11.3 Density/Area Design, Adjustments & Hose Streams
Key Takeaways
- For new occupancy-hazard spray systems, NFPA 13 (2022) Table 19.2.3.1.1 is the single-point density/area table (the successor to older 19.3.3.1.1 curve picking).
- Starting points: Light 0.10/1500; OH1 0.15/1500; OH2 0.20/1500; EH1 0.30/2500; EH2 0.40/2500 (gpm/ft² over ft²).
- Sprinkler-system demand before hose is density × design area: Light 150 gpm, OH1 225, OH2 300, EH1 750, EH2 1000 gpm.
- Table 19.2.3.1.2 combined hose-stream totals are 100 gpm (light), 250 gpm (ordinary), and 500 gpm (extra); durations are 30 min light, 60 or 90 ordinary, 90 or 120 extra.
- Quick-response wet light/ordinary systems may reduce design area 40 percent at a 10 ft ceiling down to 25 percent at 20 ft (Figure 19.2.3.2.3.1) when every listed condition is met, never below five sprinklers.
Density × area is the sprinkler demand, not the water-supply demand
For new occupancy-hazard spray-sprinkler systems, NFPA 13 (2022) abandoned “any point on the curve.” Table 19.2.3.1.1 (the 2022 successor to the older Table 19.3.3.1.1 / curve figure) gives two points per hazard. The everyday point is the smaller area and higher density. The 0.07/3000, 0.12/3000, 0.17/3000, 0.28/3000, and 0.38/3000 alternates apply when 19.2.3.1.5 requires the 3,000 ft² operation for unsprinklered combustible concealed-space adjacency—not as a free designer preference. Figure 19.2.3.1.1 curves remain for evaluation or modification of existing systems.
Independent OpenExamPrep material uses the 2022 table as exam memory, not as a claim of AHJ adoption in every city. If a jurisdiction still enforces 2019, the curves can return; the NICET reference listed for this guide is 2022.
| Hazard (Table 19.2.3.1.1) | Density (gpm/ft²) | Design area (ft²) | Sprinkler demand before hose (gpm) |
|---|---|---|---|
| Light | 0.10 | 1,500 | 0.10 × 1,500 = 150 |
| Ordinary Group 1 | 0.15 | 1,500 | 0.15 × 1,500 = 225 |
| Ordinary Group 2 | 0.20 | 1,500 | 0.20 × 1,500 = 300 |
| Extra Group 1 | 0.30 | 2,500 | 0.30 × 2,500 = 750 |
| Extra Group 2 | 0.40 | 2,500 | 0.40 × 2,500 = 1,000 |
That product is sprinklers only. Hose is a separate add.
Hose streams and duration (Table 19.2.3.1.2)
Table 19.2.3.1.2 still uses inside-hose choices of 0, 50, or 100 gpm and a total combined inside-plus-outside hose allowance of:
- Light: 100 gpm, duration 30 minutes
- Ordinary (Groups 1 and 2): 250 gpm, duration 60 or 90 minutes
- Extra (Groups 1 and 2): 500 gpm, duration 90 or 120 minutes
The lower duration in each ordinary/extra pair is permitted when waterflow-alarm and supervisory devices are electrically supervised and monitored at an approved, constantly attended location (19.2.3.1.3). Inside hose is not an automatic extra 100 gpm on top of the total; the total is 100, 250, or 500 gpm. If inside hose stations take 100 gpm, the outside remainder is 0 (light), 150 (ordinary), or 400 (extra) unless the stem states a different permitted split. Hose is added at the supply connection (where the fire department actually takes water), not pushed through the remote sprinklers.
Worked water-supply totals (sprinkler product + combined hose):
- Light: 150 + 100 = 250 gpm for 30 minutes
- OH1: 225 + 250 = 475 gpm for 60 or 90 minutes
- OH2: 300 + 250 = 550 gpm for 60 or 90 minutes
- EH1: 750 + 500 = 1,250 gpm for 90 or 120 minutes
- EH2: 1,000 + 500 = 1,500 gpm for 90 or 120 minutes
Storage ESFR and CMDA hose/duration rows live in Chapter 20 and are not these occupancy-hazard numbers. Do not import 250 gpm ESFR hose onto an extra-hazard office-shop calculation.
Quick-response area reduction — use the verified percents
19.2.3.2.3 / Figure 19.2.3.2.3.1 permit a design-area reduction without changing density when all of the following are true:
- Wet pipe system
- Light or ordinary hazard (not extra)
- Maximum ceiling height 20 ft
- No unprotected ceiling pockets exceeding 32 ft²
- No unprotected areas above cloud ceilings as allowed by 9.2.7
- The design area never uses fewer than five sprinklers (19.2.3.2.3.2)
On the figure, percent reduction y is 40 percent at a 10 ft (and lower) ceiling, 25 percent at 20 ft, and zero above 20 ft. Between 10 ft and 20 ft the straight line is y = −1.5h + 55 (h in feet). At 15 ft: y = −1.5(15) + 55 = 32.5 percent.
Worked QR, 10 ft wet ordinary, starting area 1,500 ft²: 40 percent of 1,500 = 600. Remaining design area = 1,500 − 600 = 900 ft². Density is unchanged. If the occupancy was OH2, sprinkler demand becomes 0.20 × 900 = 180 gpm before hose, not 300 gpm. Then add 250 gpm hose: 430 gpm at the supply. Quick-response sprinklers are not permitted for extra hazard or for occupancies with substantial flammable liquids or combustible dusts (19.2.3.2.2.2), so do not take a 40 percent extra-hazard cut.
Area increases that Level I must not forget
These increase area without changing density:
- Sloped ceilings exceeding 2 in 12: +30 percent (19.2.3.2.4) for the listed spray/CMSA cases
- Dry pipe and double-interlock preaction: +30 percent (19.2.3.2.5)
They compound on the originally selected area (19.2.3.2.8.1). Wet 1,500 ft² that is both dry-pipe and steeply sloped is not in one system at once, but a dry system on a steep slope is 1,500 × 1.3 × 1.3 = 2,535 ft². Dry alone is 1,500 × 1.3 = 1,950 ft².
High-temperature extra-hazard sprinklers may reduce area 25 percent, not below 2,000 ft² (19.2.3.2.6). K-11.2 or larger on extra-hazard Table 19.2.3.1.1 points may take the same 25 percent cut, not below 2,000 ft² (19.2.3.2.7). 2,500 × 0.75 = 1,875, which is below 2,000, so the floor is 2,000 ft², not 1,875.
Unsprinklered combustible concealed-space rules in 19.2.3.1.5, if they apply, are imposed after the other modifications (19.2.3.2.8.2) and can drive the 3,000 ft² alternate densities in Table 19.2.3.1.1.
Minimum remote-area width along the branch lines is 1.2 √A (28.2.4.2). For A = 1,500, √1,500 ≈ 38.73, and 1.2 × 38.73 ≈ 46.5 ft. For the 900 ft² QR area, √900 = 30, and 1.2 × 30 = 36 ft. Level I should recognize the formula; laying out every head is later work.
For a new ordinary hazard Group 2 spray system, NFPA 13 (2022) Table 19.2.3.1.1, what is the sprinkler-system demand before hose?
A wet ordinary-hazard system uses quick-response sprinklers throughout, the ceiling is 10 ft, and every 19.2.3.2.3 condition is met. Starting from 1,500 ft², what design area remains after the QR reduction?
Which combined hose-stream totals does NFPA 13 (2022) Table 19.2.3.1.2 assign to light, ordinary, and extra hazard occupancy-hazard systems?