty complaints are geosmin and 2-methylisoborneol (MIB), produced by cyanobacteria and actinomycetes. Human threshold detection is in the range of 5 to 10 nanograms per liter — parts per trillion — which is why customers can taste something no routine analysis will show. Neither compound is a health hazard, but complaints about them dominate customer contact during late-summer reservoir blooms.
Effective responses, roughly in order of practicality:
- Change the intake depth to draw below the bloom.
- Powdered activated carbon (PAC), dosed typically 5 to 30 mg/L.
- Ozone or chlorine dioxide oxidation.
- Granular activated carbon as a filter cap or post-filter adsorber for chronic problems.
- Reservoir management — copper sulfate algaecide (with care for aquatic life and for releasing cell contents), aeration or destratification, and nutrient control in the watershed.
Chlorine is the wrong tool. Chlorinating a bloom lyses algal cells, releasing intracellular geosmin, MIB, and potentially cyanotoxins, and simultaneously reacts with the organic load to raise THM and HAA formation. Prechlorination for taste and odor almost always makes complaints worse.
PAC feed point rules
PAC needs contact time to adsorb, so it is dosed as early as practical — at the intake, in the presedimentation basin, or at the rapid mix. Two constraints govern:
- Never feed PAC and an oxidant at the same point. Free chlorine, permanganate, or ozone will consume the carbon's adsorption capacity, and the carbon will consume the oxidant. Separate the feed points, or feed PAC first with the oxidant well downstream.
- PAC is removed with the floc, so it must be fed upstream of coagulation and settling. Dosing after sedimentation loads the filters with black carbon fines and risks carbon breakthrough into the clearwell.
Housekeeping matters: dry PAC is a combustible dust and a slip hazard when wet, and its handling area needs dust control, bonding and grounding on transfer equipment, and no ignition sources.
An operator feeds potassium permanganate at the raw water intake for manganese control and begins receiving customer complaints of pink water. What does this indicate?
Which raw water problem will aeration NOT correct?
Why must powdered activated carbon not be fed at the same point as free chlorine?