System Fundamentals & Devices
30-40%of exam
Circuits & Power
25-30%of exam
Installation & Mounting
15-20%of exam
Codes, Testing & Inspection
10-15%of exam
Quick Facts
- Exam
- NICET FAS-I
- Questions
- 85 MCQ
- Time
- 110 min
- Pass
- 500/700
- Format
- Open book
- Codes
- NFPA 72/70
- Fee
- $230
- Level
- Entry technician
Signal Priority
Alarm beats Supervisory beats Trouble
Ionization vs Photoelectric
Ionization
- Flaming fires
- Small particles
- Radioactive source
Photoelectric
- Smoldering fires
- Large particles
- Light scatter
Flaming vs smoldering
Which Detector Type?
- Smoldering fire risk→Photoelectric(Visible particles)
- Flaming fire risk→Ionization(Small particles)
- Large open hall→Beam detector(Long range)
- Dusty/dirty area→Heat detector(Avoid false alarm)
- High-value early warning→Aspirating(Air sampling)
- Rapid temperature jump→ROR heat(Rate change)
- Steady high heat→Fixed-temp heat(Setpoint)
- HVAC smoke spread→Duct detector(Shut fan)
Smoke Detectors
- Ionization
- Fast flaming fires
- Photoelectric
- Slow smoldering fires
- Beam
- Large open areas
- Aspirating
- Air-sample very-early warning
- Duct detector
- Sample HVAC airflow
- Spacing
- 30 ft on-center
- Off wall
- 4 in minimum
Smoke Memory
Ion flames fast, Photo smolders slow
Fixed-temp vs ROR Heat
Fixed-temp
- Reaches setpoint
- 135-174 F
- Will not reset
ROR
- Rate of change
- 12-15 F/min
- Self-restoring
Setpoint vs rate
Heat Detectors
- Fixed-temp
- Activates at setpoint
- ROR
- Rate-of-rise change
- ROR rate
- 12-15 F/min rise
- Ordinary rating
- 135-174 F
- Line-type
- Cable senses length
- Combination
- Fixed plus ROR
Alarm vs Super vs Trouble
Alarm
- Fire detected
- Smoke or waterflow
- Highest priority
Super / Trouble
- Super: tamper, impairment
- Trouble: open, ground
- Lower priority
Fire vs fault
Manual & Sprinkler
- Pull station
- Manual alarm initiation
- Single-action
- One pull motion
- Double-action
- Push-then-pull
- Near exits
- Within 5 ft
- Waterflow
- Sprinkler flow alarm
- Tamper switch
- Valve supervisory signal
- Retard chamber
- Ignores surge transients
Notification Appliances
- Horn
- Audible only
- Strobe
- Visible candela flash
- Horn/strobe
- Audible plus visible
- Speaker
- Voice EVACS output
- Temporal-3
- Standard evacuation pattern
- 520 Hz
- Sleeping-area low frequency
- Sync
- Strobes flash together
Control Unit & Signals
- FACP
- Fire alarm control panel
- Conventional
- Zone-based addressing
- Addressable
- Per-device point ID
- Alarm
- Fire condition signal
- Supervisory
- System impairment signal
- Trouble
- Fault or open signal
- Annunciator
- Remote status display
Battery Calc
24 h standby plus 5 min alarm
Class A vs Class B
Class A
- Return loop
- Survives one open
- No EOL resistor
Class B
- No return
- Open stops devices
- EOL resistor
Redundant vs simple
Class A vs Class B?
- Survive single open→Class A(Return loop)
- Simple, lower cost→Class B(EOL resistor)
- Need fault isolation→Class X(Short tolerant)
- Network backbone→Class N(Ethernet)
- End-of-line on B→EOL resistor(Supervision)
- Both wire paths used→Class A(Out and back)
Circuit Classes
- Class B
- No return path
- Class A
- Redundant return loop
- Class X
- Loop with fault isolation
- Class N
- Ethernet network path
- EOL resistor
- Class B supervision end
- Single fault
- Class A keeps operating
Circuit Classes
A loops, B ends, X isolates, N networks
IDC vs SLC vs NAC
IDC / SLC
- IDC: conventional inputs
- SLC: addressable poll
- Both initiate
NAC
- Drives appliances
- Horns and strobes
- Polarized output
Input vs output
Battery Sizing Steps
- Sum standby current→Standby amps(Quiescent)
- Multiply by 24 h→Standby Ah(Ah)
- Sum alarm current→Alarm amps(All NACs)
- Multiply by 5 min→Alarm Ah(5/60 hour)
- Add both totals→Required Ah(Subtotal)
- Apply derating→Times 1.2(Safety factor)
Pathways & Wiring
- IDC
- Initiating device circuit
- SLC
- Signaling line circuit
- NAC
- Notification appliance circuit
- Polarity
- NAC devices polarized
- Survivability
- Pathway protected from fire
- Ground fault
- Unwanted earth path
- Supervision
- Detects opens/shorts
NEC 760 Cable
FPL, then Riser, then Plenum
Primary vs Secondary Power
Primary
- Utility branch
- Dedicated circuit
- Normal supply
Secondary
- Standby battery
- 24 h plus 5 min
- AC-loss backup
Mains vs backup
NEC Article 760
- PLFA
- Power-limited fire alarm
- NPLFA
- Non-power-limited fire alarm
- FPL
- General cable type
- FPLR
- Riser-rated cable
- FPLP
- Plenum-rated cable
- Separation
- Apart from power
- Red jacket
- Common FA marking
Power & Battery
- Primary
- Utility branch circuit
- Secondary
- Standby battery backup
- Standby
- 24 h supervisory load
- Alarm load
- 5 min after standby
- Safety factor
- Multiply 1.2 result
- Charger
- Supervised, recharges battery
- AC loss
- Trouble signal generated
Mounting Heights
- Pull handle
- 42-60 in AFF
- Reach max
- 48 in ADA
- Wall strobe
- 80-96 in lens
- Ceiling strobe
- Per listed spacing
- Smoke spacing
- 30 ft on-center
- Beam ceiling
- Reduce spacing per depth
- Off wall
- Detector 4 in min
Audibility & Candela
- Public mode
- Plus 15 dB ambient
- Private mode
- Plus 10 dB ambient
- Max ceiling
- Approx 110 dBA limit
- Sleeping mode
- 75 dBA at pillow
- Candela
- Strobe light intensity
- Spacing table
- Room size vs candela
- Sync rule
- Avoid seizure flash rate
Codes & Testing
- Ch 10
- Fundamentals and power
- Ch 14
- Inspection, testing, maintenance
- Ch 17
- Initiating devices
- Ch 18
- Notification appliances
- Ch 23
- Protected premises pathways
- AHJ
- Authority having jurisdiction
- Smoke sensitivity
- Tested every 2 years
- Record of Completion
- Documents installed system
Common Traps
Ionization vs photoelectric
Ion senses flaming ≠ Photo senses smoldering
Fixed-temp vs ROR
Fixed hits setpoint ≠ ROR senses rate
Class A vs Class B
Class A loops back ≠ Class B uses EOL
Supervisory vs trouble
Supervisory is impairment ≠ Trouble is wiring fault
Public vs private mode
Public adds 15 dB ≠ Private adds 10 dB
Initiating vs notification
Chapter 17 inputs ≠ Chapter 18 outputs
Standby vs alarm time
Standby is 24 h ≠ Alarm is 5 min
Last Minute
- 1.Open book: NFPA 72 + 70 on-screen
- 2.85 questions in 110 minutes
- 3.Pass = 500 on 0-700 scale
- 4.Priority: alarm > supervisory > trouble
- 5.Ion = flaming; photo = smoldering
- 6.Fixed = setpoint; ROR = rate change
- 7.Class A = loop; B = EOL
- 8.Battery: 24 h standby + alarm
- 9.Apply 1.2 battery safety factor
- 10.Public mode = ambient + 15 dB
- 11.Pull station handle 42-60 in
- 12.Wall strobe lens 80-96 in
Explore More NICET Certifications
Continue into nearby exams from the same family. Each card keeps practice questions, study guides, flashcards, videos, and articles in one place.
More From This Family
Videos and articles for deeper review.
