4.4 Flexible Raceways, ENT, Wireways, Cable Trays, Specialty Cables & Plenum Rules

Key Takeaways

  • Flexible metal conduit and liquidtight flexible metal conduit must be secured within 12 inches of each box and at intervals of no more than 4-1/2 feet (NEC 348.30, 350.30).
  • Listed FMC may serve as the equipment grounding conductor only when the total flexible length in the ground-fault return path is 6 feet or less and the circuit is protected at 20 amperes or less (NEC 250.118(5)).
  • ENT must be secured within 3 feet of each box and at intervals of no more than 3 feet (NEC 362.30).
  • Metal wireways and sheet-metal auxiliary gutters may be filled to 20 percent of their cross section, and derating applies only above 30 current-carrying conductors (NEC 366.22, 376.22).
  • Type UF cable ampacity is limited to the 60 degree C column, and UF may not be used as service-entrance cable or embedded in poured concrete (NEC 340.12, 340.80).
Last updated: September 2026

Why this section matters

Articles 300 through 398 carry about 10 of the 60 NEC and theory questions, the most of any area on the PSI outline. Sections 4.1 through 4.3 covered Article 300 basics, common cables, rigid raceways, conduit fill, and boxes. This section covers the other wiring methods that show up in lookup questions.

Support and securing intervals at a glance

Wiring methodSecure withinMaximum support interval2020 NEC
EMT3 ft of each box or fitting10 ft358.30
RMC and IMC3 ft of each box or fitting10 ft (longer for threaded straight runs per Table 344.30(B)(2))342.30, 344.30
PVC, trade size 1/2 to 13 ft of each box3 ftTable 352.30
PVC, trade size 1-1/4 to 23 ft of each box5 ftTable 352.30
PVC, trade size 2-1/2 to 33 ft of each box6 ftTable 352.30
PVC, trade size 3-1/2 to 53 ft of each box7 ftTable 352.30
ENT3 ft of each box3 ft362.30
FMC and LFMC12 in. of each box4-1/2 ft348.30, 350.30
NM and AC cable12 in. of each box4-1/2 ft334.30, 320.30
MC cable (four or fewer conductors, 10 AWG and smaller at boxes)12 in. of each box6 ft330.30
MI cableper 332.306 ft332.30

Flexible metal conduit (Article 348)

Not permitted (348.12):

  • in wet locations;
  • in hoistways (except as Article 620 allows) or storage battery rooms;
  • in hazardous locations, except as 501.10(B) allows;
  • where exposed to materials that damage the conductors;
  • underground or embedded in poured concrete or aggregate;
  • where subject to physical damage.

Securing (348.30): within 12 inches of each box, cabinet, conduit body, or fitting, and at intervals no greater than 4-1/2 feet. The exceptions include fished runs and short unsupported lengths where flexibility is needed after installation:

  • not over 3 ft for trade sizes 1/2 through 1-1/4;
  • 4 ft for 1-1/2 through 2;
  • 5 ft for 2-1/2 and larger;
  • luminaire whips up to 6 ft in accessible ceilings.

Bends: no more than 360 degrees total between pull points, the same limit as rigid raceways (348.26).

As an equipment grounding conductor (250.118(5)): listed FMC qualifies only when all of these are true:

  • it is terminated in listed fittings;
  • the circuit conductors are protected at 20 A or less;
  • the combined length of flexible metal conduit, flexible metallic tubing, and liquidtight flexible metal conduit in the same ground-fault return path is 6 ft or less;
  • it is not installed for flexibility after installation (to minimize vibration, for example). When flexibility is needed, a wire-type EGC is required.

Liquidtight flexible metal and nonmetallic conduit (Articles 350, 356)

  • LFMC is used where flexibility or protection from liquids, vapors, or solids is needed. It is not permitted where subject to physical damage. It is secured like FMC (12 inches and 4-1/2 feet, 350.30).
  • As an EGC (250.118(6)): listed fittings; trade sizes 3/8 through 1/2 protected at 20 A or less; trade sizes 3/4 through 1-1/4 at 60 A or less; combined flexible length 6 ft or less; and a wire EGC when flexibility after installation is required.
  • LFNC is not permitted where subject to physical damage. It is generally limited to 6-ft lengths, except where the article allows longer secured runs or a longer length is approved as essential for flexibility (356.12). LFNC never serves as an EGC; a wire-type EGC is pulled in.

Electrical nonmetallic tubing (Article 362)

  • Permitted: in buildings not over three floors above grade, exposed or concealed. In taller buildings it must be concealed in walls, floors, and ceilings behind a thermal barrier with at least a 15-minute finish rating (or where fully sprinklered, as the article allows). Also permitted in wet locations and encased in concrete with approved fittings (362.10).
  • Not permitted: in hazardous locations (except as permitted elsewhere), to support luminaires, where ambient temperatures exceed the tubing's listing, for direct burial, where exposed to direct sunlight unless identified for it, or where subject to physical damage (362.12).
  • Securing: within 3 ft of each box and at intervals of no more than 3 ft (362.30).

Auxiliary gutters and wireways (Articles 366, 376)

RuleSheet-metal auxiliary gutterMetal wireway
Maximum fill20% of interior cross section (366.22(A))20% of interior cross section (376.22(A))
When derating appliesOnly above 30 current-carrying conductorsOnly above 30 current-carrying conductors (376.22(B))
Splices and tapsNot over 75% of the area at that point (366.56)Not over 75% of the area at that point (376.56)
Other limitsMay not extend more than 30 ft beyond the equipment it supplements (366.12)Horizontal runs supported at each end and at intervals not over 5 ft (376.30)

Cable trays (Article 392)

A cable tray is a support system, not a raceway. Only the wiring methods listed in Table 392.10(A) may be installed in it. In industrial establishments where only qualified persons will service the installation, single conductors 1/0 AWG and larger and certain other methods are permitted (392.10(B)). Metal cable trays may serve as equipment grounding conductors under the conditions in 392.60. Ampacity comes from 392.80, which replaces Table 310.16 adjustments for many tray installations.

Specialty cables

CableKey rules (2020 NEC)
SE (service-entrance)Permitted for services and, inside a building, for branch circuits and feeders installed like NM under Part II of Article 334. Where installed in thermal insulation, ampacity is limited to the 60 degree C rating (338.10(B)(4)). Washington limits SE cable for service conductors inside buildings (Section 13.6).
USEUnderground service-entrance cable. Not permitted for interior wiring unless it is also listed as a building wire such as RHW-2 (338.12(B)).
UFPermitted underground (including direct burial per 300.5), and in wet, dry, or corrosive locations. Not permitted as service-entrance cable; in commercial garages, theaters, motion picture studios, storage battery rooms, hoistways, or hazardous locations; embedded in poured cement, concrete, or aggregate (except nonheating leads embedded in plaster as Article 424 permits); exposed to direct sunlight unless identified; or as overhead cable except with a messenger (340.12). Ampacity is limited to 60 degree C (340.80).
MI (mineral-insulated)Permitted for services, feeders, and branch circuits, wet or dry, exposed or concealed, underground, and in hazardous locations. Supported at intervals not over 6 ft (332.30). Ends are sealed against moisture because the magnesium oxide insulation absorbs water.

Article 300 rules that cut across every method

  • Corrosion (300.6): metal raceways and fittings must be protected against corrosion suitable for the environment.
  • Raceways between temperature zones (300.7(A)): where a raceway passes from a warm to a cold area (into a walk-in cooler, for example), seal it to prevent circulation of warm air and condensation.
  • Wet locations above grade (300.9): the interior of raceways in wet locations above grade is itself a wet location, so the conductors must be listed for wet locations (such as THWN-2).
  • Independent support (300.11): raceways, cables, and boxes must be securely fastened in place. Ceiling grid wires may support them only if the wires are identified for the purpose and installed per 300.11(B). Raceways generally may not support other raceways or cables; one exception lets Class 2 cables controlling equipment be supported by that equipment's power raceway.
  • Firestopping (300.21): penetrations of fire-resistance-rated walls, floors, and ceilings must be firestopped with approved methods that keep the fire rating.
  • Ducts and plenums (300.22):
    • (A) no wiring at all in ducts that carry dust, loose stock, or flammable vapors;
    • (B) in ducts built to carry environmental air, only limited metal methods: MI cable without a nonmetallic cover, smooth or corrugated impervious-sheath MC cable, and EMT, IMC, or RMC without a nonmetallic cover (flexible metal conduit only in short lengths for equipment connections);
    • (C) in other spaces used for environmental air (plenum ceilings), metal raceways, MI, MC, and AC cable without nonmetallic coverings, and cables specifically listed for plenum use.
Test Your Knowledge

A 30-ampere circuit to a rooftop unit is run in 4 feet of listed flexible metal conduit with listed fittings, and flexibility is not required after installation. Under NEC 250.118(5), may the FMC serve as the equipment grounding conductor?

A
B
C
D