5.2 O. Reg. 211/01, O. Reg. 212/01 & TSSA Code Adoption Documents (CAD)
Key Takeaways
O. Reg. 212/01 is the Gaseous Fuels regulation and O. Reg. 211/01 is the Propane Storage and Handling regulation; each adopts national codes through its own Code Adoption Document under O. Reg. 223/01.
Gaseous Fuels CAD amendment FS-279-26 adopted CSA B149.1-25 with Ontario amendments effective June 1, 2026, replacing the 2021 adoption of B149.1-20.
Under O. Reg. 212/01 s. 8, a gas distributor has access at reasonable times and on reasonable notice to examine appliances and disconnect any that do not conform to the regulation.
Under O. Reg. 212/01 s. 12, apparent carbon monoxide poisoning, asphyxiation, explosion or fire caused by gas must be reported forthwith to a TSSA inspector.
The Gaseous Fuels CAD states that where it conflicts with an adopted code, the CAD prevails—so Ontario amendments override the national B149.1 text.
Ontario does not regulate natural gas and propane under one rule book. Each fuel has its own regulation under the TSS Act, and each regulation adopts national CSA codes through a Code Adoption Document (CAD). Mixing up the regulation numbers is one of the most common G.3 exam errors, so learn this pairing first.
1. The Regulatory Map
| Instrument | Covers | Codes it brings into force |
|---|---|---|
| O. Reg. 212/01 – Gaseous Fuels | Natural gas (and the other "gases" defined in its CAD) — appliances, piping, distributors, contractors | Gaseous Fuels CAD: CSA B149.1-25 with Ontario amendments, CSA B149.3-25 (field approval), B149.3 Annex J (mobile food service equipment), CSA B149.6-25 (biogas) and NFPA 160 (flame effects) — amendment FS-279-26, effective June 1, 2026 |
| O. Reg. 211/01 – Propane Storage and Handling | Propane storage, handling, filling, distribution, propane appliances and works | Propane CAD (adopts CSA B149.2, the propane storage and handling code, with Ontario amendments) |
| O. Reg. 215/01 – Fuel Industry Certificates | Who may do fuel work (G.1, G.2, G.3 and others) | — |
| O. Reg. 223/01 – Codes and Standards Adopted by Reference | The mechanism that lets a director adopt and amend codes through CADs | — |
FS-279-26 replaced the 2021 Gaseous Fuels CAD (which had adopted B149.1-20). From June 1, 2026, the B149.1 edition you use in Ontario—and bring to the exam—is B149.1-25 as amended by the CAD.
2. O. Reg. 212/01 (Gaseous Fuels): Sections a G.3 Must Know
| Section | Rule |
|---|---|
| s. 4 | Where approval is required, no one may sell, lease or install an appliance, equipment or thing unless it is approved (with listed exceptions such as Bunsen burners and manually operated industrial appliances of 20,000 Btu/h or less) |
| s. 5 | No one may handle gas without a licence for that purpose |
| s. 6 | No one may install, alter, purge, activate, repair, service or remove gas equipment without a certificate for that purpose; s. 6(3) allows an uncertified person to do the work in the presence of the certificate holder |
| s. 7 | Where premises are connected to gas for the first time, no appliance may be put into use until the distributor has examined the installation and is satisfied it complies |
| s. 8 | The distributor has access at all reasonable times, on reasonable notice, to examine appliances and disconnect any that do not conform, and to work on its meters and regulators |
| s. 11 | Employers must instruct employees to comply and take every reasonable precaution to ensure they do |
| s. 12 | If carbon monoxide poisoning, asphyxiation, explosion or fire appears to have occurred because of gas, a certificate holder, contractor or distributor must forthwith notify an inspector; the scene must not be disturbed except for public safety, saving life, relieving suffering, continuity of service or preserving property |
| s. 13–14 | Unacceptable conditions, with and without immediate hazard (see section 5.3) |
| s. 15 | Owners and users must keep appliances and works in safe operating condition |
| s. 16 | A distributor may not supply gas unless satisfied the installation complies and it has been inspected within the previous 10 years or under a quality-assurance inspection program |
| s. 17 | Owners of special (industrial, institutional, assembly) buildings must have maintenance procedures evaluated and the appliances inspected at least once every 10 years |
| s. 21 | No one may act as a contractor unless registered; registration expires one year after issue, a late renewal is treated as a new application, evidence of registration is displayed at the business, and address changes are reported within 30 days |
3. O. Reg. 211/01 (Propane Storage and Handling)
O. Reg. 211/01 mirrors much of the gaseous-fuels structure for propane: certificates and contractor registration, distributor access, occurrence reporting, and unacceptable conditions (ss. 19–20, with the same shut-off and notice steps as O. Reg. 212/01). It adds rules for cylinder handling facilities, filling plants, container refill centres, tank trucks and licensing.
Risk and Safety Management Plans (s. 3.1)
Retail outlets, filling plants, cardlock/keylock sites, private outlets and container refill centres must file a risk and safety management plan (RSMP) with the director. A Level 1 plan applies to smaller facilities—no more than 5,000 USWG total capacity (or 5,000 USWG fixed plus no more than 500 USWG portable storage); larger facilities file a Level 2 plan.
Safe handling of propane cylinders
- Filling limit: propane cylinders are filled by weight to a maximum filling density of 42% of their water capacity. Liquid propane expands roughly 1.5% for every 10°F rise, so the remaining vapour space (about 20% by volume) is the safety cushion.
- Requalification: Transport Canada (CSA B339) cylinders must not be refilled once their requalification date has passed; a new TC/DOT propane cylinder is due for requalification 10 years after its date of manufacture, and a registered facility re-stamps it.
- Location: CSA B149.2's location rules keep a cylinder's relief-valve discharge at least 3 ft (1 m) from any building opening and 10 ft (3 m) from any mechanical air intake, because propane vapour sinks and flows into openings.
- On construction projects O. Reg. 213/91 s. 122 requires welding and cutting cylinders to be protected from damage, never transported or stored lying horizontally, and to have their valves closed when not in use.
The filling-by-weight calculation:
Example: a cylinder stamped WC 47.6 lb and TW 17 lb holds at most of propane, so the scale should read about 37 lb when full.
4. How a Code Adoption Document Works
A CSA code is a private standard; it becomes enforceable in Ontario only when a CAD adopts it under O. Reg. 223/01. FS-279-26 says so in plain terms: the Director for O. Reg. 212/01, acting under s. 6(1) of O. Reg. 223/01, revoked and replaced the whole Gaseous Fuels CAD. The CAD then states that "in the event of conflict between a provision of this document and any code or standard referred to in this document, this document shall prevail."
Ontario amendments worth tabbing
| CAD item | Ontario rule |
|---|---|
| 4.1.5 | Where certified instructions and the code conflict, the more stringent prevails |
| 4.5.5 | An appliance exposed to fire, explosion, flood or other damage may not be sold, installed, re-activated or reconnected without AHJ approval or inspection and confirmation by a G.1 or G.2 |
| 6.13.2(a) | Drip or dirt pocket depth: at least 3 in. (75 mm) or the pipe's internal diameter, whichever is greater |
| 6.15.4 | Buried piping: at least 15 in. (400 mm) of cover, 24 in. (600 mm) under a commercial driveway or parking lot; Annex P for rocky ground |
| 6.18.2 | Manual shut-off valve location and tagging (within 50 ft of a residential appliance) |
| Table 6.3 note 2 | Wrapped or factory-coated piping (other than CSST and coated copper) is pressure tested at least 100 psig |
| 6.22.7–6.22.8 | Mandatory pressure test tag or sticker |
| 7.1.13 / Annex Q | Seasonal CO and safety checks on residential natural-draft boilers of 300,000 Btu/h or less |
| 8.17.3 / Annex R | Non-compliant B-vent installed outdoors |
Orders and guidance
A director's safety order under TSS Act s. 14 is mandatory. TSSA advisories, bulletins and guidelines explain how TSSA reads the code, but the binding text is the regulation, the CAD and the codes it adopts.
What is the legal relationship between CSA B149.1 and the TSSA Gaseous Fuels Code Adoption Document (CAD) in Ontario?
CSA B149.1 becomes provincial law automatically when CSA publishes it
The national B149.1 text overrides any conflicting Ontario CAD amendment
The CAD adopts B149.1 into O. Reg. 212/01, and where the CAD conflicts with the code, the CAD prevails
The CAD applies only to propane facilities, while B149.1 governs natural gas on its own authority
A technician must look up the unacceptable-condition procedure for a natural gas furnace. Which regulation contains it?
O. Reg. 212/01 (Gaseous Fuels)
O. Reg. 211/01 (Propane Storage and Handling)
O. Reg. 215/01 (Fuel Industry Certificates)
O. Reg. 223/01 (Codes and Standards Adopted by Reference)
Under O. Reg. 212/01, which statement correctly describes a gas distributor's powers over customer installations?
The distributor may only notify the municipal building department and has no power to interrupt the supply of gas
The distributor must repair, at its own cost, any customer appliance that fails inspection
The distributor must obtain a court order before entering a property to examine piping
It has access at reasonable times, on notice, to examine appliances and disconnect non-conforming ones