6.3 Voltage Drop Calculations on Notification Appliance Circuits
Key Takeaways
- Voltage drop on Notification Appliance Circuits (NACs) is caused by copper conductor resistance over circuit distance (Vdrop = I × Rwire), reducing operating voltage available at appliances furthest from the power source.
- Under UL 1971 and UL 464, modern 'Regulated 24VDC' notification appliances (horns, strobes, sounders) must operate reliably within a certified input range of 16.0 VDC to 33.0 VDC.
- Code-compliant NAC voltage drop engineering mandates using the 'End of Useful Battery Life' supply voltage of 20.4 VDC (1.70 V/cell across 12 lead-acid cells), establishing a maximum allowable cumulative voltage drop of only 4.4 VDC (20.4V - 16.0V = 4.4V).
- Total conductor loop resistance must always account for both outgoing and return conductors, doubling the one-way distance: Rloop = 2 × Done-way × (Rtable / 1,000), referencing NEC Chapter 9 Table 8 solid uncoated copper values at 75°C (18 AWG = 7.77 Ω, 16 AWG = 4.89 Ω, 14 AWG = 3.07 Ω, 12 AWG = 1.93 Ω per 1,000 ft).
- The Lump-Sum (End-of-Line) method provides a fast, conservative calculation by assuming the entire circuit current is drawn at the furthest appliance, whereas the Point-by-Point method calculates incremental voltage drops across each individual segment, accurately modeling distributed loads and often allowing the use of 14 AWG where lump-sum would erroneously require 12 AWG.
6.3 Voltage Drop Calculations on Notification Appliance Circuits
Quick Answer: Voltage drop on Notification Appliance Circuits (NACs) occurs when wire resistance consumes electrical potential over distance according to Ohm's Law ($V_{\text{drop}} = I \times R_{\text{wire}}$). Under UL 1971 (visual) and UL 464 (audible), modern "Regulated 24VDC" appliances require a minimum of 16.0 VDC to operate. Fire alarm engineering standards and plan review authorities mandate that voltage drop calculations start from the 20.4 VDC "End of Useful Battery Life" baseline ($1.70\text{ V/cell}$ for 12 cells), establishing a maximum allowable cumulative voltage drop of only 4.4 VDC ($20.4\text{ V} - 16.0\text{ V} = 4.4\text{ V}$). Circuit wire resistance must always account for twice the one-way distance ($2 \times D$) using NEC Chapter 9, Table 8 solid uncoated copper resistance values at $75^\circ\text{C}$ (18 AWG = $7.77,\Omega$, 16 AWG = $4.89,\Omega$, 14 AWG = $3.07,\Omega$, 12 AWG = $1.93,\Omega$ per 1,000 ft). While the Lump-Sum method assumes all current is drawn at the furthest point, the Point-by-Point method models distributed loads segment-by-segment.
Why Voltage Drop Occurs in Notification Appliance Circuits
Notification Appliance Circuits (NACs) deliver electrical power to life-safety notification appliances—including strobes, horns, chimes, bells, and 520 Hz low-frequency sounders—distributed throughout a commercial facility. As current flows from the Fire Alarm Control Unit (FACU) or Remote Power Extender (SNAC panel) through copper conductors, the inherent electrical resistance of the wire opposes electron flow.
Under Ohm's Law ($V = I \times R$), this resistance causes electrical potential (voltage) to drop progressively along the circuit. The farther an appliance is located from the power supply, the lower its terminal operating voltage.
┌─────────────────────────────────────────────────────────────────────────────┐
│ VOLTAGE DROP IN NOTIFICATION CIRCUITS │
├─────────────────────────────────────────────────────────────────────────────┤
│ │
│ FACU Power Supply Outgoing Conductor Resistance (Rwire) │
│ ┌────────────────┐ ──────/\[ R1 ]/\──────/\[ R2 ]/\───────┐ │
│ │ 20.4 VDC │ ( + ) │ │
│ │ Battery Cutoff├────────────────┬──────────────┬──────────────┤ │
│ │ │ ▼ ▼ ▼ │
│ │ │ [Strobe 1] [Strobe 2] [Strobe 3] │
│ │ │ ( - ) 20.1 VDC 18.9 VDC 17.1 VDC │
│ │ ├────────────────┴──────────────┴──────────────┤ (EOLR) │
│ └────────────────┘ ──────/\[ R1 ]/\──────/\[ R2 ]/\───────┘ │
│ Return Conductor Resistance (Rwire) │
│ │
│ • Terminal voltage steadily decreases as distance increases. │
│ • Appliance 3 at end of line must receive ≥ 16.0 VDC to operate. │
└─────────────────────────────────────────────────────────────────────────────┘
The Life-Safety Consequences of Excessive Voltage Drop
If conductor resistance is too high or circuit current is excessive, the voltage reaching downstream appliances will collapse below their minimum operational threshold, causing life-safety system failures:
- Strobe Inoperability & Flash Misfires: Electronic visual strobes contain internal DC-to-DC step-up converters that charge high-voltage flash capacitors ($250\text{--}300\text{ VDC}$) to fire xenon flash tubes or high-output LEDs. If terminal voltage drops below 16.0VDC, the charging circuit stalls. The strobe may fail to fire entirely, flash at erratic intervals below the code-mandated 1 Hz (60 to 120 flashes per minute), or lose sync with adjacent appliances, creating seizure hazards.
- Acoustic Decibel Collapse: Horns and sounders subjected to low terminal voltage produce severely degraded sound pressure levels. A horn rated at $90\text{ dBA}$ at 24VDC may produce less than $75\text{ dBA}$ at 14VDC, failing the NFPA 72 requirement to provide at least $15\text{ dBA}$ above average ambient sound levels.
- Brownout of 520 Hz Low-Frequency Sounders: Sleeping area sounders required in commercial hotels, dormitories, and apartment complexes (Group R-1 and R-2) contain microprocessor-driven audio amplifiers to generate 520 Hz square-wave tones. Low terminal voltage causes internal brownout resets, causing the sounder to fall silent while building occupants sleep.
Appliance Operating Voltage Standards: UL 1971 & UL 464
All commercial notification appliances installed under NFPA 72 must be listed by an approved Nationally Recognized Testing Laboratory (NRTL) such as Underwriters Laboratories (UL). The governing standards are:
- UL 1971: Standard for Signaling Devices for the Hearing Impaired (Visual strobes).
- UL 464: Standard for Audible Signal Appliances (Horns, bells, chimes).
The "Regulated 24VDC" Standard
Under modern UL listings, notification appliances are categorized by their operating voltage profiles:
- Regulated 24VDC (or Regulated 24VDC / FWR): The appliance is certified to operate reliably across a continuous voltage envelope of 16.0 VDC to 33.0 VDC (spanning $-33.3%$ to $+37.5%$ of nominal 24V).
- Special Application: An appliance listed only for use with specific control units where the manufacturer has tested and verified compatibility within an engineered voltage range.
[!NOTE] In modern commercial installations, virtually all commercial horns and strobes are listed as Regulated 24VDC, establishing 16.0 VDC as the absolute minimum permissible terminal operating voltage at the furthest appliance under full load.
Source Voltage Selection: 20.4VDC Battery Cutoff vs. 24.0VDC Nominal
One of the most heavily tested engineering concepts on the Oklahoma licensing exam is selecting the proper initial power supply voltage for voltage drop calculations.
┌─────────────────────────────────────────────────────────────────────────────┐
│ INITIAL SUPPLY VOLTAGE BENCHMARKS │
├─────────────────────┬──────────────┬────────────────────────────────────────┤
│ Operating Condition │ Voltage │ Engineering Application / Status │
├─────────────────────┼──────────────┼────────────────────────────────────────┤
│ Charger Float │ 27.2–27.6 VDC│ Normal AC utility present; high float │
│ Nominal System │ 24.0 VDC │ Standard nameplate reference ONLY │
│ Battery Cutoff │ 20.4 VDC │ MANDATORY WORST-CASE DESIGN BASELINE │
│ UL Minimum Cutoff │ 16.0 VDC │ Minimum operational threshold │
└─────────────────────┴──────────────┴────────────────────────────────────────┘
Why 20.4 VDC Must Be Used for Code Compliance
When utility AC power fails during a fire, the fire alarm system runs exclusively on secondary storage batteries. Over a 24-hour power outage, the battery terminal voltage steadily decays along its chemical discharge curve.
Under NFPA 72 Section 10.6.7.2 and UL 864 standards, a 24-volt sealed lead-acid battery bank (12 cells in series) is considered fully discharged when its terminal voltage reaches 1.70 Volts per cell:
If a fire erupts at the 23rd hour and 55th minute of an AC power failure, the notification appliances must operate successfully from this depleted 20.4 VDC battery supply.
Calculating Maximum Allowable Voltage Drop
With a minimum starting voltage of 20.4 VDC and a minimum UL appliance operating threshold of 16.0 VDC, the maximum allowable cumulative voltage drop across any notification circuit is:
[!WARNING] Critical Exam Watchout: Designing a circuit based on nominal 24.0 VDC allows an apparent voltage drop of $24.0 - 16.0 = 8.0\text{ VDC}$. If an installer allows an 8.0V drop, terminal voltage on battery backup will be $20.4 - 8.0 = 12.4\text{ VDC}$—far below the 16.0V UL cutoff. The appliances will fail when life-safety evacuation is most critical! Plans submitted to the Oklahoma State Fire Marshal or municipal AHJs with voltage drop exceeding 4.4 VDC will be rejected.
NEC Chapter 9, Table 8 Conductor Resistance Values
To calculate circuit resistance, installers and designers must use the standardized direct current conductor properties codified in National Electrical Code (NEC) Chapter 9, Table 8 (Conductor Properties).
Under NEC Article 760, fire alarm conductors are solid or stranded uncoated copper. Resistance values must reflect the $75^\circ\text{C}$ ($167^\circ\text{F}$) thermal rating, accounting for elevated temperatures in building plenums, electrical raceways, and during fire conditions.
┌─────────────────────────────────────────────────────────────────────────────┐
│ NEC CHAPTER 9, TABLE 8: SOLID UNCOATED COPPER AT 75°C │
├──────────┬───────────────────────────────┬──────────────────────────────────┤
│ Size │ Resistance (Ohms / 1,000 ft) │ Loop Resistance (Ohms / 1,000 ft │
│ (AWG) │ Single Conductor │ of 2-Conductor Cable Pair) │
├──────────┼───────────────────────────────┼──────────────────────────────────┤
│ 18 AWG │ 7.77 Ω │ 15.54 Ω │
│ 16 AWG │ 4.89 Ω │ 9.78 Ω │
│ 14 AWG │ 3.07 Ω │ 6.14 Ω │
│ 12 AWG │ 1.93 Ω │ 3.86 Ω │
│ 10 AWG │ 1.21 Ω │ 2.42 Ω │
└──────────┴───────────────────────────────┴──────────────────────────────────┘
Key Physical Principles:
- Inverse Relationship: As the American Wire Gauge (AWG) number decreases, conductor diameter increases, and electrical resistance decreases. 12 AWG wire has less than one-fourth the resistance of 18 AWG wire.
- Stranded vs. Solid Conductor Resistance: Stranded conductors have approximately 2% higher resistance than solid conductors of identical gauge due to the helical lay length of individual strands. Unless explicitly stated otherwise, commercial fire alarm calculations use solid copper values.
The Loop Length Rule: Doubling One-Way Distance
An electrical circuit is a complete closed loop. Direct current leaves the positive terminal of the power supply, travels down the outgoing (positive) conductor to the appliances, and must travel back through the entire length of the return (negative) conductor to reach the power supply common ground.
Therefore, the total length of copper wire introducing resistance into the circuit is twice the one-way physical cable distance:
[!IMPORTANT] The #1 Mathematical Error: Forgetting to multiply one-way distance by 2 cuts calculated circuit resistance in half, leading installers to believe undersized wire will pass inspection. Always verify whether a distance given on an exam is "one-way distance" (which must be multiplied by 2) or "total loop length" (which is already doubled).
Calculation Methodologies: Lump-Sum vs. Point-by-Point
Two recognized mathematical methodologies are utilized in commercial fire alarm design to evaluate NAC voltage drop: the Lump-Sum (End-of-Line) Method and the Point-by-Point (Segmented) Method.
┌─────────────────────────────────────────────────────────────────────────────┐
│ LUMP-SUM VS. POINT-BY-POINT COMPARISON │
├──────────────────────┬─────────────────────────────┬────────────────────────┤
│ Parameter │ Lump-Sum (End-of-Line) │ Point-by-Point │
├──────────────────────┼─────────────────────────────┼────────────────────────┤
│ Engineering Model │ All load placed at furthest │ Load distributed at │
│ │ appliance at end of wire │ actual physical spacing│
│ Mathematical Effort │ 1-Step Calculation (Fast) │ Multi-Step Iteration │
│ Conservatism │ Highly Conservative │ Highly Accurate │
│ Practical Impact │ Often forces 12 AWG wire │ Often proves 14 AWG ok │
│ Calculation Formula │ Vdrop = Itotal × Rloop │ Vdrop = Σ(Iseg × Rseg) │
└──────────────────────┴─────────────────────────────┴────────────────────────┘
1. The Lump-Sum (End-of-Line) Method
- Methodology: Assumes that 100% of the total circuit current ($I_{\text{total}}$) travels through the entire length of the wire to the very last appliance at the end of the circuit.
- Formula:
- Engineering Context: In reality, appliances are tapped along the circuit; current decreases after each tap. Because the Lump-Sum method assumes all current travels the full distance, it heavily overestimates voltage drop. However, if a circuit passes using the Lump-Sum method, it is guaranteed to pass in the physical building.
2. The Point-by-Point (Segmented) Method
- Methodology: Divides the NAC into discrete physical segments between each adjacent appliance. The voltage drop across each segment is calculated using only the current flowing through that specific segment (which equals the sum of all downstream appliances):
- Segment 1 (Panel to Appliance 1): carries $I_{\text{total}}$.
- Segment 2 (Appliance 1 to Appliance 2): carries $I_{\text{total}} - I_{\text{appliance 1}}$.
- Segment $k$ (Appliance $k-1$ to Appliance $k$): carries downstream current only.
- Terminal Voltage: The voltage at any specific device is the source voltage minus the cumulative sum of voltage drops across all preceding upstream segments:
Comprehensive Worked Comparison Study: 1.5A Load over 600 Feet
To see how wire gauge selection and calculation methodology impact code compliance, consider this definitive engineering case study:
Design Parameters:
- Initial Source Voltage: 20.4 VDC (End of battery life)
- Minimum Allowable Operating Voltage: 16.0 VDC (UL 1971 / UL 464)
- Maximum Permissible Voltage Drop: 4.4 VDC ($20.4 - 16.0 = 4.4\text{ V}$)
- Total Connected Notification Load ($I$): 1.50 Amperes
- One-Way Cable Distance ($D$): 600 Feet
- Total Conductor Loop Length: $2 \times 600\text{ ft} = \mathbf{1,200\text{ Feet}}$
Part 1: Lump-Sum Evaluation Across 18, 16, 14, and 12 AWG
┌─────────────────────────────────────────────────────────────────────────────┐
│ LUMP-SUM WIRE GAUGE COMPARISON TABLE │
├────────┬────────────┬──────────────┬────────────┬──────────────┬────────────┤
│ Gauge │ Table 8 │ Loop Res. │ Lump-Sum │ Terminal │ Code │
│ (AWG) │ (Ω/1,000') │ (1,200 ft) │ Vdrop (V) │ Voltage (V) │ Compliance │
├────────┼────────────┼──────────────┼────────────┼──────────────┼────────────┤
│ 18 AWG │ 7.77 Ω │ 9.324 Ω │ 13.99 V │ 6.41 VDC │ FAILS (Bad)│
│ 16 AWG │ 4.89 Ω │ 5.868 Ω │ 8.80 V │ 11.60 VDC │ FAILS │
│ 14 AWG │ 3.07 Ω │ 3.684 Ω │ 5.53 V │ 14.87 VDC │ FAILS (LS) │
│ 12 AWG │ 1.93 Ω │ 2.316 Ω │ 3.47 V │ 16.93 VDC │ PASSES │
└────────┴────────────┴──────────────┴────────────┴──────────────┴────────────┘
Mathematical Derivations:
- 18 AWG Evaluation: Result: FAILS CATASTROPHICALLY. Strobe flash circuits completely shut down.
- 16 AWG Evaluation: Result: FAILS. Drop of 8.80V exceeds 4.4V limit; terminal voltage 11.60V is below 16.0V.
- 14 AWG Evaluation (Lump-Sum): Result: FAILS UNDER LUMP-SUM. The 5.53V drop exceeds the 4.4V limit.
- 12 AWG Evaluation (Lump-Sum): Result: PASSES COMPLIANTLY. Drop of 3.47V is within 4.4V limit; terminal voltage $16.93\text{ V} \ge 16.0\text{ V}$.
Part 2: Point-by-Point Demonstration — Why 14 AWG Actually Passes
Under Lump-Sum analysis, 14 AWG failed ($14.87\text{ V} < 16.0\text{ V}$). However, in reality, the 1.50A load is not lumped at the end of the wire. It consists of ten (10) strobes drawing $0.15\text{ A}$ (150 mA) each, evenly distributed every 60 feet along the 600-foot hallway.
Each 60-foot segment contains $120\text{ feet}$ of total loop wire ($2 \times 60\text{ ft} = 120\text{ ft} = 0.120\text{ kft}$). Using 14 AWG solid copper ($3.07,\Omega / 1,000\text{ ft}$):
┌─────────────────────────────────────────────────────────────────────────────┐
│ POINT-BY-POINT SEGMENTED VOLTAGE DROP (14 AWG) │
├─────┬──────────┬──────────┬──────────┬───────────┬─────────────┬────────────┤
│ Seg │ Length │ Current │ Res. │ Segment │ Cumulative │ Terminal │
│ No. │ (ft) │ Carried │ (Ω) │ Drop (V) │ Drop (V) │ Voltage │
├─────┼──────────┼──────────┼──────────┼───────────┼─────────────┼────────────┤
│ 1 │ 0–60' │ 1.50 A │ 0.3684 Ω │ 0.553 V │ 0.553 V │ 19.85 VDC │
│ 2 │ 60–120' │ 1.35 A │ 0.3684 Ω │ 0.497 V │ 1.050 V │ 19.35 VDC │
│ 3 │ 120–180' │ 1.20 A │ 0.3684 Ω │ 0.442 V │ 1.492 V │ 18.91 VDC │
│ 4 │ 180–240' │ 1.05 A │ 0.3684 Ω │ 0.387 V │ 1.879 V │ 18.52 VDC │
│ 5 │ 240–300' │ 0.90 A │ 0.3684 Ω │ 0.332 V │ 2.211 V │ 18.19 VDC │
│ 6 │ 300–360' │ 0.75 A │ 0.3684 Ω │ 0.276 V │ 2.487 V │ 17.91 VDC │
│ 7 │ 360–420' │ 0.60 A │ 0.3684 Ω │ 0.221 V │ 2.708 V │ 17.69 VDC │
│ 8 │ 420–480' │ 0.45 A │ 0.3684 Ω │ 0.166 V │ 2.874 V │ 17.53 VDC │
│ 9 │ 480–540' │ 0.30 A │ 0.3684 Ω │ 0.111 V │ 2.985 V │ 17.41 VDC │
│ 10 │ 540–600' │ 0.15 A │ 0.3684 Ω │ 0.055 V │ 3.040 V │ 17.36 VDC │
└─────┴──────────┴──────────┴──────────┴───────────┴─────────────┴────────────┘
Engineering Conclusion:
- Under Lump-Sum: Calculated drop was 5.53 V, predicting terminal voltage of 14.87 V (FAIL).
- Under Point-by-Point: Real physical drop is only 3.04 V, delivering 17.36 VDC at the 10th strobe.
- Because 17.36 VDC $\ge$ 16.0 VDC, the circuit PASSES FULL CODE COMPLIANCE using 14 AWG wire!
- Practical Value: Point-by-point calculations saved the contractor from pulling heavy, expensive 12 AWG cable through crowded 3/4-inch conduit, saving thousands of dollars in copper material and labor.
Maximum Permissible Distance Formulas & Design Guidelines
Installers frequently need to know the maximum distance a Notification Appliance Circuit can run before exceeding voltage drop limits. By rearranging Ohm's Law ($V = I \times R$) and solving for one-way distance ($D$):
Where:
- $V_{\text{drop, max}} = 4.4\text{ VDC}$ (Standard battery cutoff baseline).
- $I_{\text{total}} = \text{Total circuit current in Amperes}$.
- $R_{\text{table}} = \text{NEC Chapter 9 Table 8 resistance in Ohms per 1,000 ft}$.
┌─────────────────────────────────────────────────────────────────────────────┐
│ MAXIMUM ONE-WAY DISTANCES (LUMP-SUM) │
├──────────────┬──────────────┬──────────────┬──────────────┬─────────────────┤
│ Total Load │ 18 AWG │ 16 AWG │ 14 AWG │ 12 AWG │
│ (Amperes) │ (7.77 Ω/kft) │ (4.89 Ω/kft) │ (3.07 Ω/kft) │ (1.93 Ω/kft) │
├──────────────┼──────────────┼──────────────┼──────────────┼─────────────────┤
│ 0.50 A │ 566 ft │ 900 ft │ 1,433 ft │ 2,280 ft │
│ 1.00 A │ 283 ft │ 450 ft │ 717 ft │ 1,140 ft │
│ 1.50 A │ 189 ft │ 300 ft │ 478 ft │ 760 ft │
│ 2.00 A │ 142 ft │ 225 ft │ 358 ft │ 570 ft │
└──────────────┴──────────────┴──────────────┴──────────────┴─────────────────┤
│ Based on 4.4V max allowable drop (20.4V source to 16.0V minimum terminal). │
└─────────────────────────────────────────────────────────────────────────────┘
Practical Installation Methods to Mitigate Excessive Voltage Drop
When calculations indicate that voltage drop will exceed 4.4V, technicians have four standard engineering options:
- Increase Conductor Gauge: Upgrade from 16 AWG to 14 AWG or 12 AWG. (Remember: wire gauge cannot exceed terminal screw physical capacity on appliance bases, typically 12 AWG max).
- Center-Feed the Circuit ("T-Tapping" on Class B): Rather than connecting the home run to Appliance 1 at the far end of the building, run the home run to the physical center of the building and branch in both directions. While Class B circuits must remain continuous for supervision, center-feeding shortens the maximum distance from the supply to the furthest appliance.
- Split the Load into Multiple NACs: Divide a single 2.0A circuit into two independent 1.0A circuits. Halving the current ($I$) cuts voltage drop across the wire in half ($V = I \times R$).
- Install a Remote Notification Appliance Circuit Power Extender (SNAC Panel): Mount a dedicated UL 864 / UL 1481 remote booster power supply near the notification load. The main FACU triggers the booster via a control module or sync input, providing local 24VDC power with short home-run distances.
Exam Watchouts & Common Traps
[!IMPORTANT] Critical Exam Watchouts for Voltage Drop:
- Starting Voltage Trap: Never calculate voltage drop using 24.0 VDC unless the question explicitly commands you to use "nominal voltage." The standard code-compliant baseline is 20.4 VDC ($1.70\text{ V/cell}$ end-of-battery).
- The Factor of 2: If an exam question asks: "What is the voltage drop on a 400-foot run of 14 AWG wire carrying 1.2 A?" → Total wire length is $2 \times 400 = 800\text{ feet}$. Total resistance is $0.800 \times 3.07,\Omega = 2.456,\Omega$. Drop is $1.2\text{ A} \times 2.456,\Omega = 2.95\text{ V}$. Forgetting to double the distance yields $1.47\text{ V}$, which will be an enticing distractor choice!
- Wire Gauge Direction: In the AWG numbering system, a smaller gauge number indicates a physically thicker wire with lower resistance ($R$). 12 AWG wire has lower resistance than 14 AWG wire ($1.93,\Omega < 3.07,\Omega$).
- Lump-Sum vs. Point-by-Point Distinction: If a circuit fails the Lump-Sum test, do NOT assume the circuit is impossible. If loads are evenly distributed, recalculate using Point-by-Point before pulling heavier wire.
When calculating voltage drop for a regulated 24VDC Notification Appliance Circuit powered by standby batteries, what initial supply voltage and maximum allowable voltage drop must be utilized under standard life-safety engineering practices?
A fire alarm technician is calculating the loop resistance for a 500-foot one-way Notification Appliance Circuit run using 14 AWG solid uncoated copper wire. Using NEC Chapter 9 Table 8 (3.07 Ω per 1,000 feet), what is the total circuit loop resistance?
A 24VDC NAC with a total connected load of 1.20 A spans a one-way distance of 400 feet using 16 AWG solid copper wire (4.89 Ω per 1,000 ft). Using the Lump-Sum (End-of-Line) method and an initial supply voltage of 20.4 VDC, what is the voltage drop and resulting terminal voltage at the last device, and does it meet the UL minimum requirement?