4.2 Backflow Prevention Devices (Air Gap, RPZ, DCVA, PVB)
Key Takeaways
- Protection hierarchy from highest to lowest: air gap > reduced pressure zone (RPZ) > pressure vacuum breaker (PVB) > double check valve assembly (DCVA).
- Air gap must be at least 2× the supply pipe diameter or 1 inch minimum, and protects against both backsiphonage and backpressure.
- RPZ (two check valves plus a relief valve open to atmosphere) is the standard device for high-hazard (health) cross-connections and protects against backsiphonage and backpressure.
- PVB protects against backsiphonage only, must be installed at least 12 inches above the highest downstream outlet, and is common on irrigation lines.
- Backsiphonage is caused by negative pressure (vacuum) pulling water back; backpressure is caused by downstream pressure greater than supply pushing water back.
4.2 Backflow Prevention Devices (Air Gap, RPZ, DCVA, PVB)
Quick Answer: A cross-connection is any physical link between potable water and a non-potable source. Backflow is the reverse flow of used or contaminated water through that link. The hardware that stops it ranks, from strongest to weakest: air gap > reduced pressure zone (RPZ) assembly > pressure vacuum breaker (PVB) > double check valve assembly (DCVA). Match the device to the hazard: high-hazard (health) connections need an air gap or RPZ; low-hazard (non-health) connections can use a DCVA; irrigation with no backpressure risk can use a PVB.
Why backflow matters
Potable distribution normally maintains positive pressure outward to every service, so water only flows one way. Two conditions can reverse that:
- Backsiphonage — a drop or loss of supply pressure (main break, pump failure, high fire demand) creates a vacuum that pulls water from the customer back into the main.
- Backpressure — the customer's side has pressure higher than the supply (a boiler, pump, elevated tank, or chemical feed) and pushes water into the main.
Any device that protects against both is more versatile than one that protects against only backsiphonage.
The protection hierarchy
| Device | Protects vs backsiphonage | Protects vs backpressure | Hazard level | Testable? | Key install rule |
|---|---|---|---|---|---|
| Air gap | Yes | Yes | Highest (health) | N/A (physical) | Gap ≥ 2× pipe diameter or 1 in min |
| RPZ (reduced pressure zone assembly) | Yes | Yes | High (health) | Yes | Above ground, not in flooded pit |
| PVB (pressure vacuum breaker) | Yes | No | Moderate (non-health) | Yes | ≥12 in above highest downstream outlet |
| DCVA (double check valve assembly) | Yes | Yes (lower protection) | Low (non-health) | Yes | Can be below ground in a vault |
| AVB (atmospheric vacuum breaker) | Yes | No | Low | No | Not for continuous pressure |
Air gap
An air gap is a physical separation between the supply outlet and the flood rim of the receiving vessel. It is the highest level of protection because there is no mechanical path for water to return. The rule of thumb is AG ≥ 2× the inside diameter of the supply pipe, or at least 1 inch, whichever is greater. Air gaps protect against both backsiphonage and backpressure. The trade-off is that the flow falls through air and is not under pressure downstream, so you need a reservoir or tank to collect it; you cannot run a pressurized line through an air gap.
Reduced pressure zone assembly (RPZ)
A reduced pressure zone (RPZ) assembly is the strongest mechanical device. It contains two independently spring-loaded check valves in series with a relief valve between them open to atmosphere. The zone between the two checks is kept at a pressure lower than supply. If the supply pressure drops, or if either check valve fails, the relief valve opens and dumps the contaminated water to the floor rather than letting it reach the potable main. Because the relief valve dumps on failure, an RPZ protects against both backsiphonage and backpressure and is the required device for high-hazard (health-threat) cross-connections — chemical feed, medical, industrial, irrigation with chemicals, car washes, etc.
Installation rules to remember:
- Must be installed above ground, not in a pit that can flood (a flooded pit defeats the relief valve).
- Must be testable — a certified tester uses gauge kits to verify both checks and the relief valve.
- Must not be buried or installed where the relief port can be submerged.
Double check valve assembly (DCVA)
A double check valve assembly (DCVA) has two independent spring-loaded check valves in series and no relief valve. It protects against backsiphonage and backpressure but at a lower level than an RPZ, because if a check fails there is no dump path — the second check is the only barrier. DCVAs are rated for low-hazard (non-health) service only, such as a residential irrigation line without chemicals or a fire sprinkler system with no antifreeze. They are testable and can be installed below grade in a vault, which is one reason they are chosen where an RPZ is not required.
Pressure vacuum breaker (PVB)
A pressure vacuum breaker (PVB) has a single check valve plus an atmospheric vent that opens when supply pressure drops, admitting air to break the siphon. It protects against backsiphonage only — not backpressure. It must be installed at least 12 inches above the highest downstream outlet so the siphon cannot pull water over it. PVBs are common on residential and commercial irrigation systems. They are not suitable for continuous pressure below grade or for lines that can see backpressure (a pump or elevated tank downstream).
Atmospheric vacuum breaker (AVB)
An atmospheric vacuum breaker (AVB) is similar to a PVB but is not designed for continuous pressure — it must be on a line that opens to atmosphere when not flowing. It is the simplest and cheapest backsiphonage device and is not testable. On the exam, know that AVBs are backsiphonage-only and not for continuous pressure.
Selecting the device — a decision flow
- Is the hazard high (health) or low (non-health)? High → air gap or RPZ. Low → DCVA or PVB.
- Can the downstream side produce backpressure? Yes → you cannot use PVB or AVB; choose RPZ (high hazard) or DCVA (low hazard). No → PVB or AVB is acceptable for backsiphonage.
- Can the device be flooded or submerged? RPZ must be above ground; DCVA can be in a vault.
- Is there a physical gap possible at the receiving vessel? If yes, an air gap is the gold standard.
Installation and testing notes
- All mechanical assemblies (RPZ, DCVA, PVB) are testable and must be tested at install, after repair, and annually.
- An RPZ that dumps continuously is telling you a check has failed or supply pressure is unstable — do not cap the relief port.
- Do not install a PVB below the highest downstream outlet; if the outlet is higher than the PVB, the siphon can still pull.
- The cross-connection control program (ordinance, surveys, test records) is a separate management topic; this section covers the hardware you will see on the exam.
A car wash bay is connected to the potable supply and the downstream side includes a chemical soap injection pump that can pressurize the line above supply pressure. Which backflow device is required?
What is the minimum air gap for a 2-inch supply pipe under the general rule (2× inside diameter or 1 inch, whichever is greater)?
Which statement correctly describes a double check valve assembly (DCVA)?
A main break upstream of a service line causes the distribution pressure to drop below atmospheric, pulling water from a customer's hose back into the main. What is this type of backflow called?