11.1 Gas Pipe & Tubing Sizing Fundamentals (Tables & Pressure Drop)

Key Takeaways

  • The CSA B149.1 Annex A and B tables are applied with the Longest Developed Length (LDL) method: measure the developed length from the meter or last-stage regulator outlet to the most remote appliance and size every segment from that length row.

  • Appliance input ratings in BTU/h\text{BTU/h} must be converted to volumetric fuel demand in cubic feet per hour (CFH=BTU/h÷Heating Value\text{CFH} = \text{BTU/h} \div \text{Heating Value}), applying nominal heating values of 1,000 BTU/cu ft1{,}000\text{ BTU/cu ft} for Natural Gas (SG≈0.60\text{SG} \approx 0.60) and 2,500 BTU/cu ft2{,}500\text{ BTU/cu ft} for Commercial Propane (SG≈1.52\text{SG} \approx 1.52).

  • CSA B149.1 Table 6.1 limits pressure drop to 0.5 in. w.c.0.5\text{ in. w.c.} where supply pressure is below 7 in. w.c.7\text{ in. w.c.} (Tables A.1 and A.8) and to 1 in. w.c.1\text{ in. w.c.} for supplies of 7 to 14 in. w.c.7\text{ to }14\text{ in. w.c.} (Tables A.2 and A.9 for natural gas; B.1 and B.6 for propane).

  • When executing the LDL method, every individual pipe segment—including main distribution trunks and all appliance branch takeoffs—must be sized using the row corresponding to the total system LDL (or the next higher table increment), never using a branch's individual developed length alone.

  • Although commercial propane vapor is heavier than air (SG≈1.52\text{SG} \approx 1.52 vs 0.600.60), its 2.5×2.5\times higher volumetric energy density (2,500 BTU/cu ft2{,}500\text{ BTU/cu ft} vs 1,000 BTU/cu ft1{,}000\text{ BTU/cu ft}) reduces required volumetric flow by 60%60\%, allowing smaller pipe and tubing diameters for identical appliance heat inputs.

Last updated: October 2026

Gas Pipe & Tubing Sizing Fundamentals (Tables & Pressure Drop)

In fuel gas distribution, correct pipe and tubing sizing is the engineering foundation of appliance performance and operational safety. An undersized piping system causes excessive friction loss, leading to severe pressure drop during peak firing conditions. Pressure starvation destabilizes appliance burner manifolds, produces unstable lifting flames, causes incomplete combustion and toxic carbon monoxide (COCO) generation, and triggers nuisance dropouts of low-pressure safety switches. Conversely, severely oversized piping introduces unnecessary material costs and creates excessively large internal fuel volumes that complicate pressure testing and purging procedures.

Under the Technical Standards and Safety Act, 2000, Ontario Regulation 212/01 (Gaseous Fuels), and the CSA B149.1 Natural Gas and Propane Installation Code, certified Gas Technician 3 (G.3) certificate holders must master the physical principles of gas flow, volumetric conversions, table navigation in Annex A and Annex B, and the Longest Developed Length (LDL) sizing methodology.


Principles of Fuel Gas Flow & Pressure Drop

Gas flowing through a closed conduit experiences continuous internal fluid resistance caused by fluid viscosity and friction against the pipe wall. The fundamental relationship governing low-pressure fuel gas flow (operating below 0.5 psig/14 in. w.c.0.5\text{ psig} / 14\text{ in. w.c.}) is expressed through empirical flow formulations such as Pole's Formula and the Weymouth Equation:

Q=C×ΔP×d5SG×LQ = C \times \sqrt{\frac{\Delta P \times d^5}{SG \times L}}

Where:

  • QQ = Volumetric flow rate in cubic feet per hour (CFH\text{CFH})
  • ΔP\Delta P = Allowable pressure drop across the pipe run (inches water column, in. w.c.\text{in. w.c.})
  • dd = Internal diameter of the pipe or tubing (inches)
  • SGSG = Specific gravity of the fuel gas relative to air (1.001.00)
  • LL = Developed length of the piping run (feet)
  • CC = Empirical friction and flow coefficient

Analyzing this fluid dynamic relationship reveals four core rules essential for gas technicians:

  1. Direct Impact of Pipe Diameter (d5d^5): Flow capacity is proportional to the fifth power of internal diameter. A minor increase in pipe size yields an exponential expansion in capacity. For example, moving from nominal 1/2-inch1/2\text{-inch} Schedule 40 pipe (d=0.622 ind = 0.622\text{ in}) to 3/4-inch3/4\text{-inch} pipe (d=0.824 ind = 0.824\text{ in}) more than doubles the flow capacity at identical length and pressure drop.
  2. Inverse Impact of Length (L\sqrt{L}): As developed length increases, friction accumulates. Doubling the length of a pipe reduces its delivery capacity by a factor of 2≈1.414\sqrt{2} \approx 1.414 (a 29.3%29.3\% flow reduction).
  3. Square-Root Impact of Allowable Drop (ΔP\sqrt{\Delta P}): Increasing allowable pressure drop increases capacity, but only by the square root of the drop ratio.
  4. Inverse Impact of Specific Gravity (SG\sqrt{SG}): Heavier gases encounter greater inertial resistance. A gas with a higher specific gravity experiences slower flow velocities under identical differential pressures.

Volumetric Flow Conversion: BTU/h\text{BTU/h} to CFH\text{CFH}

Appliance rating plates specify thermal input capacities in British Thermal Units per hour (BTU/h\text{BTU/h}) or Kilowatts (kW\text{kW}) (1 kW=3,412.14 BTU/h1\text{ kW} = 3{,}412.14\text{ BTU/h}). Pipe capacity tables, however, are commonly expressed as volume flow—Cubic Feet per Hour (CFH\text{CFH}) or Cubic Metres per Hour (m3/h\text{m}^3\text{/h}) (1 m3/h=35.315 CFH1\text{ m}^3\text{/h} = 35.315\text{ CFH})—so always check the units in the table heading.

To size any pipe run, technicians must convert thermal ratings to volumetric flow using the gross heating value of the fuel gas:

Volumetric Flow (CFH)=Appliance Input Rating (BTU/h)Gross Heating Value of Fuel (BTU/cu ft)\text{Volumetric Flow (CFH)} = \frac{\text{Appliance Input Rating (BTU/h)}}{\text{Gross Heating Value of Fuel (BTU/cu ft)}}

Natural Gas vs. Commercial Propane Energetics

Fuel ParameterNatural Gas (Utility Supply)Commercial Propane (HD-5)
Nominal Chemical CompositionMethane (CH4\text{CH}_4, 85% to 95%85\%\text{ to }95\%)Propane (C3H8\text{C}_3\text{H}_8, ≥90%\ge 90\%)
Gross Heating Value (Imperial)1,000 BTU/cu ft1{,}000\text{ BTU/cu ft} (nominal)2,500 BTU/cu ft2{,}500\text{ BTU/cu ft} (nominal)
Gross Heating Value (SI Metric)37.3 MJ/m337.3\text{ MJ/m}^393.1 MJ/m393.1\text{ MJ/m}^3
Specific Gravity (SGSG, Air = 1.001.00)0.600.60 (Nominal range 0.55 to 0.650.55\text{ to }0.65; Lighter)1.521.52 (Nominal range 1.50 to 1.551.50\text{ to }1.55; Heavier)
Standard Low-Pressure Delivery7.0 in. w.c.7.0\text{ in. w.c.} (1.75 kPa1.75\text{ kPa})11.0 in. w.c.11.0\text{ in. w.c.} (2.75 kPa2.75\text{ kPa})
Standard Manifold Pressure3.5 in. w.c.3.5\text{ in. w.c.} (0.87 kPa0.87\text{ kPa})10.0 in. w.c.10.0\text{ in. w.c.} (2.50 kPa2.50\text{ kPa})

Note

Use the heating value from the gas supplier when you have it. A nominal 1,000 BTU/cu ft1{,}000\text{ BTU/cu ft} (37.3 MJ/m337.3\text{ MJ/m}^3) is the customary value for natural gas sizing exercises, and Ontario pipeline gas is close to it.

Comparative Flow Calculation

Consider a high-efficiency condensing furnace with an input rating of 100,000 BTU/h100{,}000\text{ BTU/h}:

  • Operating on Natural Gas: CFHNG=100,000 BTU/h1,000 BTU/cu ft=100 CFH\text{CFH}_{\text{NG}} = \frac{100{,}000\text{ BTU/h}}{1{,}000\text{ BTU/cu ft}} = 100\text{ CFH}

  • Operating on Commercial Propane: CFHLP=100,000 BTU/h2,500 BTU/cu ft=40 CFH\text{CFH}_{\text{LP}} = \frac{100{,}000\text{ BTU/h}}{2{,}500\text{ BTU/cu ft}} = 40\text{ CFH}

Even though propane is more than twice as dense as natural gas (SG=1.52SG = 1.52 vs 0.600.60), its volumetric energy concentration is 2.5 times2.5\text{ times} greater. Consequently, an appliance requires 60%60\% less volume of propane to deliver the exact same thermal output. This critical distinction explains why propane piping and copper tubing lines are almost always smaller in diameter than natural gas piping serving equivalent loads.


Pressure Regimes & Allowable Pressure Drops

Piping sizing tables in CSA B149.1 Annex A (Natural Gas) and Annex B (Propane) are categorized by inlet operating pressure, allowable pressure drop (ΔP\Delta P), and piping material.

Low-Pressure Systems (up to 14 in. w.c.)

CSA B149.1 Clause 6.3.2 and Table 6.1 set the maximum pressure drop allowed between the meter (or last-stage regulator) and the appliance:

Piping system supply pressureMaximum allowable pressure dropNatural gas tables (Annex A)Propane tables (Annex B)
Less than 7 in. w.c. (1.75 kPa)0.5 in. w.c. (0.125 kPa)Tables A.1 and A.8—
7 in. w.c. up to 14 in. w.c. (1.75–3.5 kPa)1 in. w.c. (0.25 kPa)Tables A.2 and A.9Tables B.1 and B.6

Ontario residential natural gas is delivered at about 7 in. w.c., so Table 6.1 allows a 1 in. w.c. drop and the Table A.2 capacities. Sizing to a 0.5 in. w.c. drop (Table A.1) is more conservative and also complies—useful where an appliance needs a higher minimum inlet pressure or the supply sits at the low end of its range. Propane systems supplied at about 11 in. w.c. use the 1 in. w.c. tables in Annex B. The tables already include an allowance for a reasonable number of fittings.

Medium-Pressure Hybrid Systems (2 psig/14 kPa2\text{ psig} / 14\text{ kPa})

Modern large residential and commercial buildings frequently employ 2 psig2\text{ psig} (14 kPa14\text{ kPa}) natural gas distribution:

  • Gas is distributed through compact, small-diameter piping (often 3/8-inch3/8\text{-inch} or 1/2-inch1/2\text{-inch} CSST or copper tubing) from the meter to central manifolds.
  • Dedicated Line Pressure Regulators (LPRs) certified to CSA 6.22 / ANSI Z21.80 reduce the pressure from 2 psig2\text{ psig} down to appliance operating levels (7 in. w.c.7\text{ in. w.c.}) immediately adjacent to each appliance or appliance manifold.
  • Clause 6.3.4 sizes 2 psig systems from the minimum pressure available at the line pressure regulator, using the 2 psig tables in Annex A (Tables A.2, A.3, A.4, A.10 and A.11) or Annex B (Tables B.2 and B.7) for propane.

Practice Capacity Table (0.5 in. w.c. Drop)

The table below is an illustrative practice table: rounded capacities for Schedule 40 steel pipe carrying natural gas (SG=0.60SG = 0.60) at a 0.5 in. w.c.0.5\text{ in. w.c.} drop, following the pattern of published low-pressure capacity tables. Use it to practise the method. On the job and in the TSSA exam, read the actual CSA B149.1 Annex A table for your allowed pressure drop.

Total Developed Length (Feet)Nominal 1/2" Pipe (CFH)Nominal 3/4" Pipe (CFH)Nominal 1" Pipe (CFH)Nominal 1-1/4" Pipe (CFH)Nominal 1-1/2" Pipe (CFH)Nominal 2" Pipe (CFH)
101753606801,4002,1003,950
201202504659501,4602,750
30972003757701,1802,200
40821703206609901,900
50731512855808701,680
60661382605307901,520
70611252404907301,400
80571182204606901,300
90531102054306501,220
100501041954006201,160
12544931753605501,020
1504084160325500930

Important

When the measured developed length of a system falls between two table values (for example, 74 feet74\text{ feet}), do not interpolate—use the next longer length row (in this case, 80 feet80\text{ feet}). This conservative rule prevents undersizing.


The Longest Developed Length (LDL) Methodology

The Longest Developed Length (LDL) method is the standard way to use the Annex A and B tables for branched low-pressure systems. It is based on a foundational physical principle: the total friction drop across any path from the gas meter to an appliance must not exceed the allowable limit (0.5 in. w.c.0.5\text{ in. w.c.}).

If a technician were to size a short appliance branch (e.g., 15 feet15\text{ feet}) using the 15-foot15\text{-foot} table column while the main header runs 80 feet80\text{ feet}, the cumulative pressure drop across both segments would exceed the allowed drop. Sizing every segment from the total system LDL keeps the drop within the Table 6.1 limit under full load.

The Six-Step Sizing Protocol

  1. Establish Total System Load: Sum the maximum firing rates of all connected appliances in BTU/h\text{BTU/h} and convert each to volumetric flow (CFH\text{CFH}) by dividing by the fuel heating value.
  2. Measure Developed Lengths: Determine the linear length of pipe from the meter or regulator outlet to each individual appliance shutoff valve. Developed length includes actual pipe travel plus an allowance for fittings if using advanced equivalent length methods (under standard residential Annex A tables, fitting friction is incorporated into conservative table margins).
  3. Identify the Longest Developed Length (LDL): Find the single farthest appliance from the gas supply. Round this distance UP to the next higher row in the applicable sizing table. This row becomes the sole sizing reference for the entire piping network.
  4. Size Main Distribution Trunk Sections: Starting at the meter, size each main line segment based on the cumulative CFH demand of all downstream appliances, reading across the established LDL row.
  5. Size Intermediate Distribution Headers: At each tee or junction, recalculate the remaining downstream load and select the required pipe diameter from the LDL row.
  6. Size Individual Appliance Branch Lines: Size each branch takeoff based strictly on that individual appliance's CFH\text{CFH} demand, using the exact same system LDL row—regardless of how short that branch pipe actually is.

Worked Trade Sizing Example: Residential Installation

To master this procedure, work through a complete residential sizing problem using the practice table above.

Jobsite Specifications

  • Fuel Gas: Natural Gas (1,000 BTU/cu ft1{,}000\text{ BTU/cu ft}, SG=0.60SG = 0.60)
  • Supply Pressure: 7.0 in. w.c.7.0\text{ in. w.c.} (<0.5 psig<0.5\text{ psig})
  • Allowable Pressure Drop: 0.5 in. w.c.0.5\text{ in. w.c.} (a conservative choice; Table 6.1 would allow 1 in. w.c.1\text{ in. w.c.} at a 7 in. w.c.7\text{ in. w.c.} supply)
  • Piping Material: Schedule 40 Black Steel Pipe

Appliance Schedule & Firing Rates

  1. Appliance A — High-Efficiency Furnace: 100,000 BTU/h=100 CFH100{,}000\text{ BTU/h} = 100\text{ CFH}
  2. Appliance B — Domestic Water Heater: 40,000 BTU/h=40 CFH40{,}000\text{ BTU/h} = 40\text{ CFH}
  3. Appliance C — Gas Cooking Range: 65,000 BTU/h=65 CFH65{,}000\text{ BTU/h} = 65\text{ CFH}
  4. Appliance D — Gas Fireplace: 35,000 BTU/h=35 CFH35{,}000\text{ BTU/h} = 35\text{ CFH}
  • Total Connected System Demand: 100+40+65+35=240 CFH100 + 40 + 65 + 35 = \mathbf{240\text{ CFH}}

Layout & Linear Piping Distances

  • Meter to Junction 1 (J1): 20 feet20\text{ feet}
  • Junction 1 to Water Heater (Branch B): 15 feet15\text{ feet} (Total distance from meter: 20+15=35 ft20 + 15 = 35\text{ ft})
  • Junction 1 to Junction 2 (J2): 15 feet15\text{ feet}
  • Junction 2 to Furnace (Branch A): 10 feet10\text{ feet} (Total distance from meter: 20+15+10=45 ft20 + 15 + 10 = 45\text{ ft})
  • Junction 2 to Junction 3 (J3): 20 feet20\text{ feet}
  • Junction 3 to Range (Branch C): 10 feet10\text{ feet} (Total distance from meter: 20+15+20+10=65 ft20 + 15 + 20 + 10 = 65\text{ ft})
  • Junction 3 to Fireplace (Branch D): 20 feet20\text{ feet} (Total distance from meter: 20+15+20+20=75 ft20 + 15 + 20 + 20 = \mathbf{75\text{ ft}})

Step-by-Step Sizing Execution

Step 1: Identify Longest Developed Length (LDL)

The farthest appliance is the Gas Fireplace, located at a total developed distance of 75 feet75\text{ feet} from the meter outlet. The practice table does not list 75 feet75\text{ feet}; therefore, round UP to the 80-foot80\text{-foot} row.

All pipe segments in this system will be sized using the 80-foot80\text{-foot} row.

At 80 feet80\text{ feet}, the practice table gives:

  • 1/2-inch1/2\text{-inch}: 57 CFH57\text{ CFH}
  • 3/4-inch3/4\text{-inch}: 118 CFH118\text{ CFH}
  • 1-inch1\text{-inch}: 220 CFH220\text{ CFH}
  • 1-1/4-inch1\text{-}1/4\text{-inch}: 460 CFH460\text{ CFH}

Step 2: Size Main Trunk Segment 1 (Meter to J1)

  • Connected Load: Supplies all 4 appliances (240 CFH240\text{ CFH} total).
  • Capacity Check at 80 ft80\text{ ft}: A 1-inch1\text{-inch} pipe carries 220 CFH220\text{ CFH} (220<240220 < 240, insufficient). A 1-1/4-inch1\text{-}1/4\text{-inch} pipe carries 460 CFH460\text{ CFH} (460≥240460 \ge 240, compliant).
  • Selected Size: 1-1/4 inch1\text{-}1/4\text{ inch}

Step 3: Size Branch B to Water Heater (J1 to Water Heater)

  • Connected Load: 40 CFH40\text{ CFH}.
  • Capacity Check at 80 ft80\text{ ft}: A 1/2-inch1/2\text{-inch} pipe carries 57 CFH57\text{ CFH} (57≥4057 \ge 40, compliant).
  • Selected Size: 1/2 inch1/2\text{ inch}

Step 4: Size Main Trunk Segment 2 (J1 to J2)

  • Connected Load: Supplies Furnace, Range, and Fireplace (100+65+35=200 CFH100 + 65 + 35 = 200\text{ CFH}).
  • Capacity Check at 80 ft80\text{ ft}: A 3/4-inch3/4\text{-inch} pipe carries 118 CFH118\text{ CFH} (insufficient). A 1-inch1\text{-inch} pipe carries 220 CFH220\text{ CFH} (220≥200220 \ge 200, compliant).
  • Selected Size: 1 inch1\text{ inch}

Step 5: Size Branch A to Furnace (J2 to Furnace)

  • Connected Load: 100 CFH100\text{ CFH}.
  • Capacity Check at 80 ft80\text{ ft}: A 1/2-inch1/2\text{-inch} pipe carries only 57 CFH57\text{ CFH} (insufficient). A 3/4-inch3/4\text{-inch} pipe carries 118 CFH118\text{ CFH} (118≥100118 \ge 100, compliant).
  • Selected Size: 3/4 inch3/4\text{ inch}

Warning

If an apprentice improperly sized Branch A using its own branch distance of 10 feet10\text{ feet}, the table at 10 feet10\text{ feet} would indicate a 1/2-inch1/2\text{-inch} pipe delivers 175 CFH175\text{ CFH}, leading to the erroneous selection of 1/2-inch1/2\text{-inch} pipe. Under peak winter firing, the excessive friction across the 45 feet45\text{ feet} of total piping would starve the furnace burner, tripping its low gas pressure switch or causing roll-out.

Step 6: Size Main Trunk Segment 3 (J2 to J3)

  • Connected Load: Supplies Range and Fireplace (65+35=100 CFH65 + 35 = 100\text{ CFH}).
  • Capacity Check at 80 ft80\text{ ft}: A 1/2-inch1/2\text{-inch} pipe carries 57 CFH57\text{ CFH} (insufficient). A 3/4-inch3/4\text{-inch} pipe carries 118 CFH118\text{ CFH} (118≥100118 \ge 100, compliant).
  • Selected Size: 3/4 inch3/4\text{ inch}

Step 7: Size Branch C to Range (J3 to Range)

  • Connected Load: 65 CFH65\text{ CFH}.
  • Capacity Check at 80 ft80\text{ ft}: A 1/2-inch1/2\text{-inch} pipe carries 57 CFH57\text{ CFH} (57<6557 < 65, insufficient). A 3/4-inch3/4\text{-inch} pipe carries 118 CFH118\text{ CFH} (118≥65118 \ge 65, compliant).
  • Selected Size: 3/4 inch3/4\text{ inch}

Step 8: Size Branch D to Fireplace (J3 to Fireplace)

  • Connected Load: 35 CFH35\text{ CFH}.
  • Capacity Check at 80 ft80\text{ ft}: A 1/2-inch1/2\text{-inch} pipe carries 57 CFH57\text{ CFH} (57≥3557 \ge 35, compliant).
  • Selected Size: 1/2 inch1/2\text{ inch}

Summary Sizing Schedule

Piping SegmentDownstream Load (CFH)Table Length RowMinimum Pipe SizeSegment Capacity
Trunk 1 (Meter to J1)240 CFH240\text{ CFH}80 ft80\text{ ft}1-1/4 inch1\text{-}1/4\text{ inch}460 CFH460\text{ CFH}
Branch B (Water Heater)40 CFH40\text{ CFH}80 ft80\text{ ft}1/2 inch1/2\text{ inch}57 CFH57\text{ CFH}
Trunk 2 (J1 to J2)200 CFH200\text{ CFH}80 ft80\text{ ft}1 inch1\text{ inch}220 CFH220\text{ CFH}
Branch A (Furnace)100 CFH100\text{ CFH}80 ft80\text{ ft}3/4 inch3/4\text{ inch}118 CFH118\text{ CFH}
Trunk 3 (J2 to J3)100 CFH100\text{ CFH}80 ft80\text{ ft}3/4 inch3/4\text{ inch}118 CFH118\text{ CFH}
Branch C (Range)65 CFH65\text{ CFH}80 ft80\text{ ft}3/4 inch3/4\text{ inch}118 CFH118\text{ CFH}
Branch D (Fireplace)35 CFH35\text{ CFH}80 ft80\text{ ft}1/2 inch1/2\text{ inch}57 CFH57\text{ CFH}

Tubing Sizing Nuances: Copper & CSST

Seamless Copper Tubing (Annex A Tables A.8 & A.9)

Copper tubing for fuel gas is ASTM B88 Type K or L, or ASTM B837 Type G. Unlike steel pipe, which is designated by Nominal Pipe Size (NPS) (where 1/2-inch1/2\text{-inch} Schedule 40 has an internal diameter of 0.622 in0.622\text{ in} and an outside diameter of 0.840 in0.840\text{ in}), copper tubing is designated strictly by its Outside Diameter (OD). Consequently, a 1/2-inch1/2\text{-inch} OD copper tube has an inside diameter of only ≈0.430 in\approx 0.430\text{ in}—significantly smaller than nominal 1/2-inch1/2\text{-inch} steel pipe. Technicians must never use steel pipe tables to size copper tubing; always use the tubing tables in Annex A for the allowed pressure drop (for example Table A.8 at 0.5 in. w.c.0.5\text{ in. w.c.} and Table A.9 at 1 in. w.c.1\text{ in. w.c.}).

Corrugated Stainless Steel Tubing (CSST)

CSST features continuous helical or annular corrugations that grant flexibility but induce substantial internal fluid turbulence. Because corrugation geometry varies between manufacturers, CSST cannot be sized with generic pipe tables. Instead, CSST utilizes the Equivalent Hydraulic Diameter (EHD) rating system certified under CSA 6.26 / ANSI LC 1:

  • The manufacturer's certified engineering tables must be consulted.
  • Technicians determine the required EHD number based on gas load and LDL.
  • If sizing hybrid 2 psig2\text{ psig} CSST systems, the line regulator must be accounted for in the sizing calculation.
Loading diagram...
CSA B149.1 Longest Developed Length (LDL) Sizing Methodology
Test Your Knowledge

A residential natural gas piping system (Schedule 40 black iron, sized with this section's 0.5 in. w.c.0.5\text{ in. w.c.} practice table) supplies four appliances. The gas meter delivers 7 in. w.c.7\text{ in. w.c.}, and the distance from the meter to the farthest appliance (a 35,000 BTU/h35{,}000\text{ BTU/h} fireplace) is 72 feet72\text{ feet}. A branch line supplies a 100,000 BTU/h100{,}000\text{ BTU/h} furnace located only 15 feet15\text{ feet} along the pipe run. Using the Longest Developed Length (LDL) method, what minimum nominal pipe size is required for the furnace branch line?

A

3/4 inch, because the furnace requires 100 CFH and must be sized using the 80-foot length row

B

1/2 inch, because the branch length is only 15 feet and the table allows 120 CFH at 20 feet for 1/2 inch pipe

C

1 inch, because all furnace supply lines must match the main distribution header diameter

D

1-1/4 inch, because appliances exceeding 80,000 BTU/h require heavy-wall low-velocity piping

Test Your Knowledge

A technician is converting an appliance installation from natural gas to commercial propane. A commercial water heater has a certified firing rate of 250,000 BTU/h250{,}000\text{ BTU/h}. Assuming nominal heating values of 1,000 BTU/cu ft1{,}000\text{ BTU/cu ft} for natural gas and 2,500 BTU/cu ft2{,}500\text{ BTU/cu ft} for propane, what is the required volumetric flow rate for each fuel gas?

A

100 CFH for natural gas and 250 CFH for propane

B

250 CFH for natural gas and 100 CFH for propane

C

25 CFH for natural gas and 62.5 CFH for propane

D

625 CFH for natural gas and 250 CFH for propane

Test Your Knowledge

A residential natural gas system is supplied at 7 in. w.c. Under CSA B149.1 Table 6.1, what is the maximum allowable pressure drop, and which natural gas pipe table matches that drop?

A

2 psig, using Table A.3

B

0.5 in. w.c., using Table A.1, because 7 in. w.c. is the bottom of the range

C

1 in. w.c., using Table A.2

D

0.5 psig, using Table B.1