Understanding Basic Irrigation Principles
41-46%of exam
Understanding Electrical Principles
28-32%of exam
Understanding Hydraulic Principles
26-27%of exam
Quick Facts
- Exam
- CIT
- Credential
- Certified Irrigation Technician
- Body
- Irrigation Association
- Questions
- 100 multiple choice
- Weighting
- All items weighted equally
- Time
- 3 hours
- Pass
- Unannounced; typically 68-72%
- Delivery
- Computer-based testing centers
- Languages
- English and Spanish
- Fee
- $175 member / $300 nonmember
- Experience
- 6 months or 1,000 hours
- Register by
- 14 days before exam
- Bring
- Silent nonprinting calculator, pencils
- Provided
- Scratch sheets and equations
- Results
- Emailed within 24 hours
- Retake
- 90 days between attempts
- Attempt cap
- Three per two-year period
- Recert
- 20 CEUs every two years
What Each Backflow Stops
Siphon only: AVB, PVB. Both: DCVA, RP
Backsiphonage vs Backpressure
Backsiphonage
- Supply pressure turns negative
- Main break or hydrant use
- AVB and PVB protect
Backpressure
- Downstream pressure exceeds supply
- Pump, boiler, or elevation
- Needs DCVA or RP
Suction vs push back
Backflow Assembly Picker
- High hazard or chemigation→RP assembly(12 in above grade)
- Backpressure is possible→DCVA or RP(Vacuum breakers fail here)
- Low hazard, continuous pressure→PVB(12 in above heads)
- Low hazard, below grade→DCVA(Vault with drainage)
- One zone, intermittent pressure→AVB(6 in above heads)
- Reclaimed water supply→RP assembly(Purple pipe required)
- Absolute separation needed→Air gap(Not a testable assembly)
Sprinklers + Nozzles
- Fixed spray head
- Fine mist, no moving stream
- Spray precipitation rate
- Roughly 1.5-2.0 in/hrFast
- Gear-drive rotor
- Rotating stream, larger radius
- Rotor precipitation rate
- Roughly 0.4-0.6 in/hrSlow
- Spray nozzle pressure
- About 30 psi at nozzle
- Rotor nozzle pressure
- About 45 psi at nozzle
- Head-to-head spacing
- Throw reaches the next head
- Spacing percentage
- About 50% of diameter
- MPR nozzle
- Flow scaled to arc
- Quarter-circle MPR flow
- About one quarter of full
- Misting at nozzle
- Pressure is too high
- Dry ring around head
- Pressure is too low
- Nozzle replacement rule
- Match brand, arc, radius
- Zone matching rule
- Never mix sprays and rotors
Blowout Limits
80 PVC, 50 poly, never through backflow
AVB vs PVB
AVB
- 6 in above highest outlet
- Downstream of each valve
- No continuous pressure
- Not testable
PVB
- 12 in above highest outlet
- Upstream of all valves
- Continuous pressure allowed
- Testable assembly
Per zone vs whole system
Sprinkler Symptom Picker
- Fine fog at nozzle→Reduce pressure(Regulator or flow control)
- Short throw, large droplets→Raise pressure(Check for leaks)
- Dry ring around head→Pressure too low(Or wrong nozzle)
- Head weeps after shutdown→Add check valve(Classic low-head drainage)
- Head will not retract→Debris in wiper seal(Flush the riser)
- Uneven depth across arcs→Install MPR nozzles(Match flow to arc)
- Runoff before cycle ends→Cycle and soak(Rate exceeds infiltration)
Swing Joints + Fittings
- Swing joint
- Flexible riser under sprinkler head
- Triple-swing assembly
- Three street ells linked
- Swing joint purpose
- Absorbs impact, allows height adjustment
- PVC primer
- Softens and cleans joint surfaces
- Solvent cement
- Fuses pipe and fitting
- Cement cure time
- Wait per label before pressurizing
- Poly pipe joints
- Barbed insert plus stainless clamp
- Poly and solvent cement
- Cement will not bond poly
- Threaded joint sealing
- Tape or dope, no overtightening
- Male adapter rule
- Plastic male into metal female
Locate Paint Colors
Red power, yellow gas, blue water, purple reclaimed
Class vs Schedule Pipe
Class pipe
- Number is the psi rating
- Class 200 means 200 psi
- Same rating every diameter
Schedule pipe
- Number describes wall thickness
- Rating falls as diameter grows
- Schedule 40 is common
Pressure rated vs wall rated
Pipe + Pressure Ratings
- Class 200 PVC
- 200 psi working pressurePressure rated
- Class 315 PVC
- 315 psi working pressure
- Schedule 40
- Wall thickness, not fixed psiWall rated
- Schedule rating drift
- Rating falls as diameter grows
- SDR
- Diameter divided by wall thickness
- Rating temperature
- Rated at 73 degrees F
- Polyethylene pipe
- Flexible, freeze tolerant, barbed fittings
- Purple pipe
- Reclaimed, non-potable water
- Mainline
- Constantly pressurized upstream of valves
- Lateral
- Pressurized only while zone runs
- Sleeve
- Larger pipe under hardscape
Spray vs Rotor
Fixed spray
- About 1.5-2.0 in/hr
- Roughly 30 psi nozzle
- Short radius, sprays continuously
Gear rotor
- About 0.4-0.6 in/hr
- Roughly 45 psi nozzle
- Long radius, rotating stream
Never mix in one zone
Backflow Functionality
- AVB
- Backsiphonage only, not testable
- AVB height
- 6 in above highest outlet
- AVB pressure limit
- No continuous pressure allowed
- AVB position
- Downstream of the control valve
- PVB
- Testable, continuous pressure allowed
- PVB height
- 12 in above highest outlet
- PVB protection
- Backsiphonage only, not backpressure
- DCVA
- Two check valves in seriesLow hazard
- RP assembly
- Checks plus atmospheric relief valveHigh hazard
- RP height
- 12 in above grade
- Air gap
- Physical separation, strongest protection
- Anti-siphon valve
- Control valve with built-in AVB
- Chemigation protection
- RP assembly required
- Assembly testing
- Usually annual, per local code
Pumps + Water Supplies
- Centrifugal pump
- Above water, needs priming
- Submersible pump
- Sits in well below water
- Jet pump
- Shallow well, self-priming
- Cavitation
- Suction bubbles collapse in impeller
- Cavitation sound
- Like gravel rattling inside pump
- Pump start relay
- Controller signal energizes pump
- Dry-run protection
- Low pressure or float cutoff
- Dead-heading a pump
- Closed discharge overheats the pump
- Potable supply
- City main through backflow assembly
- Non-potable supply
- Well, pond, or reclaimed
- Static water level
- Well level before pumping
- Drawdown
- Level drop while pumping
Water Meters + Leaks
- Low-flow indicator
- Small triangle, star, or dial
- Leak test
- All off, indicator still turns
- Meter sizing
- Size to peak system flow
- Oversized flow
- Meter loses excessive pressure
- Mainline leak sign
- Wet spot, meter creeps constantly
- Lateral leak sign
- Wet only while zone runs
- Low-head drainage
- Lowest head weeps after shutdown
- Check valve fix
- Stops low-head drainage
Job Safety
- Call 811 first
- Mark utilities before any digging
- Locate wait period
- Legal notice before breaking ground
- Red locate paint
- Electric power lines
- Yellow locate paint
- Gas, oil, or steam
- Orange locate paint
- Communication and signal lines
- Blue locate paint
- Potable water lines
- Purple locate paint
- Reclaimed water and irrigation
- Green locate paint
- Sewer and drain lines
- Trench safety
- Shore or slope deep trenches
- Confined space entry
- Test atmosphere, follow permit
- SDS
- Chemical hazard sheets onsite
- Blowout eye protection
- Required whenever air is used
Startup + Winterization
- Spring startup
- Fill slowly to purge air
- Fast fill risk
- Air surge blows nozzles off
- Blowout PVC limit
- 80 psi maximum air
- Blowout poly limit
- 50 psi maximum air
- Compressor sizing
- Zone GPM divided by 7.5
- Blowout connection point
- Downstream of the backflow assembly
- Air through backflow
- Destroys internal checks and seats
- Blowout run limit
- Short bursts, one zone
- Manual drain system
- Open drain valves at lows
- Backflow winterizing
- Open test cocks, relieve pressure
- Controller in winter
- Set off or rain mode
Soil-Plant-Water Basics
- Infiltration rate
- Speed soil absorbs applied water
- Sandy soil
- Fast intake, low water holding
- Clay soil
- Slow intake, high water holding
- Runoff cause
- Precipitation rate exceeds infiltration rate
- Cycle and soak
- Split run time, add soaks
- Root zone depth
- Turf shallower than trees
- Field capacity
- Water held after gravity drainage
- Wilting point
- Plant can no longer extract
- Available water
- Between capacity and wilting point
Plans + As-Builts
- As-built drawing
- Record of what was installed
- Legend
- Key to plan symbols
- Scale
- Plan distance to real distance
- Engineer scale
- Reads decimal foot plans
- Specifications
- Written material and method rules
- Valve location record
- Measure from two fixed points
- Sleeve record
- Pipe crossings under hardscape
Ohm's Law
V = I x R at 24 VAC
Open vs Short Circuit
Open circuit
- Meter reads OL or infinite
- Cut wire or burned coil
- Zone simply will not run
Short circuit
- Meter reads near zero ohms
- Nicked jacket or failed coil
- Controller faults or blows fuse
No path vs bypass path
Zone Will Not Start
- Controller display is dead→Check 120 VAC supply(Breaker or GFCI)
- No zone runs at all→Test transformer output(Look for 24 VAC)
- One zone silent, others fine→Test that station output(Meter set to VAC)
- Station reads 24 VAC→Fault is in field(Wire, splice, or solenoid)
- Station reads zero volts→Controller output failed(Move wire to spare)
- Bleed screw opens valve→Electrical fault confirmed(Valve is mechanically sound)
- Bleed screw does nothing→Hydraulic fault confirmed(No water or debris)
- Sensor light is active→Bypass the rain sensor(Common wire interrupted)
Voltmeter Operation
- VAC setting
- Measures field solenoid voltage
- VDC setting
- Wrong for 24 VAC circuits
- Ohms setting
- Power off, leads disconnected
- Continuity
- Beeps on a complete path
- Amps setting
- Measures current draw inline
- Clamp meter
- Reads amps without breaking circuit
- OL reading
- Open circuit, infinite resistance
- Near-zero ohms
- Short circuit or crossed wires
- Healthy station voltage
- Roughly 24-28 VAC under load
- Zero volts at station
- No output from the controller
- Solenoid current draw
- Well under one amp
Troubleshooting Order
Power, program, controller, wire, solenoid, valve
Master Valve vs Pump Relay
Master valve
- Normally closed solenoid valve
- Isolates mainline when idle
- Limits leak and break damage
Pump start relay
- Switches line power to pump
- Controller cannot drive pumps
- Needs adequate zone flow
Same terminal, different device
Ohm Reading Picker
- Reads 20-60 ohms→Coil is healthy(Look upstream instead)
- Reads under 20 ohms→Shorted solenoid(Replace the coil)
- Reads OL or infinite→Open circuit(Cut wire or coil)
- Good at valve, bad at controller→Field wire or splice(Track the wire)
- Resistance climbing over time→Corroded splice(Redo waterproof connector)
- Two zones open together→Two solenoids, one station(Split to separate terminals)
Controllers + Transformers
- Program
- Start times, run times, days
- Start time meaning
- Whole program runs once each
- Repeated cycles cause
- Extra start times were entered
- Station terminal
- One numbered wire per zone
- Common terminal
- Shared return for all solenoids
- MV/P terminal
- Master valve or pump relay
- Transformer job
- Steps 120 VAC to 24
- Transformer test
- Read primary and secondary volts
- Seasonal adjust
- Percent scaling of every runtime
- Rain delay
- Pauses watering for set days
- Controller reset
- Clears faults per manufacturer steps
- Smart ET controller
- Adjusts runtime from weather data
- Manual station test
- Runs each zone in order
Solenoids + Field Wiring
- Solenoid function
- Plunger vents the diaphragm chamber
- Solenoid voltage
- 24 VAC standard
- Healthy coil resistance
- Roughly 20-60 ohmsMemorize
- Below 20 ohms
- Shorted coil, blows fuse
- Infinite ohms
- Open coil or cut wire
- Manual bleed screw
- Opens valve without any electricity
- Bleed opens the valve
- Fault is electrical, not hydraulic
- Wire size rule
- Longer runs need thicker wire
- Voltage drop
- Volts lost over wire length
- Common wire color
- Usually white in the field
- Burial depth
- 6 in minimum, NEC low voltage
- Under driveways, streets
- 18 in homes; 24 in streets
- Spare wires
- Pull extras for future repairs
Wire Tracking + Splices
- Wire tracker
- Transmitter tone plus handheld receiver
- Valve locating
- Follow the tone to solenoid
- Direct-burial splice
- Waterproof grease or gel connector
- Wire nut alone
- Not rated for buried splices
- Failing splice symptom
- Resistance climbs, valve chatters
- Splice location
- Inside an accessible valve box
- Surge protection
- Ground the controller properly
- Lightning damage sign
- Several zones dead at once
Pressure and Head
psi x 2.31 = feet; feet x 0.433 = psi
Static vs Dynamic Pressure
Static
- Measured with no flow
- Highest reading you will see
- Set by supply and elevation
Dynamic
- Measured while zone runs
- Always lower than static
- Falls further as flow rises
No flow vs flowing
Low Pressure Picker
- Static reading is low→Supply side problem(Meter, city, or well)
- Static fine, dynamic low→Flow related loss(Friction or too many heads)
- Only far heads suffer→Undersized lateral pipe(Check the friction chart)
- All zones weak after repair→Partly closed isolation valve(Open it fully)
- Uphill heads are weak→Elevation loss(0.433 psi per foot)
- Pressure fine, flow poor→Clogged filter or nozzle(Clean and retest)
- Whole system lost pressure→Mainline break(Meter spins with all off)
Pressure + Flow Testing
- Static pressure
- Measured with no flow
- Dynamic pressure
- Measured while the zone runs
- Pressure loss
- Static minus dynamic reading
- psi to feet
- Multiply psi by 2.31IA equation
- Feet to psi
- Multiply feet by 0.433IA equation
- Elevation gain
- Costs 0.433 psi per foot
- Elevation drop
- Gains 0.433 psi per foot
- Flow equation
- Q = A x V
- Velocity limit
- Below 5 feet per second
- Water hammer
- Surge from fast valve closure
- Gauge test point
- Read at the last head
- Bucket test
- Time to fill known volume
- Precipitation rate equation
- PR = 96.3 x GPM / area
Globe vs Angle Valve
Globe body
- Inlet and outlet inline
- Drops into straight pipe
- Serviced from the top
Angle body
- Inlet below, outlet at side
- Turns flow ninety degrees
- Used under anti-siphon valves
Straight run vs corner
Drip Component Picker
- Emitters plugging repeatedly→Finer filter(120-200 mesh)
- Pressure over emitter rating→Pressure regulator(Often 25-30 psi)
- Long run or slope→Pressure compensating emitters(Even flow throughout)
- Fines collect at line end→Flush valve(Flush every season)
- Soil pulled in at shutdown→Air vacuum relief(Install at high point)
- Turf area over dripline→Subsurface drip(Add root protection)
Valves
- Globe valve body
- Inlet and outlet inline
- Angle valve body
- Inlet below, outlet at side
- Diaphragm operation
- Pressure above holds valve shut
- Flow control stem
- Throttles the zone at valve
- Master valve
- Normally closed, isolates the mainline
- Isolation valve
- Manual shutoff for repairs
- Quick coupling valve
- Hose point on the mainline
- Valve box
- Access, protection, splice housing
- Valve will not close
- Debris under the diaphragm
- Valve will not open
- No power or plugged port
- Valve chatter
- Weak voltage or low flow
- Pressure regulating module
- Holds a set downstream pressure
Chart vs Hazen-Williams
CIT scope
- Read friction loss charts
- Look up size and flow
- Multiply by run length
Designer scope
- Computes the Hazen-Williams equation
- Sizes pipe from scratch
- Tested on CID and CIC
Look up, do not derive
Sensors
- Rain sensor
- Interrupts the common wire
- Rain sensor test
- Press plunger, zone should stop
- Freeze sensor
- Blocks watering below set temperature
- Wind sensor
- Suspends watering above set speed
- Soil moisture sensor
- Waters only when soil dries
- Flow sensor
- Reports actual gallons per minute
- High flow alarm
- Broken mainline or stuck valve
- Low flow alarm
- Clogged zone or closed valve
- Sensor bypass switch
- Ignores the sensor for testing
Drip Mechanics
- Required drip components
- Filter and pressure regulator
- Filter mesh
- Openings per linear inch
- Typical emitter filtration
- 120-200 mesh screen
- Higher mesh number
- Finer screen, smaller particles
- Drip pressure regulator
- Commonly set 25-30 psi
- Pressure compensating emitter
- Even flow across pressure range
- Non-compensating emitter
- Flow rises with pressure
- Maximum lateral length
- Limited by flow and slope
- Flush valve
- Purges fines from line ends
- Air vacuum relief
- Stops soil suction at shutdown
- Subsurface drip
- Buried dripline with root protection
- Emitter flow units
- Gallons per hour, not minute
Friction Loss Charts
- Chart basis
- Loss per 100 feet
- Chart inputs
- Pipe size, material, flow
- Scale to run
- Multiply by actual pipe length
- Smaller pipe
- Higher velocity, higher loss
- Larger pipe
- Lower velocity, lower loss
- C factor
- Pipe roughness coefficient
- Fitting losses
- Added as equivalent pipe length
- Chart columns
- Velocity beside friction loss
Common Traps
Class vs Schedule
Class 200 means 200 psi ≠ Schedule 40 is wall thickness
Vacuum breaker heights
AVB sits 6 inches up ≠ PVB sits 12 inches up
Vacuum breakers and backpressure
AVB and PVB stop backsiphonage ≠ Only DCVA and RP stop backpressure
Chart vs equation
CIT reads friction charts ≠ Designers compute Hazen-Williams
Volts vs ohms
Volts tested with power on ≠ Ohms tested with power off
Bleed screw diagnosis
Bleed opens means electrical fault ≠ Bleed fails means hydraulic fault
Master valve vs relay
Master valve stops water ≠ Relay switches pump power
Mesh number direction
200 mesh is a finer screen ≠ 100 mesh is a coarser screen
Mixing head types
Spray applies 1.5-2.0 in/hr ≠ Rotor applies 0.4-0.6 in/hr
Pass mark
Cut score varies by form ≠ It is not a flat 70%
Last Minute
- 1.Principles 41-46%, electrical 28-32%
- 2.Hydraulics is 26-27% of exam
- 3.100 questions, 3 hours, equal weight
- 4.Pass mark unannounced, typically 68-72%
- 5.1 psi = 2.31 feet head
- 6.1 foot head = 0.433 psi
- 7.Keep velocity below 5 ft/s
- 8.Healthy solenoid reads 20-60 ohms
- 9.AVB 6 in, PVB 12 in
- 10.RP is the high-hazard assembly
- 11.Class pipe number is its psi
- 12.Blowout: 80 PVC, 50 poly
- 13.Never blow air through backflow
- 14.Ohms testing requires power off
- 15.Bleed screw isolates electrical faults
- 16.Drip needs filter and regulator
- 17.Higher mesh number is finer
- 18.Call 811 before any digging
- 19.Read charts, do not derive
- 20.Retake wait is 90 days
- 21.Recert: 20 CEUs, two years
Explore More Irrigation Association Certifications
Continue into nearby exams from the same family. Each card keeps practice questions, study guides, flashcards, videos, and articles in one place.