4.4 Basic Electricity, Ohm's Law & Electrical Power for HVAC
Key Takeaways
Ohm's Law states that voltage equals current times resistance, and the three power forms P = VI, P = I squared R, and P = V squared / R all follow from it.
Electric resistance heat converts energy at 3,412 Btu per hour for every kilowatt, which is why a 15 kW strip bank produces 51,180 Btu/h and draws 62.5 A at 240 volts.
Series circuits share one current and divide voltage; parallel circuits share one voltage and divide current, which is why every load in an HVAC control circuit is wired in parallel.
Three-phase power is calculated as the square root of 3 times line voltage times line current times power factor, roughly 1.732 times the single-phase product.
NEMA limits motor voltage unbalance to 1 percent, and a 2 percent unbalance can raise winding temperature enough to shorten motor life sharply.
4.4 Basic Electricity, Ohm's Law & Electrical Power for HVAC
Note
Why this belongs in general knowledge: Roughly one exam question in ten on the Alabama HAC examination is electrical, and the ten Electrical Applications items assume the fundamentals in this section are already fluent. Every strip-heat calculation, capacitor test, motor amperage check, and minimum circuit ampacity problem reduces to Ohm's Law and the power formulas.
The Four Quantities
| Quantity | Symbol | Unit | Water analogy | Meter |
|---|---|---|---|---|
| Voltage (electromotive force) | E or V | volt (V) | Pressure | Voltmeter, in parallel |
| Current | I | ampere (A) | Flow rate | Ammeter or clamp meter, in series or around one conductor |
| Resistance | R | ohm | Pipe friction | Ohmmeter, on a de-energized circuit only |
| Power | P | watt (W) | Work performed | Wattmeter or calculated |
Ohm's Law
The Power Wheel
Worked example: a 240-volt electric heating element measures 9.6 ohms.
- Current:
- Power:
- Heat output:
The constant 3,412 Btu/h per kilowatt is worth memorizing; it converts any electric resistance heat rating to a thermal load and appears repeatedly on the exam.
Series and Parallel Circuits
Series
One path. The same current flows through every component, resistances add, and voltage divides in proportion to resistance.
Safety devices are wired in series with the load precisely so that opening any one of them stops all current - the high-limit switch, rollout switch, pressure switch, and door switch on a furnace form a series safety string.
Parallel
Multiple paths. Every branch sees the same voltage, currents add, and total resistance is always less than the smallest branch resistance.
Loads - contactor coils, transformers, blower motors, condenser fan motors - are wired in parallel so that each receives full voltage and any one can operate independently.
Two-resistor shortcut: . Two 20-ohm branches in parallel give ohms.
Alternating Current, Phase and Power Factor
- North American utility power alternates at 60 hertz - the sine wave completes 60 full cycles per second, reversing polarity 120 times.
- Meters read root-mean-square (RMS) values. A nominal 240 V RMS sine wave has a peak of V, which is why a 240-volt circuit stresses insulation to roughly 340 volts.
- Single-phase residential service is normally 120/240 V; three-phase commercial service is commonly 208Y/120 V, 480Y/277 V, or 240 V delta.
Power in AC Circuits
| Quantity | Formula (single phase) | Formula (three phase) |
|---|---|---|
| Apparent power (VA) | ||
| True power (watts) | ||
| Power factor | same |
Purely resistive loads such as electric heat have a power factor of 1.0, so watts equal volt-amperes. Motors are inductive: current lags voltage and the power factor falls to roughly 0.80 to 0.90, so a motor drawing 10 A at 240 V consumes 2,400 VA but only about 2,040 watts of true power.
Three-phase example: a 480-volt, three-phase compressor draws 22 A at a 0.85 power factor.
Voltage Unbalance: A Motor Killer
Three-phase voltage unbalance produces disproportionate current unbalance and rapid winding heating.
Worked example: measured line voltages are 462, 476, and 469 V. The average is V. The maximum deviation is V. Unbalance is .
- NEMA recommends operating motors at no more than 1% voltage unbalance.
- Current unbalance runs roughly 6 to 10 times the voltage unbalance percentage.
- At 2% voltage unbalance a motor should be derated; at 5% it should not be operated at all.
Measuring Safely
- Voltage is measured in parallel with the circuit, under power. Resistance is measured only with power off and with capacitors discharged - an ohmmeter applied to a live circuit is destroyed and can injure the technician.
- A clamp ammeter reads the magnetic field around a single conductor. Clamping both conductors of a 240-volt circuit reads zero, because the opposing fields cancel.
- Meter category (CAT) ratings describe how much transient energy the meter can survive: CAT II at the receptacle, CAT III at the distribution panel and fixed equipment, CAT IV at the service entrance and utility connection. Use a CAT III 600 V or better meter at HVAC disconnects and panels, and confirm the leads carry the same rating as the meter.
- Always apply the live-dead-live test: prove the meter on a known live source, test the target circuit, then prove the meter again.
A 240-volt electric resistance heating element measures 12 ohms of resistance. What is its current draw and heating capacity?
20 amperes and 16,378 Btu/h
20 amperes and 4,800 Btu/h
28.8 amperes and 20,472 Btu/h
2,880 amperes and 51,180 Btu/h
A technician measures three-phase line voltages of 228, 240, and 234 volts at a rooftop unit disconnect. What is the voltage unbalance, and what does NEMA guidance say about it?
1.7 percent unbalance, which is within the 1 percent NEMA recommendation
5.1 percent unbalance, taking the full 12-volt spread between the highest and lowest readings
2.6 percent unbalance, which exceeds the NEMA recommendation and warrants investigation before the compressor is restarted
0.5 percent unbalance, because unbalance is calculated against the nominal 240-volt rating
Why are the high-limit switch, rollout switch, and pressure switch on a gas furnace wired in series with the gas valve, while the blower motor, inducer motor, and transformer are wired in parallel across the supply?
Series wiring divides voltage among the safeties so each one sees a safe, reduced potential
Series wiring means opening any single safety interrupts all current to the valve, while parallel wiring gives each load full voltage and independent operation
Parallel wiring reduces total circuit current, which allows smaller conductors to be used for the loads
The arrangement is a manufacturer preference with no functional significance to the control sequence
Sections you finish are checked off in the contents.