Cheat sheet

IA CIT Cheat Sheet

Quick Facts

Exam
CIT
Credential
Certified Irrigation Technician
Body
Irrigation Association
Questions
100 multiple choice
Weighting
All items weighted equally
Time
3 hours
Pass
Unannounced; typically 68-72%
Delivery
Computer-based testing centers
Languages
English and Spanish
Fee
$175 member / $300 nonmember
Experience
6 months or 1,000 hours
Register by
14 days before exam
Bring
Silent nonprinting calculator, pencils
Provided
Scratch sheets and equations
Results
Emailed within 24 hours
Retake
90 days between attempts
Attempt cap
Three per two-year period
Recert
20 CEUs every two years

What Each Backflow Stops

Siphon only: AVB, PVB. Both: DCVA, RP

AVB: no continuous pressurePVB: continuous pressure allowedDCVA: low hazard onlyRP: high hazard rated

Backsiphonage vs Backpressure

Backsiphonage

  • Supply pressure turns negative
  • Main break or hydrant use
  • AVB and PVB protect

Backpressure

  • Downstream pressure exceeds supply
  • Pump, boiler, or elevation
  • Needs DCVA or RP

Suction vs push back

Backflow Assembly Picker

  1. High hazard or chemigationRP assembly(12 in above grade)
  2. Backpressure is possibleDCVA or RP(Vacuum breakers fail here)
  3. Low hazard, continuous pressurePVB(12 in above heads)
  4. Low hazard, below gradeDCVA(Vault with drainage)
  5. One zone, intermittent pressureAVB(6 in above heads)
  6. Reclaimed water supplyRP assembly(Purple pipe required)
  7. Absolute separation neededAir gap(Not a testable assembly)

Sprinklers + Nozzles

Fixed spray head
Fine mist, no moving stream
Spray precipitation rate
Roughly 1.5-2.0 in/hrFast
Gear-drive rotor
Rotating stream, larger radius
Rotor precipitation rate
Roughly 0.4-0.6 in/hrSlow
Spray nozzle pressure
About 30 psi at nozzle
Rotor nozzle pressure
About 45 psi at nozzle
Head-to-head spacing
Throw reaches the next head
Spacing percentage
About 50% of diameter
MPR nozzle
Flow scaled to arc
Quarter-circle MPR flow
About one quarter of full
Misting at nozzle
Pressure is too high
Dry ring around head
Pressure is too low
Nozzle replacement rule
Match brand, arc, radius
Zone matching rule
Never mix sprays and rotors

Blowout Limits

80 PVC, 50 poly, never through backflow

80 psi rigid PVC50 psi polyethyleneConnect downstream of backflowAlways wear eye protection

AVB vs PVB

AVB

  • 6 in above highest outlet
  • Downstream of each valve
  • No continuous pressure
  • Not testable

PVB

  • 12 in above highest outlet
  • Upstream of all valves
  • Continuous pressure allowed
  • Testable assembly

Per zone vs whole system

Sprinkler Symptom Picker

  1. Fine fog at nozzleReduce pressure(Regulator or flow control)
  2. Short throw, large dropletsRaise pressure(Check for leaks)
  3. Dry ring around headPressure too low(Or wrong nozzle)
  4. Head weeps after shutdownAdd check valve(Classic low-head drainage)
  5. Head will not retractDebris in wiper seal(Flush the riser)
  6. Uneven depth across arcsInstall MPR nozzles(Match flow to arc)
  7. Runoff before cycle endsCycle and soak(Rate exceeds infiltration)

Swing Joints + Fittings

Swing joint
Flexible riser under sprinkler head
Triple-swing assembly
Three street ells linked
Swing joint purpose
Absorbs impact, allows height adjustment
PVC primer
Softens and cleans joint surfaces
Solvent cement
Fuses pipe and fitting
Cement cure time
Wait per label before pressurizing
Poly pipe joints
Barbed insert plus stainless clamp
Poly and solvent cement
Cement will not bond poly
Threaded joint sealing
Tape or dope, no overtightening
Male adapter rule
Plastic male into metal female

Locate Paint Colors

Red power, yellow gas, blue water, purple reclaimed

Orange: communicationsGreen: sewerWhite: proposed digPink: survey marks

Class vs Schedule Pipe

Class pipe

  • Number is the psi rating
  • Class 200 means 200 psi
  • Same rating every diameter

Schedule pipe

  • Number describes wall thickness
  • Rating falls as diameter grows
  • Schedule 40 is common

Pressure rated vs wall rated

Pipe + Pressure Ratings

Class 200 PVC
200 psi working pressurePressure rated
Class 315 PVC
315 psi working pressure
Schedule 40
Wall thickness, not fixed psiWall rated
Schedule rating drift
Rating falls as diameter grows
SDR
Diameter divided by wall thickness
Rating temperature
Rated at 73 degrees F
Polyethylene pipe
Flexible, freeze tolerant, barbed fittings
Purple pipe
Reclaimed, non-potable water
Mainline
Constantly pressurized upstream of valves
Lateral
Pressurized only while zone runs
Sleeve
Larger pipe under hardscape

Spray vs Rotor

Fixed spray

  • About 1.5-2.0 in/hr
  • Roughly 30 psi nozzle
  • Short radius, sprays continuously

Gear rotor

  • About 0.4-0.6 in/hr
  • Roughly 45 psi nozzle
  • Long radius, rotating stream

Never mix in one zone

Backflow Functionality

AVB
Backsiphonage only, not testable
AVB height
6 in above highest outlet
AVB pressure limit
No continuous pressure allowed
AVB position
Downstream of the control valve
PVB
Testable, continuous pressure allowed
PVB height
12 in above highest outlet
PVB protection
Backsiphonage only, not backpressure
DCVA
Two check valves in seriesLow hazard
RP assembly
Checks plus atmospheric relief valveHigh hazard
RP height
12 in above grade
Air gap
Physical separation, strongest protection
Anti-siphon valve
Control valve with built-in AVB
Chemigation protection
RP assembly required
Assembly testing
Usually annual, per local code

Pumps + Water Supplies

Centrifugal pump
Above water, needs priming
Submersible pump
Sits in well below water
Jet pump
Shallow well, self-priming
Cavitation
Suction bubbles collapse in impeller
Cavitation sound
Like gravel rattling inside pump
Pump start relay
Controller signal energizes pump
Dry-run protection
Low pressure or float cutoff
Dead-heading a pump
Closed discharge overheats the pump
Potable supply
City main through backflow assembly
Non-potable supply
Well, pond, or reclaimed
Static water level
Well level before pumping
Drawdown
Level drop while pumping

Water Meters + Leaks

Low-flow indicator
Small triangle, star, or dial
Leak test
All off, indicator still turns
Meter sizing
Size to peak system flow
Oversized flow
Meter loses excessive pressure
Mainline leak sign
Wet spot, meter creeps constantly
Lateral leak sign
Wet only while zone runs
Low-head drainage
Lowest head weeps after shutdown
Check valve fix
Stops low-head drainage

Job Safety

Call 811 first
Mark utilities before any digging
Locate wait period
Legal notice before breaking ground
Red locate paint
Electric power lines
Yellow locate paint
Gas, oil, or steam
Orange locate paint
Communication and signal lines
Blue locate paint
Potable water lines
Purple locate paint
Reclaimed water and irrigation
Green locate paint
Sewer and drain lines
Trench safety
Shore or slope deep trenches
Confined space entry
Test atmosphere, follow permit
SDS
Chemical hazard sheets onsite
Blowout eye protection
Required whenever air is used

Startup + Winterization

Spring startup
Fill slowly to purge air
Fast fill risk
Air surge blows nozzles off
Blowout PVC limit
80 psi maximum air
Blowout poly limit
50 psi maximum air
Compressor sizing
Zone GPM divided by 7.5
Blowout connection point
Downstream of the backflow assembly
Air through backflow
Destroys internal checks and seats
Blowout run limit
Short bursts, one zone
Manual drain system
Open drain valves at lows
Backflow winterizing
Open test cocks, relieve pressure
Controller in winter
Set off or rain mode

Soil-Plant-Water Basics

Infiltration rate
Speed soil absorbs applied water
Sandy soil
Fast intake, low water holding
Clay soil
Slow intake, high water holding
Runoff cause
Precipitation rate exceeds infiltration rate
Cycle and soak
Split run time, add soaks
Root zone depth
Turf shallower than trees
Field capacity
Water held after gravity drainage
Wilting point
Plant can no longer extract
Available water
Between capacity and wilting point

Plans + As-Builts

As-built drawing
Record of what was installed
Legend
Key to plan symbols
Scale
Plan distance to real distance
Engineer scale
Reads decimal foot plans
Specifications
Written material and method rules
Valve location record
Measure from two fixed points
Sleeve record
Pipe crossings under hardscape

Ohm's Law

V = I x R at 24 VAC

Volts = amps x ohmsLow ohms means high current20-60 ohms is healthy

Open vs Short Circuit

Open circuit

  • Meter reads OL or infinite
  • Cut wire or burned coil
  • Zone simply will not run

Short circuit

  • Meter reads near zero ohms
  • Nicked jacket or failed coil
  • Controller faults or blows fuse

No path vs bypass path

Zone Will Not Start

  1. Controller display is deadCheck 120 VAC supply(Breaker or GFCI)
  2. No zone runs at allTest transformer output(Look for 24 VAC)
  3. One zone silent, others fineTest that station output(Meter set to VAC)
  4. Station reads 24 VACFault is in field(Wire, splice, or solenoid)
  5. Station reads zero voltsController output failed(Move wire to spare)
  6. Bleed screw opens valveElectrical fault confirmed(Valve is mechanically sound)
  7. Bleed screw does nothingHydraulic fault confirmed(No water or debris)
  8. Sensor light is activeBypass the rain sensor(Common wire interrupted)

Voltmeter Operation

VAC setting
Measures field solenoid voltage
VDC setting
Wrong for 24 VAC circuits
Ohms setting
Power off, leads disconnected
Continuity
Beeps on a complete path
Amps setting
Measures current draw inline
Clamp meter
Reads amps without breaking circuit
OL reading
Open circuit, infinite resistance
Near-zero ohms
Short circuit or crossed wires
Healthy station voltage
Roughly 24-28 VAC under load
Zero volts at station
No output from the controller
Solenoid current draw
Well under one amp

Troubleshooting Order

Power, program, controller, wire, solenoid, valve

Start at the controllerSplit the run in halfBleed screw separates the fault

Master Valve vs Pump Relay

Master valve

  • Normally closed solenoid valve
  • Isolates mainline when idle
  • Limits leak and break damage

Pump start relay

  • Switches line power to pump
  • Controller cannot drive pumps
  • Needs adequate zone flow

Same terminal, different device

Ohm Reading Picker

  1. Reads 20-60 ohmsCoil is healthy(Look upstream instead)
  2. Reads under 20 ohmsShorted solenoid(Replace the coil)
  3. Reads OL or infiniteOpen circuit(Cut wire or coil)
  4. Good at valve, bad at controllerField wire or splice(Track the wire)
  5. Resistance climbing over timeCorroded splice(Redo waterproof connector)
  6. Two zones open togetherTwo solenoids, one station(Split to separate terminals)

Controllers + Transformers

Program
Start times, run times, days
Start time meaning
Whole program runs once each
Repeated cycles cause
Extra start times were entered
Station terminal
One numbered wire per zone
Common terminal
Shared return for all solenoids
MV/P terminal
Master valve or pump relay
Transformer job
Steps 120 VAC to 24
Transformer test
Read primary and secondary volts
Seasonal adjust
Percent scaling of every runtime
Rain delay
Pauses watering for set days
Controller reset
Clears faults per manufacturer steps
Smart ET controller
Adjusts runtime from weather data
Manual station test
Runs each zone in order

Solenoids + Field Wiring

Solenoid function
Plunger vents the diaphragm chamber
Solenoid voltage
24 VAC standard
Healthy coil resistance
Roughly 20-60 ohmsMemorize
Below 20 ohms
Shorted coil, blows fuse
Infinite ohms
Open coil or cut wire
Manual bleed screw
Opens valve without any electricity
Bleed opens the valve
Fault is electrical, not hydraulic
Wire size rule
Longer runs need thicker wire
Voltage drop
Volts lost over wire length
Common wire color
Usually white in the field
Burial depth
6 in minimum, NEC low voltage
Under driveways, streets
18 in homes; 24 in streets
Spare wires
Pull extras for future repairs

Wire Tracking + Splices

Wire tracker
Transmitter tone plus handheld receiver
Valve locating
Follow the tone to solenoid
Direct-burial splice
Waterproof grease or gel connector
Wire nut alone
Not rated for buried splices
Failing splice symptom
Resistance climbs, valve chatters
Splice location
Inside an accessible valve box
Surge protection
Ground the controller properly
Lightning damage sign
Several zones dead at once

Pressure and Head

psi x 2.31 = feet; feet x 0.433 = psi

2.31 feet per psi0.433 psi per foot20 feet costs 8.7 psi

Static vs Dynamic Pressure

Static

  • Measured with no flow
  • Highest reading you will see
  • Set by supply and elevation

Dynamic

  • Measured while zone runs
  • Always lower than static
  • Falls further as flow rises

No flow vs flowing

Low Pressure Picker

  1. Static reading is lowSupply side problem(Meter, city, or well)
  2. Static fine, dynamic lowFlow related loss(Friction or too many heads)
  3. Only far heads sufferUndersized lateral pipe(Check the friction chart)
  4. All zones weak after repairPartly closed isolation valve(Open it fully)
  5. Uphill heads are weakElevation loss(0.433 psi per foot)
  6. Pressure fine, flow poorClogged filter or nozzle(Clean and retest)
  7. Whole system lost pressureMainline break(Meter spins with all off)

Pressure + Flow Testing

Static pressure
Measured with no flow
Dynamic pressure
Measured while the zone runs
Pressure loss
Static minus dynamic reading
psi to feet
Multiply psi by 2.31IA equation
Feet to psi
Multiply feet by 0.433IA equation
Elevation gain
Costs 0.433 psi per foot
Elevation drop
Gains 0.433 psi per foot
Flow equation
Q = A x V
Velocity limit
Below 5 feet per second
Water hammer
Surge from fast valve closure
Gauge test point
Read at the last head
Bucket test
Time to fill known volume
Precipitation rate equation
PR = 96.3 x GPM / area

Globe vs Angle Valve

Globe body

  • Inlet and outlet inline
  • Drops into straight pipe
  • Serviced from the top

Angle body

  • Inlet below, outlet at side
  • Turns flow ninety degrees
  • Used under anti-siphon valves

Straight run vs corner

Drip Component Picker

  1. Emitters plugging repeatedlyFiner filter(120-200 mesh)
  2. Pressure over emitter ratingPressure regulator(Often 25-30 psi)
  3. Long run or slopePressure compensating emitters(Even flow throughout)
  4. Fines collect at line endFlush valve(Flush every season)
  5. Soil pulled in at shutdownAir vacuum relief(Install at high point)
  6. Turf area over driplineSubsurface drip(Add root protection)

Valves

Globe valve body
Inlet and outlet inline
Angle valve body
Inlet below, outlet at side
Diaphragm operation
Pressure above holds valve shut
Flow control stem
Throttles the zone at valve
Master valve
Normally closed, isolates the mainline
Isolation valve
Manual shutoff for repairs
Quick coupling valve
Hose point on the mainline
Valve box
Access, protection, splice housing
Valve will not close
Debris under the diaphragm
Valve will not open
No power or plugged port
Valve chatter
Weak voltage or low flow
Pressure regulating module
Holds a set downstream pressure

Chart vs Hazen-Williams

CIT scope

  • Read friction loss charts
  • Look up size and flow
  • Multiply by run length

Designer scope

  • Computes the Hazen-Williams equation
  • Sizes pipe from scratch
  • Tested on CID and CIC

Look up, do not derive

Sensors

Rain sensor
Interrupts the common wire
Rain sensor test
Press plunger, zone should stop
Freeze sensor
Blocks watering below set temperature
Wind sensor
Suspends watering above set speed
Soil moisture sensor
Waters only when soil dries
Flow sensor
Reports actual gallons per minute
High flow alarm
Broken mainline or stuck valve
Low flow alarm
Clogged zone or closed valve
Sensor bypass switch
Ignores the sensor for testing

Drip Mechanics

Required drip components
Filter and pressure regulator
Filter mesh
Openings per linear inch
Typical emitter filtration
120-200 mesh screen
Higher mesh number
Finer screen, smaller particles
Drip pressure regulator
Commonly set 25-30 psi
Pressure compensating emitter
Even flow across pressure range
Non-compensating emitter
Flow rises with pressure
Maximum lateral length
Limited by flow and slope
Flush valve
Purges fines from line ends
Air vacuum relief
Stops soil suction at shutdown
Subsurface drip
Buried dripline with root protection
Emitter flow units
Gallons per hour, not minute

Friction Loss Charts

Chart basis
Loss per 100 feet
Chart inputs
Pipe size, material, flow
Scale to run
Multiply by actual pipe length
Smaller pipe
Higher velocity, higher loss
Larger pipe
Lower velocity, lower loss
C factor
Pipe roughness coefficient
Fitting losses
Added as equivalent pipe length
Chart columns
Velocity beside friction loss

Common Traps

Class vs Schedule

Class 200 means 200 psi Schedule 40 is wall thickness

Vacuum breaker heights

AVB sits 6 inches up PVB sits 12 inches up

Vacuum breakers and backpressure

AVB and PVB stop backsiphonage Only DCVA and RP stop backpressure

Chart vs equation

CIT reads friction charts Designers compute Hazen-Williams

Volts vs ohms

Volts tested with power on Ohms tested with power off

Bleed screw diagnosis

Bleed opens means electrical fault Bleed fails means hydraulic fault

Master valve vs relay

Master valve stops water Relay switches pump power

Mesh number direction

200 mesh is a finer screen 100 mesh is a coarser screen

Mixing head types

Spray applies 1.5-2.0 in/hr Rotor applies 0.4-0.6 in/hr

Pass mark

Cut score varies by form It is not a flat 70%

Last Minute

  1. 1.Principles 41-46%, electrical 28-32%
  2. 2.Hydraulics is 26-27% of exam
  3. 3.100 questions, 3 hours, equal weight
  4. 4.Pass mark unannounced, typically 68-72%
  5. 5.1 psi = 2.31 feet head
  6. 6.1 foot head = 0.433 psi
  7. 7.Keep velocity below 5 ft/s
  8. 8.Healthy solenoid reads 20-60 ohms
  9. 9.AVB 6 in, PVB 12 in
  10. 10.RP is the high-hazard assembly
  11. 11.Class pipe number is its psi
  12. 12.Blowout: 80 PVC, 50 poly
  13. 13.Never blow air through backflow
  14. 14.Ohms testing requires power off
  15. 15.Bleed screw isolates electrical faults
  16. 16.Drip needs filter and regulator
  17. 17.Higher mesh number is finer
  18. 18.Call 811 before any digging
  19. 19.Read charts, do not derive
  20. 20.Retake wait is 90 days
  21. 21.Recert: 20 CEUs, two years
Same family resources

Explore More Irrigation Association Certifications

Continue into nearby exams from the same family. Each card keeps practice questions, study guides, flashcards, videos, and articles in one place.