Free CIT Exam Flashcards

Memorize 50 essential terms and definitions for the Irrigation Association Certified Irrigation Technician (CIT). See the term, recall the definition, then flip to check yourself.

50 Flashcards
3 Topics
100% Free
TermClick to flip

Spray head vs. rotor: why can they never share a zone?

Tap to reveal definition
Card 1 of 50Basic Irrigation Principles

Filter by Topic

Jump to Card

About These CIT Flashcards

These 50 flashcards are designed to help you memorize key terms and definitions for the Irrigation Association Certified Irrigation Technician (CIT). Each card shows a term on the front and its definition on the back—the classic flashcard format for vocabulary memorization. Use these alongside our practice questions to build both recall and comprehension.

Topics Covered

Basic Irrigation Principles22 cards
Electrical Principles15 cards
Hydraulic Principles13 cards

Complete Flashcard Reference

Review every term in this set. Open any term to reveal its definition.

Spray head vs. rotor: why can they never share a zone?

A fixed spray applies roughly 1.5 to 2.0 in/hr while a gear-driven rotor applies roughly 0.4 to 0.6 in/hr. On one zone the spray area floods long before the rotor area is watered. What must match within a zone is precipitation rate, not brand or body style.

Matched precipitation rate (MPR) nozzle

A nozzle series whose flow is scaled to arc, so a quarter-circle nozzle discharges about one quarter the GPM of a full-circle nozzle at the same radius. Every arc on the zone then applies the same inches per hour. Non-MPR nozzles leave the quarter heads badly over-watered.

Precipitation rate formula on the IA equation sheet

PR (in/hr) = 96.3 x total GPM / area (sq ft). The constant 96.3 converts gallons per minute spread over square feet into inches per hour. Use the total flow of the zone and the total area that zone actually covers.

Head-to-head (50 percent) spacing

Heads are spaced so each one throws water all the way to the next head, which is about 50 percent of the diameter of throw. Sprinklers apply the most water close to the head, so the overlap is what creates uniform coverage. Tighten spacing further on windy sites.

When does a zone need cycle-and-soak?

When the zone's precipitation rate is higher than the soil's intake (infiltration) rate, which shows up as runoff or puddling. Split the required run time into several short cycles with soak periods between them. The total water applied does not change, only the delivery.

Purpose of a swing joint under a sprinkler head

An articulated riser assembly (typically three street ells, or flexible pipe) between the lateral and the head. It absorbs mower and vehicle impact, lets you set head height to finished grade, and keeps that shock from snapping the lateral fitting off the pipe.

PVC 'Class 200' vs. 'Schedule 40': what does each rating describe?

Class pipe is rated by pressure: Class 200 means 200 psi working pressure at 73 F in every diameter. Schedule pipe is rated by wall thickness, so its pressure rating falls as diameter grows - a 4 in Schedule 40 is rated far lower than a 1/2 in Schedule 40.

Solvent-welding PVC: what does the primer actually do?

Primer softens and cleans both the pipe end and the socket so the cement can chemically fuse them into one piece; it is not just a cleaner. Prime, cement, seat with a quarter turn, hold, and do not pressurize until the cement maker's cure time for that size and temperature has passed.

How are polyethylene (PE) pipe joints made?

With barbed insert fittings clamped with stainless-steel clamps, or with compression fittings. Solvent cement does not bond polyethylene at all. PE stays flexible in cold soil, which is why it is common for laterals in hard-freeze regions.

Pump cavitation: what causes it and what does it sound like?

Suction-side pressure drops below the water's vapor pressure, so bubbles form and then collapse violently in the impeller. It sounds like gravel in the pump and it pits the impeller. Fix the suction side - clogged screen, undersized or leaking suction line, too much lift - not the discharge side.

Backsiphonage vs. backpressure

Backsiphonage is backflow caused by negative pressure in the supply, such as a water main break or heavy hydrant use pulling a vacuum. Backpressure is backflow caused by downstream pressure exceeding supply pressure, from a pump, elevation, or thermal expansion. Vacuum breakers stop only the first.

Atmospheric vacuum breaker (AVB): what are its limits?

Backsiphonage protection only. It installs downstream of the control valve, at least 6 in above the highest downstream outlet, and it may not stay under continuous pressure (12 hours or less at a time). No shutoff valve may be installed downstream. Some local codes require more height.

Pressure vacuum breaker (PVB): what makes it different from an AVB?

A PVB is a testable assembly that may stay under continuous pressure, so one unit upstream of all the zone valves protects the whole system. Set it at least 12 in above the highest downstream outlet. Like the AVB it stops backsiphonage only, never backpressure.

Double check valve assembly (DCVA)

Two independently loaded check valves in series with test cocks. It protects against both backsiphonage and backpressure, but it is approved for low-hazard (pollutant) connections only. Where local code permits, a DCVA may be installed below grade in a vault.

Reduced pressure principle assembly (RP)

Two check valves plus a relief valve that dumps to atmosphere the moment the zone between the checks loses its pressure differential. It is the only assembly accepted for high-hazard (contaminant) irrigation connections, such as systems with chemical injection. It installs above grade, commonly at least 12 in, and the relief port must never be submerged.

First step before any trenching, boring, or stake driving

Call 811 (or the local one-call center) and wait the required notice period for the utilities to mark the site. Marks expire and must be re-requested if the work is delayed. Hand-dig inside the tolerance zone around every marked line.

Maximum air pressure for a compressed-air blowout

Industry practice caps blowout at about 80 psi on rigid PVC and about 50 psi on flexible polyethylene, and never above the lowest-rated component on that zone. Volume (CFM) is what pushes the water out; raising pressure instead of CFM blows nozzles off and splits fittings.

Why is the blowout compressor connected downstream of the backflow assembly?

High-velocity, heat-carrying air destroys the internal rubber checks and seats of a PVB, RP, or DCVA. Never blow compressed air through a backflow assembly. Drain it separately through its test cocks and leave the test cocks open for the winter.

Spring startup: why open the main slowly instead of all at once?

The system is full of air. Charging it fast drives that air ahead of the water as a surge that can blow nozzles out and crack fittings. Open the isolation valve part way, let each zone run to purge air and flush debris, then check heads and pressure.

Using the water meter to confirm a hidden leak

Shut every fixture and zone, then watch the meter's low-flow indicator - the small triangle, star, or dial. Any movement means water is still passing, most often a control valve leaking by or a cracked lateral. This confirms a leak exists before you start digging for it.

What do purple pipe, purple valve box lids, and purple tape mean?

Reclaimed or non-potable water. The color coding is required so nobody cross-connects that line to drinking water or a hose bib. Reclaimed sites also carry warning signage, and their quick couplers are typically keyed differently from potable ones.

What is an as-built drawing, and why does a technician care?

A record drawing of what was actually installed - mainline routing, valve, splice, and sleeve locations, head layout - which almost always differs from the design plan. It is the fastest way to find a buried valve and the cheapest way to avoid cutting a mainline on the next repair.

Ohm's Law in irrigation troubleshooting

V = I x R, or volts = amps x ohms. At a fixed 24 VAC the resistance decides the current: a shorted coil (low ohms) pulls too much current and faults the station output, while an open coil (infinite ohms) pulls none and the valve never opens.

Why must the meter be set to VAC, not VDC, to test a station output?

Irrigation controllers send 24 volts alternating current to the zone solenoids, stepped down by a transformer at the controller. Because it is AC, the two solenoid leads have no polarity - either one may go to the common.

Solenoid resistance: what reading says the coil is good?

Roughly 20 to 60 ohms measured across the two solenoid leads with the meter on ohms; Rain Bird's own troubleshooting guidance uses this window for landscape valves. Confirm it against the specific manufacturer's spec, because coil ratings differ by model.

Open circuit (OL or infinite ohms) read between a station wire and the common

A broken coil winding, a cut field wire, or a corroded splice. Re-test at the valve with the solenoid leads disconnected: if the solenoid alone reads normal, the break is out in the field wiring, not in the valve.

Short circuit (near-zero ohms) read between a station wire and the common

Failed coil insulation, a nicked wire jacket touching the common, or two solenoids wired onto one station. A short pulls excess current and typically blows the controller fuse or trips a station fault. Isolate at the valve to tell the coil from the wire.

Why do you kill power and disconnect the leads before an ohms test?

A resistance measurement injects the meter's own small current. Live 24 VAC on the circuit produces a false reading and can damage the meter. Voltage is tested live; resistance and continuity are tested dead and isolated.

Common wire vs. station (zone) wire

Each solenoid gets its own station wire back to a numbered controller terminal, and all of the solenoids share one common return to the COM terminal, conventionally white. A broken station wire kills one zone; a broken common kills every zone past the break.

Why will a standard wire nut not survive a buried valve splice?

Wire nuts are not rated for wet or direct-burial use. Water wicks in, corrodes the copper, and raises circuit resistance until the valve stops pulling in. Use a listed waterproof direct-burial connector (grease-cap or gel-filled) and leave an expansion loop of wire in the box.

A valve sits at the far end of a long wire run. What changes?

Voltage drop. Resistance rises with wire length and falls as the wire gets thicker, so long runs need a larger conductor - a smaller AWG number, 14 instead of 18. Too much drop leaves the solenoid under-volted, so it chatters or never lifts.

What does the controller's transformer do, and how do you test it?

It steps 120 VAC line power down to about 24 VAC for the solenoids. Read the primary input and the secondary output with the meter on VAC. Line voltage present but no 24 VAC out means the transformer has failed, not the field wiring.

Three settings that define one irrigation program

Start time(s), station run times, and watering days or interval. The program begins once per start time and then steps through its stations in order - it does not run only one station per start time.

A zone runs three times every morning and nobody changed the run times. Why?

Three start times are entered in the same program, and each start time re-runs the entire program from station one. Delete the extra start times. Shortening or lengthening run times will never fix a repeat-cycle problem.

Master valve (MV) terminal vs. pump start relay

Both use the same controller output, energized whenever any station runs. A master valve is a normally closed valve that leaves the mainline unpressurized between cycles; a pump start relay uses that 24 VAC signal to switch the pump's line-voltage circuit. Never wire a pump straight to the MV terminal.

How do you find a buried valve when there is no as-built?

With a wire tracker: a transmitter puts a tone on the station wire and a receiver follows the signal above ground to the solenoid. The same tool finds breaks, because the tone stops at the fault. Narrow the search first with the box lids and the mainline route.

How does a rain shutoff sensor stop the system?

It opens the circuit - wired into the controller's sensor terminals or in series with the common - so no solenoid can be energized even though the program keeps running its clock. That is why a controller can display a zone as running while nothing waters.

Static pressure vs. dynamic (working) pressure

Static is measured with no water moving; dynamic is measured with the zone running. The gap between them is everything the water lost getting there - friction in pipe, fittings, valve, and meter, plus elevation. Sizing decisions use dynamic pressure at the head, never static at the point of connection.

Converting between psi and feet of head

1 psi = 2.31 ft of water, and 1 ft of water = 0.433 psi. Both come from the weight of water, so a 1 ft column exerts 0.433 psi at its base no matter how wide the pipe is. Diameter changes volume, not static pressure.

A head sits 20 ft uphill of its valve. How much pressure does elevation cost?

About 8.7 psi, from 20 ft x 0.433 psi/ft, before any friction loss is counted. Running the same 20 ft downhill adds that pressure instead. Elevation is separate from friction and is added to or subtracted from the pressure budget on its own.

Reading a friction loss chart

Charts give loss in psi (or feet) per 100 ft for one pipe size, material, and flow rate, so multiply by the run length in hundreds of feet. Loss climbs steeply with flow and drops steeply as pipe size increases - one size up usually beats buying more pressure.

Why is pipe velocity commonly held at or below about 5 ft/s?

Faster water carries enough momentum that a quick-closing valve converts it into a pressure surge - water hammer - that fractures fittings and pipe. Low velocity also keeps friction loss reasonable. Size the pipe to the flow rather than forcing more GPM through a small line.

What causes water hammer, and how do you reduce it?

The shock wave from stopping moving water abruptly: a fast-closing solenoid valve, a quickly shut ball valve, or trapped air slamming shut. Reduce it by holding velocity down, upsizing pipe, using the valve's flow control to slow closure, and purging air at startup.

Globe body vs. angle body control valve

Both use the same diaphragm mechanism. A globe valve's inlet and outlet are in line, so it drops into a straight run of pipe. An angle valve turns the flow 90 degrees, which suits a bottom-inlet installation and generally costs slightly less pressure.

Anti-siphon valve

An angle control valve with an atmospheric vacuum breaker built into the same body, so each zone carries its own backflow protection. It must be above ground and at least 6 in above the highest head it serves (some codes require 12 in), and nothing that can create backpressure may be installed downstream of it.

What does the flow control stem on a control valve do?

It limits how far the diaphragm can lift, throttling the zone. Use it to trim excess pressure at the heads when they mist, and to slow the valve's closure. It is not a shutoff, and closing it too far can stop the valve from opening at all.

Manual bleed screw on a solenoid valve: what does it prove?

Opening it vents the diaphragm chamber and forces the valve open hydraulically with no electricity involved. If the zone runs on bleed but not from the controller, the fault is electrical - solenoid, field wire, or controller. If it will not run on bleed either, the fault is mechanical.

Two components every drip zone needs downstream of the valve

A filter and a pressure regulator. Emitter passages are small enough to plug on particles a sprinkler would pass straight through, and drip runs at far lower pressure than a sprinkler zone, so unregulated mainline pressure blows fittings off the tubing.

What does a filter's 'mesh' number mean for drip?

Openings per linear inch of screen, so a higher number is a finer screen that catches smaller particles. Landscape drip typically calls for roughly 120 to 200 mesh, about 75 to 125 microns. Always meet the emitter manufacturer's stated minimum.

What does a flow sensor paired with a master valve protect against?

It compares measured flow against the learned flow for the running zone. High flow means a broken mainline, a blown lateral, or a missing head; low flow means a stuck valve or a plugged zone. On an alarm the controller closes the master valve, which is why the pair is used on large or unattended sites.

Frequently Asked Questions

How many questions are on the CIT exam and how long do I get?

The Irrigation Association's exam specification sheet lists 100 multiple-choice questions, equally weighted, with 3 hours allotted. The exam is offered in English and Spanish. You may bring a silent, battery-operated, nonprinting calculator and #2 pencils; scratch sheets and the equation sheet are supplied at the testing center. Phones, tablets, and smart watches are not permitted.

What is the passing score for the CIT exam?

There is no fixed announced passing score. The IA states that individual forms of the CIT exam contain different blends of questions and that statistical equating produces a pass-fail score tied to the specific form, so the cut score is not announced before the administration. The IA adds that the passing score typically ranges between 68% and 72%. Results are reported only as pass or fail - computer-based candidates get results within 24 hours by email, and paper-pencil candidates in about 45 days.

What topics are on the CIT exam?

The official detailed content outline has three domains: Understanding Basic Irrigation Principles at 41-46%, Understanding Electrical Principles at 28-32%, and Understanding Hydraulic Principles at 26-27%. Sprinklers and nozzles, swing joints, pipe fittings, pumps, backflow functionality, water meters, job safety, and winterization sit in the first domain. Voltmeter use, controllers, transformers, solenoids, wiring, and splicing sit in the second. Sensors, valves, pressure and flow testing, drip mechanics, and friction loss charts sit in the third.

Do I need experience or a sponsor to take the CIT exam?

No sponsor and no degree are required. The Irrigation Association recommends a minimum of six months or 1,000 hours of irrigation-related field experience, but that is a recommendation rather than an eligibility gate. You must agree to the code of ethics on the application, register at least 14 days before the exam date, and present photo ID with a signature at the testing center. All IA certification programs are self study, and IA education courses are not required to sit for the exam.

What happens if I fail the CIT exam?

You cannot schedule a retake until you have been officially notified of your result, and no candidate may retake an IA exam until 90 days have passed. You may sit the exam no more than three times within a two-year period; if the third attempt is unsuccessful you must wait one year before re-applying to the program. Failed candidates receive an analysis-of-performance report identifying the deficient knowledge areas. Exam fees are not refunded for a failed attempt.

How do I keep my CIT certification current?

Recertify every two years by earning and submitting 20 CEUs, of which a minimum of five Tier 1 CEUs per cycle must relate to sustainable irrigation or water-efficient concepts. CEUs must be earned during the current cycle and generally cannot be carried forward. A renewal fee is also due every year by December 31. Certifications that lapse are suspended and eventually revoked, and a lapsed professional must retake and pass the exam at full price to regain the credential.

Same family resources

Explore More Irrigation Association Certifications

Continue into nearby exams from the same family. Each card keeps practice questions, study guides, flashcards, videos, and articles in one place.