1.4 HVACR Mathematics, Unit Conversions, and Efficiency Ratings
Key Takeaways
Ohm's Law, the sensible heat formula, and area/volume math are all tested as applied arithmetic: the exam gives you a field scenario and expects one number back.
One ton of refrigeration equals 12,000 BTU/hr, derived from the 288,000 BTU required to melt one ton of ice over 24 hours.
SEER2, EER2, and HSPF2 replaced SEER, EER, and HSPF in 2023 because AHRI 210/240 raised the external static pressure test condition from roughly 0.10-0.20 in. w.c. to 0.50 in. w.c.
AFUE measures seasonal fuel-burning efficiency as a percentage; COP is a dimensionless ratio of heat moved to energy consumed, and a COP of 3.0 equals roughly 10.2 BTU/watt-hour.
Life-cycle cost analysis compares first cost plus lifetime energy, maintenance, and replacement cost, which is why a higher-SEER2 unit can win on total cost while losing on purchase price.
1.4 HVACR Mathematics, Unit Conversions, and Efficiency Ratings
The first sheet of the HVAC Excellence Competency and Task List is General Studies, and it opens with mathematics. That placement is deliberate: almost every technical competency later in the list resolves into a calculation. Sizing a duct, verifying a charge, checking a temperature rise, or proving a compressor is pumping all end with a number that either falls inside the manufacturer's window or does not. The exam does not test mathematics abstractly — it embeds it inside field scenarios.
1. The Arithmetic the Task List Actually Names
The task list requires proficiency in decimals, fractions, negative numbers, squares, cubes, roots, ratios, proportions, basic equations, and conversion between English (inch-pound) and metric (SI) measurement.
Fractions and Decimals in Tubing and Sheet Metal Work
Refrigerant tubing is sold in fractional outside diameters (1/4", 3/8", 1/2", 5/8", 7/8", 1-1/8"). Manometers and static pressure readings are decimal (0.35 in. w.c.). You will constantly move between the two.
- Fraction to decimal: divide numerator by denominator. .
- Decimal to fraction (to the nearest 1/16): multiply by 16 and round. .
- Adding fractions requires a common denominator: a run of " plus " equals inches.
Negative Numbers and Delta-T
("delta T") is simply the difference between two temperatures, and the task list calls it out by name. Sign matters when one temperature is below zero.
- Evaporator entering air , leaving air : (a normal residential temperature split).
- Walk-in freezer box air , coil saturation : TD across the coil.
Area and Volume
- Rectangular duct area (sq ft) . A 20" × 8" duct is .
- Round duct area (sq ft) . A 10" round duct has ", so area .
- Box or room volume . A walk-in holds — the starting number for infiltration load and for blower-door conditioned-volume math.
- Velocity, area, and CFM tie together: . At 900 FPM through the 1.11 sq ft duct above, .
Ratios and Proportions
The task list specifically asks you to manipulate ratios for compressors, pumps, drives, and fans. The pulley (sheave) proportion is the classic:
A 1725 RPM motor with a 4" sheave driving a 10" blower sheave turns the blower at . Opening an adjustable motor sheave makes it functionally smaller, which lowers blower RPM and airflow — a fact that trips up candidates every year.
2. Unit Conversions You Must Know Cold
| Quantity | Conversion |
|---|---|
| Temperature | ; |
| Absolute temperature | ; |
| Refrigeration capacity | 1 ton = 12,000 BTU/hr = 200 BTU/min |
| Electrical heat | 1 kW = 3,412 BTU/hr; 1 W = 3.412 BTU/hr |
| Horsepower | 1 HP = 746 W = 2,545 BTU/hr |
| Pressure | 1 psi = 2.036 in. Hg = 27.7 in. w.c.; 1 atm = 14.696 psia = 29.92 in. Hg |
| Vacuum | 1 in. Hg = 25.4 mm Hg = 25,400 microns; 1 mm Hg (torr) = 1,000 microns |
| Length / volume | 1 in = 25.4 mm; 1 gal = 3.785 L = 231 in³ |
Where the ton comes from: melting one ton (2,000 lb) of ice absorbs (144 BTU/lb is the latent heat of fusion of water). Spread over 24 hours that is . Reconstructing the derivation is safer than memorizing it, because the exam sometimes asks for the 288,000 figure directly.
3. Efficiency Ratings and the Acronyms on the Task List
The General Studies sheet lists a specific block of acronyms you are expected to define. They fall into three families.
Cooling and heat pump ratings
| Rating | What it measures | Units |
|---|---|---|
| EER / EER2 | Steady-state cooling efficiency at one rating condition | BTU/hr per watt |
| SEER / SEER2 | Seasonal cooling efficiency across a range of outdoor temperatures | BTU/hr per watt |
| HSPF / HSPF2 | Seasonal heating efficiency of a heat pump over a heating season | BTU/hr per watt |
| COP | Heat moved divided by energy consumed, same units top and bottom | dimensionless |
| IEER | Part-load weighted efficiency for larger commercial equipment | BTU/hr per watt |
The "2" ratings arrived in 2023 with the revised AHRI Standard 210/240 M1 test procedure, which raised the external static pressure used during testing from roughly 0.10–0.20 in. w.c. to 0.50 in. w.c. The equipment did not get worse; the test got more realistic, so a 14 SEER unit re-rated at roughly 13.4 SEER2. Because COP is dimensionless, converting from an EER-style rating requires dividing out the BTU-per-watt-hour constant: . A heat pump with a COP of 3.0 is delivering about 10.2 BTU per watt-hour.
Fuel-burning ratings
AFUE (Annual Fuel Utilization Efficiency) is a percentage of fuel energy converted to usable heat over a heating season, including cycling and off-cycle losses. It is not the same number a combustion analyzer reports: a combustion analyzer computes steady-state efficiency, which is always higher than AFUE for the same appliance. A furnace at 82% steady-state may carry an 80% AFUE label.
Buildings, energy, and cost
- BIM — Building Information Modeling. CBECS — Commercial Buildings Energy Consumption Survey. EIA — Energy Information Administration. ECM — in this context, Energy Conservation Measure (the same three letters also mean Electronically Commutated Motor; the task list contains both, and context decides).
- USGBC / LEED and GBI / Green Globes are the two major green-building rating programs. DOE is the U.S. Department of Energy, which sets minimum equipment efficiency standards.
- Renewable vs. sustainable: renewable energy replenishes on a human timescale (solar, wind, geothermal, biomass). Sustainable practice meets present needs without compromising future supply — a broader idea that includes efficiency and material choice, not just the fuel source.
- Life-cycle cost analysis (LCCA) totals first cost, installation, energy over the expected service life, maintenance, and disposal or replacement. It is the argument a technician uses to justify a higher-efficiency unit: a $1,200 price premium that saves $300 per year in energy pays back in four years and then earns for the remaining life of the equipment.
A technician measures a rectangular supply duct at 24 inches by 10 inches and reads an average velocity of 700 FPM with a rotating-vane anemometer. What airflow is the duct carrying?
1,167 CFM
1,680 CFM
240 CFM
16,800 CFM
A belt-drive blower turns at 800 RPM with a 1725 RPM motor and a 4.5-inch motor sheave. The technician opens the adjustable motor sheave by two full turns, reducing its effective pitch diameter to 4.0 inches. What happens to blower speed and airflow?
Blower speed rises to about 900 RPM because opening a sheave increases its diameter
Blower speed falls to about 711 RPM and airflow decreases, because opening the sheave reduces its effective pitch diameter
Blower speed is unchanged because sheave adjustment only affects belt tension
Blower speed falls to about 400 RPM because airflow varies with the square of the diameter ratio
An installer compares a 14.3 SEER2 condenser at $3,400 against a 17.0 SEER2 condenser at $4,600, with an estimated annual cooling energy saving of $260. Which statement correctly applies life-cycle cost analysis?
The cheaper unit always wins life-cycle cost analysis because first cost is the largest single number
Life-cycle cost analysis cannot be applied because SEER2 is a seasonal rather than steady-state rating
The $1,200 premium recovers in roughly 4.6 years of energy savings, so over a 15-year service life the higher-efficiency unit has the lower life-cycle cost
The units are equivalent because both ratings were produced under the same AHRI 210/240 M1 test procedure
Sections you finish are checked off in the contents.