6.2 Extra Hazard Groups 1 & 2 and Storage Overview

Key Takeaways

  • EH1 (4.3.4 / 3.3.141.1) is very high quantity and combustibility, or dust/lint with rapidly developing high-heat-release fires, but little or no flammable or combustible liquid.
  • EH2 (4.3.5 / 3.3.141.2) is very high combustibles, substantial flammable or combustible liquids, or extensive shielding of combustibles.
  • Opened EH1 annex examples include saw mills, die casting, combustible hydraulic-fluid use areas, plywood/particleboard manufacturing, and upholstering with plastic foams; opened EH2 examples include flammable-liquid spraying and flow coating.
  • Miscellaneous storage (4.3.1.4) is capped at 12 ft high, 10 percent of building area or 4,000 ft² whichever is greater, 1,000 ft² per pile, and 25 ft pile separation — beyond that, 4.3.6 sends the job to Chapters 20–25.
  • Level I identifies when a job has left simple occupancy-hazard layout; commodity class, high-piled arrays, ESFR, and in-rack design are Level II/III work, not a Level I ESFR chapter.
Last updated: September 2026

Extra Hazard is still an occupancy class, not a warehouse class

Extra Hazard sits on the same 4.3 occupancy-hazard ladder as Light and Ordinary. It is for process and contents that will outrun an ordinary-hazard spray layout. It is not a synonym for "warehouse" and it is not a substitute for the storage chapters. A saw mill with airborne dust can be Extra Hazard Group 1 while the mill's separate finished-goods racks, if they fail the miscellaneous-storage tests, are a Chapter 20–25 problem.

Riser-area limits tighten here: 4.4.1 allows 40,000 ft² (3,720 m²) on one extra-hazard riser, not the 52,000 ft² used for light and ordinary hazard. 4.4.3 says that when one system protects extra hazard (or high-piled storage) plus ordinary or light hazard, the extra-hazard or storage coverage cannot exceed its own floor-area cap, and the total still cannot exceed the lesser-hazard cap. A Level I layout that dumps an EH process room and three office floors onto one riser without checking 4.4.3 is already a failed sheet.

Extra Hazard Group 1 (4.3.4 / 3.3.141.1)

EH1 protects occupancies or portions of other occupancies where quantity and combustibility are very high, or dust, lint, or other materials introduce rapidly developing fires with high heat-release rates, but with little or no combustible or flammable liquids.

Section 4.3.4 restates the body test as (1) spaces with very high quantity and combustibility of contents and (2) spaces where dust, lint, or other materials introduce rapidly developing fires.

Opened annex examples (2019 A.4.3.5 roster, the EH1 example list in extracts) include uses similar to: aircraft hangars except as governed by NFPA 409; combustible hydraulic-fluid use areas; die casting; metal extruding; plywood and particleboard manufacturing; printing using inks with flash points below 100°F (38°C); rubber reclaiming, compounding, drying, milling, and vulcanizing; saw mills; textile picking, opening, blending, garnetting, or carding of cotton, synthetics, wool shoddy, or burlap; and upholstering with plastic foams.

The trainee error is to see hydraulic oil and jump to EH2. The EH1 annex explicitly lists combustible hydraulic-fluid use areas. EH2 is for moderate to substantial amounts of flammable or combustible liquids as a characterizing occupancy, or extensive shielding — spraying, flow coating, dipping — not every gallon of hydraulic oil in a machine base. Classify the process you are looking at.

Worked case: a die-cast cell has molten metal, oily dies, and no spray booth. That matches the EH1 annex (die casting) and the "little or no flammable liquid" half of 3.3.141.1. A second room on the same drawing is a listed paint-spray booth. That second room is an EH2 annex use (flammable liquids spraying). Two extra-hazard groups can exist in one plant. Label each room. Do not average them into "extra hazard" on the cover sheet.

Extra Hazard Group 2 (4.3.5 / 3.3.141.2)

EH2 is occupancies or portions of other occupancies with moderate to substantial amounts of flammable or combustible liquids, or occupancies where shielding of combustibles is extensive. Section 4.3.5 lists (1) very high quantity and combustibility, (2) substantial combustible or flammable liquids, and (3) extensive shielding of combustibles.

Opened annex examples (2019 A.4.3.6 start of the EH2 list) include asphalt saturating, flammable liquids spraying, flow coating, and manufactured-home or modular-building assemblies where a finished enclosure is present. Do not invent later list items that were not in the opened extract. If the process is solvent extracting or varnish dipping and you have not confirmed it on the adopted annex page, classify from the body definition (substantial liquids or shielding) and flag the designer — do not guess an annex bullet.

Shielding matters on layout even when the liquid quantity looks modest. A flow-coating line with product hung so tightly that spray discharge cannot reach the fuel package is an EH2 shielding problem, not an OH2 machine shop with a drum in the corner.

Storage overview for Level I — know when you have left "simple layout"

4.3.1.3 sends commodity classification and storage arrangements for miscellaneous and low-piled storage to Sections 20.3 through 20.5. Definition 3.3.37 says a commodity is the combination of product, packing material, and container. Level I does not need to memorize every Class I–IV and Group A plastic figure. Level I does need to recognize that a cardboard carton on a plastic pallet is not "the product only."

Miscellaneous storage (4.3.1.4) — all of these must be true:

  • Height not more than 12 ft (3.7 m) (4.3.1.4.1).
  • Not more than 10 percent of the building area or 4,000 ft² (370 m²) of the sprinklered area, whichever is greater (4.3.1.4.2).
  • Not more than 1,000 ft² (93 m²) in one pile or area (4.3.1.4.3).
  • At least 25 ft (7.6 m) from other storage piles or areas (4.3.1.4.4).

Low-piled storage (4.3.1.5) caps Class I through Class IV at 12 ft (3.7 m) and Group A plastics at 5 ft (1.5 m). Miscellaneous tire storage has its own 2,000 ft² (185 m²) cap (4.3.1.6.1).

Protection for those limited arrays is selected from Table 4.3.1.7.1.1 and 19.2.3.1.1, with a 3,000 ft² (280 m²) maximum design area for miscellaneous storage (4.3.1.7.1.3). In-rack sprinklers, when required, go to Chapter 25 (4.3.1.8).

4.3.6 High-Piled Storage. Storage that does not meet 4.3.1.4 through 4.3.1.8 shall be protected in accordance with Chapters 20 through 25. That sentence is the Level I off-ramp. Early-suppression fast-response (ESFR) sprinklers, control-mode special application (CMSA) sprinklers, in-rack schemes, and commodity-by-arrangement figures live in those chapters. They are not occupancy-hazard density/area in 4.3.2–4.3.5.

4.3.7 sends special occupancy hazards to Chapter 27 (a hangar already pointing at NFPA 409 is the classic example). Do not force a Chapter 27 occupancy onto an EH1 annex label just because the annex mentioned hangars "except as governed by NFPA 409."

When the job leaves Level I "simple layout"

Escalate to the designer of record or a Level II/III layout technician when any of these appear:

  • Rack storage, solid shelves, or flue-space questions.
  • Storage higher than the 4.3.1 miscellaneous/low-piled height caps, or plastics above 5 ft.
  • Piles that fail the 10 percent / 4,000 ft² / 1,000 ft² / 25 ft tests.
  • A request for ESFR, CMSA, or in-rack sprinklers.
  • Encapsulation, open-top containers, or mixed commodities on one pallet.
  • A process that looks like EH2 liquid operations but also has high-piled packaged goods in the same volume.

A Level I trainee who sketches an ESFR grid because a warehouse "looks extra hazard" has left Task 1.5.1. Extra Hazard is an occupancy class. High-piled storage is a different design method. Flag it; do not invent it.

Path2022 hookLevel I action
EH1 process4.3.4 / 3.3.141.1; saw mill, die cast, hydraulic-fluid use, little liquidLabel the room EH1; keep liquids/spray rooms separate
EH2 process4.3.5 / 3.3.141.2; spraying, flow coating, substantial liquids or shieldingLabel the room EH2; do not borrow OH2 machine-shop spacing
Miscellaneous / low-piled4.3.1.4–4.3.1.8; Table 4.3.1.7.1.1Confirm height, area, pile, and separation; then occupancy-style criteria
High-piled / special4.3.6 Chapters 20–25; 4.3.7 Chapter 27Stop occupancy-hazard layout; get Level II/III or Chapter 27 help
Test Your Knowledge

A millwork plant has a saw-mill floor with airborne wood dust and no flammable-liquid process, plus a separate listed spray booth used for solvent-based finish. How should those two rooms be classified under NFPA 13 (2022)?

A
B
C
D
Test Your Knowledge

An otherwise Light Hazard clinic wants to store boxed supplies in one room. The pile is 11 ft high, occupies 1,200 ft², is the only storage in a 20,000 ft² sprinklered floor, and sits 30 ft from any other storage. Which miscellaneous-storage limit in NFPA 13 (2022) 4.3.1.4 has already been broken?

A
B
C
D
Test Your Knowledge

A 24 ft high rack-storage warehouse of cartoned commodities fails every miscellaneous and low-piled test in 4.3.1.4 through 4.3.1.8. The owner asks the Level I technician to "just use Extra Hazard Group 1 density like a saw mill." What is the correct 2022 response?

A
B
C
D