10.3 Nonpotable Water Systems and Graywater Storage

Key Takeaways

  • Graywater includes discharge from lavatories, bathtubs, showers, and clothes washers, but excludes blackwater from toilets, urinals, and kitchen sinks (IPC Section 1302).
  • A potable water makeup line must discharge into a nonpotable storage tank through an air gap (at least 2 pipe diameters or 1 inch minimum) or an RPZ backflow preventer.
  • Nonpotable water piping must be painted purple or wrapped in purple tape, and labeled at intervals not exceeding 5 feet (IPC Section 1301.9).
  • Storage tanks must be covered, vermin-proof, and vented to the atmosphere with vents protected by a corrosion-resistant screen (typically 1/16-inch mesh).
Last updated: July 2026

10.3 Nonpotable Water Systems and Graywater Storage

Commercial plumbing inspection includes verifying the safe design and installation of nonpotable water systems, including graywater recycling and rainwater harvesting. These systems are governed by IPC Chapters 13 and 14 and are designed to conserve potable water by utilizing alternative water sources for flushing fixtures, landscape irrigation, and cooling tower makeup.

Understanding Nonpotable Water Sources

Inspectors must distinguish between different types of wastewater to ensure they are routed and treated correctly:

  • Graywater (IPC Section 1302): Wastewater collected from lavatories, bathtubs, showers, clothes washers, and laundry trays. It excludes waste streams with high organic or chemical loads.
  • Rainwater: Natural precipitation collected from roof surfaces or aboveground stormwater catchments.
  • Blackwater (Prohibited for Graywater Systems): Wastewater containing human waste, organic matter, or heavy chemicals. This includes discharge from toilets, urinals, kitchen sinks, dishwashers, and food waste disposers. Blackwater must go directly to the sanitary drainage system.
  • Reclaimed Water: Wastewater treated by a utility provider and delivered to the property for nonpotable applications.
SourceAllowed Collection PointsPermitted Uses (Treated)Prohibited Sources
GraywaterBathtubs, showers, lavatories, laundry trays, clothes washers.Toilet/urinal flushing, subsurface irrigation.Toilets, urinals, kitchen sinks, dishwashers.
RainwaterRoof gutters, downspouts, aboveground catchments.Toilet flushing, surface/subsurface irrigation, cooling towers.Parking lot runoff, surface drains (unless treated).

Cross-Connection Control and Makeup Water

The absolute separation of potable water and nonpotable water systems is the primary safety concern for plumbing inspectors. Under IPC Section 1301.6, cross-connections between potable and nonpotable systems are strictly prohibited.

Potable Makeup Water Supply:

Nonpotable storage systems require a potable water makeup supply to ensure continuous operation when graywater or rainwater is unavailable (e.g., during droughts). This makeup line must be protected by:

  1. Approved Air Gap: The potable water pipe must discharge into the nonpotable tank through a physical air gap. The air gap must be at least twice the diameter of the supply pipe, but never less than 1 inch.
  2. Backflow Preventer: If an air gap is not used, the potable supply must connect to the tank or pump manifold using an approved backflow prevention assembly, such as a Reduced Pressure Zone (RPZ) backflow preventer or a Pressure Vacuum Breaker (PVB), installed in accordance with IPC Section 608.

Piping Identification and Signage

To prevent future maintenance errors or accidental ingestion, nonpotable systems must be clearly identified throughout the building.

Piping Identification (IPC Section 1301.9):

  • Color Coding: Nonpotable water distribution piping must be painted purple or wrapped in purple tape.
  • Labeling: Piping must be permanently labeled with the words "CAUTION: NONPOTABLE WATER - DO NOT DRINK" in contrasting lettering.
  • Intervals: Labels must be placed at intervals not exceeding 5 feet (1524 mm), and on both sides of any wall or floor penetration.

Signage for Outlets (IPC Section 1301.9.1):

  • All nonpotable water outlets, such as hose bibbs, wall hydrants, and irrigation valves, must be marked with a permanent warning sign.
  • The sign must display an international symbol for "do not drink" and read: "NONPOTABLE WATER - DO NOT DRINK" or "WARNING: NONPOTABLE WATER - DO NOT DRINK".
  • In commercial restrooms where toilets are flushed with nonpotable water, signs are often required indicating that nonpotable water is used for flushing.

Storage Tank Design and Vents

Storage tanks (cisterns) used for graywater and rainwater collection must meet the structural and sanitary requirements of IPC Section 1301.8:

  • Approved Materials: Tanks must be constructed of materials that are compatible with the stored water and resistant to corrosion. Concrete, fiberglass, and approved food-grade plastics are common.
  • Covered and Sealed: Tanks must be equipped with a tight-fitting cover to prevent contamination, keep out debris, and prevent the entry of insects (specifically mosquitoes) and vermin.
  • Light Exclusion: Tanks must be opaque or shielded to prevent sunlight from entering, which halts the growth of algae.
  • Vent Requirements (IPC Section 1301.8.6):
    • Tanks must be vented to the atmosphere to prevent vacuum collapse or overpressurization during filling and emptying.
    • The vent opening must be protected by a corrosion-resistant screen with a mesh size small enough to exclude insects (typically 1/16-inch mesh or finer).
    • Tank vents must not tie into the building's sanitary venting system.
  • Overflows: Overflows must discharge indirectly to the drainage system through a physical air gap to prevent sanitary sewage from backing up into the nonpotable storage tank.
  • Sump Pumps & Filtration: Tanks must include a filtration system to remove sediment and debris. Graywater stored for more than 24 hours must be treated and disinfected (using chlorine, UV, or ozone) because stagnant graywater rapidly breeds pathogens.
Test Your Knowledge

Which of the following waste streams is permitted to be collected as graywater for reuse in a nonpotable water system?

A
B
C
D
Test Your Knowledge

How must nonpotable water piping be identified inside a commercial building to prevent cross-connections?

A
B
C
D
Test Your Knowledge

What is the requirement for venting nonpotable water storage tanks (such as rainwater cisterns)?

A
B
C
D
Congratulations!

You've completed this section

Continue exploring other exams