12.3 Electrical Loads & Power Factor

Key Takeaways

  • Resistive loads (electric strip heaters, crankcase heaters) maintain voltage and current perfectly in phase (0 deg phase angle), operating at unity power factor (PF = 1.0) where true power equals apparent power (Watts = VA).
  • Inductive loads (compressor and fan motor windings, relay and contactor coils, solenoid valves) produce magnetic fields that induce Counter-Electromotive Force (CEMF), causing current to lag voltage by up to 90 deg ('ELI') and dropping power factor below 1.0.
  • Capacitive loads (motor run and start capacitors) store electrostatic energy across dielectric plates, causing current to lead voltage by up to 90 deg ('ICE'); run capacitors counteract inductive reactance in PSC motors to improve overall power factor.
  • The Power Triangle defines the relationship between Apparent Power (S in VA), True Power (P in Watts), and Reactive Power (Q in VAR); Power Factor is the ratio of true power to apparent power (PF = Watts / VA = cos theta).
  • Electric motors draw momentary Locked Rotor Amps (LRA)—typically 4 to 6 times continuous Full Load Amps (FLA) or Rated Load Amps (RLA)—for 0.5 to 2.0 seconds until rotor rotation establishes CEMF to restrict running current.
Last updated: September 2026

12.3 Electrical Loads & Power Factor

The Three Classifications of HVAC Electrical Loads

Every electrical load in an HVAC/R system converts electrical energy into another form of energy—thermal, mechanical, magnetic, or electrostatic. In alternating current circuits, electrical loads behave in three fundamentally different ways based on how they alter the phase relationship between alternating voltage and alternating current.

AC Waveform Phase Relationships Across Load Types:
=========================================================================
1. RESISTIVE LOAD (In Phase - PF = 1.0)
   Voltage: [ + ] ---/\--- [ - ] ---/\---  Voltage & Current rise, fall,
   Current: [ + ] ---/\--- [ - ] ---/\---  and cross zero simultaneously!

2. INDUCTIVE LOAD ("ELI" - Current Lags Voltage by Phase Angle Theta)
   Voltage: [ + ] ---/\------- [ - ] ---/\---  Voltage peaks FIRST;
   Current:      [ + ] ---/\------- [ - ] ---/\---  Current LAGS behind.

3. CAPACITIVE LOAD ("ICE" - Current Leads Voltage by Phase Angle Theta)
   Current: [ + ] ---/\------- [ - ] ---/\---  Current peaks FIRST;
   Voltage:      [ + ] ---/\------- [ - ] ---/\---  Voltage LAGS behind.
=========================================================================

1. Resistive Loads (Pure Resistance & Unity Power Factor)

Resistive loads consist of electrical conductors designed to oppose current flow and convert electrical energy directly into thermal heat through Joule dissipation ($P = I^2 \times R$).

  • Phase Relationship: In a purely resistive circuit, the voltage and current waveforms are completely in phase with one another. The phase angle ($\theta$) is exactly $0^\circ$. The current wave reaches its positive peak, crosses zero, and reaches its negative peak at the exact same microsecond as the voltage wave.
  • Power Factor: The cosine of $0^\circ$ is $1.0$. Therefore, resistive loads operate at unity power factor ($ ext{PF} = 1.0$).
  • True vs. Apparent Power: All electrical energy supplied to a resistive load is converted into real heat work. True Power (in Watts) equals Apparent Power (in Volt-Amps): Watts=Volt-Amperes(P=S)\text{Watts} = \text{Volt-Amperes} \quad (P = S)
  • HVAC Examples: Electric resistance duct heater packages (nichrome wire coils), crankcase belly-band heaters, heat pump defrost pan heaters, and domestic water heater elements.

2. Inductive Loads (CEMF & Lagging Current)

Inductive loads consist of coiled wire wound around a magnetic iron core. When alternating current flows through the coil, it generates an expanding and collapsing magnetic field. This shifting magnetic field cuts across adjacent turns of the same coil, inducing an opposing internal voltage called Counter-Electromotive Force (CEMF) or back-EMF, as governed by Lenz's Law.

  • Phase Relationship: Because the induced CEMF actively fights the rise and fall of current, current lags behind voltage by a phase angle of up to $90^\circ$.
  • The "ELI" Mnemonic: Technicians use the classic mnemonic "ELI the ICE man" to remember inductive phase relationships:
    • In an inductive circuit (L), Voltage (E) leads Current (I)—written E - L - I.
  • Power Factor: Because the current and voltage peaks do not coincide, inductive loads operate at a lagging power factor strictly less than $1.0$ (typically $0.70\text{ to }0.85$ in uncorrected single-phase induction motors).
  • Energy Behavior: Inductive loads absorb electrical energy from the utility during one portion of the AC cycle to establish their magnetic fields, and then discharge that magnetic energy back into the power lines as the cycle reverses. This sloshing magnetic energy performs no useful mechanical work.
  • HVAC Examples: Hermetic compressor motor windings, condenser fan motors, indoor blower motors, contactor and relay coils, and solenoid valves.

3. Capacitive Loads (Electrostatic Storage & Leading Current)

Capacitive loads consist of two conductive aluminum plates separated by an insulating dielectric material (such as paper impregnated with dielectric oil or metalized polypropylene film). Capacitors store electrical energy in an electrostatic field between the plates.

  • Phase Relationship: When AC voltage is applied, maximum current flows into the capacitor plates initially when the plates are completely discharged (voltage is zero). As the plates charge up, the voltage across them rises, choking off current flow. Consequently, current leads voltage by up to $90^\circ$.
  • The "ICE" Mnemonic: From "ELI the ICE man":
    • In a capacitive circuit (C), Current (I) leads Voltage (E)—written I - C - E.
  • HVAC Examples: Motor run capacitors (oil-filled, oval or round metal cans) and motor start capacitors (dry electrolytic, black phenolic plastic shells).
Load TypePrimary Energy ConversionPhase RelationshipPower Factor (PF)Primary HVAC Examples
ResistiveElectrical to Thermal (Heat)Current and Voltage are in phase ($\theta = 0^\circ$)Unity ($ ext{PF} = 1.0$)Duct heat strips, crankcase heaters, defrost heaters.
InductiveElectrical to Magnetic / MechanicalCurrent lags Voltage by angle $\theta$ ("ELI")Lagging ($ ext{PF} < 1.0$, typically $0.70-0.85$)Compressor motors, fan motors, contactor coils, solenoids.
CapacitiveElectrical to Electrostatic FieldCurrent leads Voltage by angle $\theta$ ("ICE")Leading ($ ext{PF} < 1.0$, cancels inductive lag)Motor run capacitors, motor start capacitors.

The Power Triangle: Apparent, True & Reactive Power

In alternating current circuits containing both resistance and inductance (such as an electric motor with copper wire resistance and stator magnetic inductance), power must be analyzed using vector mathematics known as the Power Triangle.

The AC Power Triangle:
=========================================================================
             /| 
            / | 
           /  | 
Apparent  /   |  Reactive Power (Q)
Power (S)/    |  Measured in Volt-Amperes Reactive (VAR)
 measured/     |  (Non-working magnetic energy)
in VA   /      | 
       /       | 
      / Theta  | 
     +---------+ 
     True / Real Power (P)
     Measured in Watts (W)
     (Actual work performed / heat dissipated)
=========================================================================
Mathematical Relationships:
  S^2 = P^2 + Q^2  ===>  S = sqrt(P^2 + Q^2)
  Power Factor (PF) = cos(Theta) = True Power / Apparent Power = Watts / VA
  True Power (P) = E * I * PF = E * I * cos(Theta)
=========================================================================

1. Apparent Power ($S$)

Apparent Power is the total power that appears to be supplied to the circuit by the electric utility, calculated simply as the product of measured line voltage and measured line current: S=E×IS = E \times I

  • Apparent power is measured in Volt-Amperes (VA) or Kilovolt-Amperes (kVA).
  • It represents the total capacity that utility generators, transformers, and distribution wires must support to deliver current to the equipment.

2. True / Real Power ($P$)

True Power (also called Real or Active Power) is the actual rate at which electrical energy is converted into useful mechanical work (shaft rotation) or dissipated as heat: P=E×I×PF=E×I×cos(θ)P = E \times I \times \text{PF} = E \times I \times \cos(\theta)

  • True power is measured in Watts (W) or Kilowatts (kW).
  • This is the power registered by utility revenue meters and billed to the customer as kilowatt-hours (kWh).

3. Reactive Power ($Q$)

Reactive Power (often called "phantom power" or "wattless power") is the power required to establish and sustain the alternating magnetic fields inside inductive coils: Q=E×I×sin(θ)Q = E \times I \times \sin(\theta)

  • Reactive power is measured in Volt-Amperes Reactive (VAR) or kVAR.
  • Reactive power performs zero real work. It sloshes continuously back and forth between the utility generator and the motor windings twice every AC cycle.

Power Factor (PF) Definition & Calculation

Power Factor is mathematically defined as the ratio of True Power to Apparent Power, which equals the cosine of the phase angle ($\theta$) between voltage and current:

Power Factor (PF)=True Power (Watts)Apparent Power (Volt-Amps)=PS=cos(θ)\text{Power Factor (PF)} = \frac{\text{True Power (Watts)}}{\text{Apparent Power (Volt-Amps)}} = \frac{P}{S} = \cos(\theta)

Worked Field Problem: Calculating Motor Power Factor

A service technician tests a $240\text{ VAC}$ single-phase condensing unit compressor. A clamp-on ammeter reads $15.0\text{ A}$, and an electronic wattmeter measures a true power consumption of $2,880\text{ W}$.

  1. Calculate the Apparent Power ($S$): S=E×I=240 V×15.0 A=3,600 VAS = E \times I = 240\text{ V} \times 15.0\text{ A} = 3,600\text{ VA}
  2. Calculate the Power Factor ($ ext{PF}$): PF=True PowerApparent Power=2,880 W3,600 VA=0.80(80% lagging)\text{PF} = \frac{\text{True Power}}{\text{Apparent Power}} = \frac{2,880\text{ W}}{3,600\text{ VA}} = 0.80 \quad (80\% \text{ lagging})
  3. Calculate the Reactive Power ($Q$): Q=S2P2=3,60022,8802=12,960,0008,294,400=4,665,600=2,160 VARQ = \sqrt{S^2 - P^2} = \sqrt{3,600^2 - 2,880^2} = \sqrt{12,960,000 - 8,294,400} = \sqrt{4,665,600} = 2,160\text{ VAR}

Field Consequences of Low Power Factor & Correction Methods

Operating equipment with a low power factor ($<0.85$) produces severe detrimental consequences throughout the electrical distribution infrastructure:

  1. Excessive Line Current: To deliver a required amount of true mechanical work ($P$), a low power factor forces the utility line to carry significantly higher amperage ($I = P / [E \times \text{PF}]$). High current requires larger wire sizes, larger disconnect switches, and larger circuit breakers.
  2. Increased $I^2 R$ Conductor Heat Losses: Higher amperage flowing through building branch wiring increases resistive heating in conductors, wasting energy before it ever reaches the motor.
  3. Line Voltage Drop: High line current creates excessive voltage drops across supply wires ($V_{\text{drop}} = I \times R_{\text{wire}}$), resulting in depressed voltage at the compressor terminals during startup and running.
  4. Commercial Utility Surcharges: Electric utility companies penalize commercial and industrial customers whose overall facility power factor falls below $0.90$ or $0.95$, imposing substantial monthly billing penalties.

Power Factor Correction via Permanent Split Capacitor (PSC) Run Capacitors

In HVAC equipment, single-phase motors utilize run capacitors to achieve natural power factor correction:

  • An induction motor stator winding is heavily inductive, drawing lagging reactive current ($+90^\circ$ current lag).
  • A run capacitor connected in series with the motor's auxiliary start winding is capacitive, drawing leading reactive current ($-90^\circ$ current lead).
  • Because capacitive VARs and inductive VARs are exactly $180^\circ$ out of phase with one another, they cancel each other out vectorially: Qnet=QinductiveQcapacitiveQ_{\text{net}} = Q_{\text{inductive}} - Q_{\text{capacitive}}
  • When properly sized, the run capacitor supplies the magnetizing VARs needed by the motor locally. The electric utility no longer has to supply this reactive current from the power plant. As a result, the motor's overall power factor increases from roughly $0.70$ up to $0.90\text{ or }0.95$, and the total line current drawn by the motor drops significantly.

Momentary Inrush vs. Continuous Running Loads

When evaluating motor circuits, technicians must distinguish between momentary starting current and continuous operating current.

Motor Inrush vs. Running Current Timeline:
=========================================================================
 Current
   ^
   |  +-------------------+  <-- Locked Rotor Amps (LRA)
   |  |                   |      (4 to 6 Times Running Amps!)
   |  |   INRUSH PERIOD   |      Duration: 0.5 to 2.0 seconds
   |  |  (Rotor at 0 RPM) |      Zero CEMF
   |  |                   |
   |  +-------------------+------------------------------------------
   |                      \ 
   |                       \  CEMF Develops as Rotor Accelerates
   |                        \ 
   |                         +--------------------------------------- <-- FLA / RLA
   |                                                                      (Continuous Running)
   +--------------------------------------------------------------------> Time
=========================================================================

1. Locked Rotor Amps (LRA)

Locked Rotor Amps (LRA) is the instantaneous starting inrush current drawn by an electric motor at the precise instant voltage is applied while the rotor is completely stationary ($0\text{ RPM}$).

  • Why LRA Occurs: When the rotor is not spinning, it generates zero Counter-Electromotive Force (CEMF). The only opposition to current flow is the raw DC resistance and minimal stationary inductive reactance of the heavy copper windings. As a result, current spikes violently to 4 to 6 times the motor's normal continuous running amperage.
  • Duration: Under normal conditions, LRA persists for only a fraction of a second ($0.5\text{ to }2.0\text{ seconds}$) while the rotor accelerates up to operating speed.
  • CEMF Generation: As the rotor bars accelerate through the stator magnetic field, they cut lines of flux, rapidly generating CEMF. This back-EMF opposes line voltage, choking back the current from LRA down to normal running levels.

2. Full Load Amps (FLA) and Rated Load Amps (RLA)

  • Full Load Amps (FLA): The continuous current drawn by an open-drive electric motor (such as an evaporator blower motor or condenser fan motor) when delivering its rated mechanical horsepower output under design ambient conditions.
  • Rated Load Amps (RLA): The continuous current drawn specifically by a hermetic refrigeration compressor motor when operating at standard design suction and discharge pressures. Because hermetic compressor motors are actively cooled by cold suction refrigerant vapor flowing directly over the windings, they can dissipate more heat than an air-cooled motor of identical size, and are classified under UL and NEMA standards using RLA rather than FLA.

Diagnostic Interpretation of LRA in the Field

When troubleshooting a compressor that hums loudly and shuts off on its internal thermal overload protector:

  • A clamp-on ammeter reading full LRA (e.g., $75\text{ A}$ on a unit rated for $14\text{ A RLA}$) for $3\text{ seconds}$ confirms that the compressor is mechanically stuck (locked scroll or seized bearings) or that the run/start capacitor circuit has failed to develop an out-of-phase starting magnetic field.
  • Circuit breakers and fuses for HVAC equipment must be sized according to equipment nameplate specifications (Maximum Overcurrent Protection / MOP), utilizing time-delay dual-element fuses or inverse-time circuit breakers engineered to tolerate high LRA inrush without nuisance tripping.
Test Your Knowledge

A technician measures the electrical parameters of a 240 VAC residential electric duct heater containing nickel-chromium heating elements. The clamp meter reads an operating current of 20.0 A and an electronic wattmeter measures true power consumption at exactly 4,800 Watts. What is the power factor of this circuit, and what is the phase relationship between the operating voltage and current?

A
B
C
D
Test Your Knowledge

A single-phase condensing unit compressor draws 15.0 A at 240 VAC according to an ammeter and voltmeter (Apparent Power = 3,600 VA). A digital power analyzer records a true power consumption of 2,880 Watts. What is the operating power factor of the compressor motor, and what physical mechanism accounts for the difference between true power and apparent power?

A
B
C
D
Test Your Knowledge

A service technician responds to a no-cooling call for a 3-ton residential air conditioner with a compressor nameplate rating of RLA = 14.0 A and LRA = 75.0 A. Upon a call for cooling, the compressor emits a loud hum, fails to rotate, and trips its internal overload protector after 3 seconds. Clamp-on ammeter testing reveals a continuous current draw of 74.5 A throughout the 3-second attempt. What does this diagnostic reading confirm?

A
B
C
D