11.1 IEEE C37.2 Device Function Numbers, IEEE 315 Symbols, and NEMA Ratings

Key Takeaways

  • Level II task 2.4.1 requires recognizing and interpreting IEEE electrical device function numbers and NEMA ratings, citing IEEE C37.2 Sections 3 and 4, IEEE 315, and NEMA ICS 19.
  • The 2026 Level II outline restates this as task 2.3.3, identify the most common IEEE and ANSI electrical device function numbers.
  • Suffix letters qualify a device number: 87T is transformer differential, 87B bus differential, 51N neutral time overcurrent, 51G ground time overcurrent.
  • NEMA enclosure types describe environmental protection, and Type 3R is rain-tight outdoor while Type 4X adds corrosion resistance and hose-directed water.
  • NEMA and IEC contactor ratings are not interchangeable: NEMA sizes are conservative fixed steps while IEC ratings are matched precisely to a duty category.
Last updated: August 2026

IEEE C37.2 Device Function Numbers, IEEE 315 Symbols, and NEMA Ratings

Quick Answer: Level II task 2.4.1 requires the technician to "recognize and interpret IEEE electrical device function numbers and NEMA ratings," citing IEEE C37.2 Sections 3 and 4, IEEE 315, NEMA ICS 19, and NFPA 70B Annexes F and G. The 2026 outline restates it as Level II task 2.3.3, "Identify the most common IEEE/ANSI electrical device function numbers." This is vocabulary, it is directly testable, and it is worth points that require no equipment access at all.


1. The device function numbers

IEEE C37.2 assigns a number to a device function so that a drawing produced anywhere is readable everywhere. The numbers you must know:

No.FunctionNotes
21DistanceImpedance-based; line and backup protection
24Volts per hertzOverexcitation protection for transformers and generators
25Synchronizing / synchronism checkPermits closing only when two sources are in step
27Undervoltage
32Directional powerReverse power on generators
37Undercurrent or underpowerLoss of load, pump run-dry
40Loss of field / loss of excitationGenerators
46Reverse phase or phase balance currentDetects unbalance and single-phasing
47Phase sequence / phase balance voltage
49Thermal (machine or transformer)Thermal replica
50Instantaneous overcurrentNo intentional delay
51AC time overcurrentInverse time delay
52AC circuit breakerThe breaker itself
55Power factor
59Overvoltage
60Voltage or current balanceBlown fuse detection on VT circuits
62Time delay stopping or openingTimer
63Pressure switchTransformer sudden pressure relay
64Ground detector
67AC directional overcurrentOvercurrent qualified by direction
68Blocking
74Alarm
79AC reclosingAutomatic reclosing after a trip
81FrequencyOver and under, and rate of change
86Lockout relayLatching; must be manually reset
87DifferentialCompares current in versus current out
94Tripping or trip-freeAuxiliary tripping relay

Suffix letters qualify the number, and the exam tests the combinations:

CombinationMeaning
87TTransformer differential
87BBus differential
87GGenerator differential
87LLine differential
51NNeutral time overcurrent — from the residual of three phase CTs
51GGround time overcurrent — from a dedicated ground or window CT
50/51Combined instantaneous and time overcurrent in one device
52aBreaker auxiliary contact that follows the breaker — closed when the breaker is closed
52bBreaker auxiliary contact that is opposite the breaker — closed when the breaker is open

52a and 52b are worth memorizing exactly, because they appear in every control schematic. Mnemonic: a = "as the breaker" (same state); b = "backwards" (opposite state). A trip coil circuit is supervised by a 52a contact so the coil is only energized while the breaker is actually closed; a close coil circuit is supervised by a 52b so it can only operate when the breaker is open.

Device 86, the lockout relay, is the other one that decides questions. It is a hand-reset latching device: once operated it stays operated, and the breaker cannot be reclosed until someone physically resets it. That is deliberate — an 86 operates for faults serious enough that a human should look at the equipment before it goes back into service, such as transformer differential or sudden pressure.

2. IEEE 315 symbols

IEEE 315 (with ANSI Y32.9) defines the graphic symbols. Conventions that matter most:

  • Contacts are always shown de-energized and un-actuated. A normally-closed contact is drawn closed on the schematic even though it will be open in normal operation once its coil is energized. This convention catches candidates constantly.
  • Transformer windings are drawn as delta or wye, with the wye neutral shown grounded, resistance-grounded, reactance-grounded, or floating — each a distinct symbol carrying real information about the system.
  • Polarity marks on instrument transformers indicate the instantaneous current direction relationship and are essential for differential and directional schemes.
  • Ground symbols distinguish earth ground, equipment ground, and chassis or signal common.

3. NEMA enclosure types

NEMA 250 classifies enclosures by the environment they protect against. The types a testing technician meets:

TypeLocationProtects against
1IndoorIncidental contact, falling dirt
3ROutdoorRain, sleet, snow; rain-tight, with drainage provisions
3OutdoorRain, sleet, windblown dust; external ice formation
4Indoor/outdoorHose-directed water, splashing water, windblown dust
4XIndoor/outdoorEverything Type 4 covers plus corrosion
7Indoor hazardousClass I, Groups A-D — explosion-proof
9Indoor hazardousClass II — combustible dust
12Indoor industrialDust, falling dirt, dripping non-corrosive liquids

The pairs that get confused: 3R is rain-tight, 4 is water-tight. 3R keeps out falling rain and has weep holes to drain what does get in; Type 4 withstands a directed hose stream. 4X adds corrosion resistance — the X is the corrosion qualifier and matters in coastal, chemical, and wash-down environments. Type 7 and 9 are the hazardous location enclosures, and their construction is entirely different: they are built to contain an internal explosion and cool the escaping gases below the ignition temperature of the surrounding atmosphere, not to keep the atmosphere out.

The field consequence for a testing technician: re-installing a cover with a damaged or omitted gasket, or leaving a conduit hub unsealed, downgrades the enclosure rating. On a Type 7 enclosure it defeats the explosion containment entirely. Restoring the enclosure to its rated condition is part of completing the work, and it belongs on the checklist.

4. NEMA versus IEC control equipment

Both rate contactors and starters, and they are not interchangeable.

NEMA (ICS 2)IEC (60947)
BasisFixed sizes (00, 0, 1, 2, 3, 4, 5…)Rated to a specific utilization category and duty
Sizing philosophyConservative; one size covers a horsepower range with marginPrecise; matched to the actual application
Physical sizeLarger for the same horsepowerSmaller and lighter
Application flexibilityInterchangeable across a rangeMust match the duty category
Electrical lifeGenerally longer at a given ratingShorter unless a higher category is selected

Utilization categories in IEC — AC-1 for non-inductive loads, AC-3 for squirrel-cage motor starting with breaking at running speed, AC-4 for plugging and inching duty — are the key. A contactor perfectly adequate as AC-3 may be badly undersized for AC-4 service, because AC-4 requires interrupting locked-rotor current repeatedly. The field consequence is the classic one: an IEC contactor replaced with "the same amp rating" from a different category fails prematurely, and the diagnosis is a selection error rather than a defective component.

NEMA's conservatism means a NEMA Size 2 starter will do the job for anything within its horsepower band without further analysis. That is why NEMA equipment dominates US industrial installations where maintainability and interchangeability matter more than panel space.

5. Reading a nameplate

The 2026 Level II outline makes 2.3.1, "Recognize nameplate data," its own task. What to capture, by apparatus:

  • Transformer: kVA (all cooling stages), primary and secondary voltage, percent impedance, connection and vector group, cooling class (ONAN/ONAF/ODAF), temperature rise, BIL, tap voltages, liquid type and volume, serial number.
  • Circuit breaker: frame size, continuous current, interrupting rating at each voltage, voltage rating, BIL, control voltage, operation counter reading, serial number.
  • Motor: horsepower, voltage, full-load amperes, service factor, insulation class, temperature rise, frame, RPM, code letter, design letter, duty, enclosure.
  • CT: ratio (and all taps on a multi-ratio unit), accuracy class and burden (metering and relaying classes differ), thermal and mechanical rating factor, polarity marking.
  • Arrester: MCOV, duty-cycle rating, class.

Photograph nameplates rather than only transcribing them. A transposed digit in a percent impedance propagates into the short-circuit study, the coordination study, and the arc flash labels.

Exam trap: A schematic shows a contact labelled 52b in a circuit and the question asks its state while the breaker is closed. A 52b contact is opposite the breaker, so with the breaker closed the 52b contact is open. Candidates who reverse a and b get every close-circuit and trip-circuit question wrong.

Test Your Knowledge

On a control schematic, what is the state of a 52b auxiliary contact while the circuit breaker is closed?

A
B
C
D
Test Your Knowledge

What distinguishes a NEMA Type 4X enclosure from a NEMA Type 3R?

A
B
C
D
Test Your Knowledge

What does the device designation 87T on a protection drawing indicate?

A
B
C
D