12.1 Structured Cabling, Fiber Optics & Industrial Ethernet Networks
Key Takeaways
- TIA/EIA-568 establishes a maximum horizontal channel length of 100 metres (90 m permanent solid-conductor link plus 10 m total stranded patch cords) for Cat5e (100 MHz), Cat6 (250 MHz), and Cat6A (500 MHz).
- Industrial Ethernet environments mandate shielded twisted pair (STP/FTP) or industrial M12 connectors (IP67 sealed) to resist mechanical vibration, moisture, and intense electromagnetic interference (EMI) from VFDs and welders.
- Fiber optic cabling provides total immunity to electromagnetic interference and high-voltage isolation; single-mode fiber (SMF, ~9 µm core, 1310/1550 nm laser) spans tens of kilometres, whereas multi-mode fiber (MMF, 50 or 62.5 µm core, 850/1300 nm VCSEL/LED) serves plant distances up to 300–550 m.
- Industrial Ethernet networks utilize deterministic protocols (EtherNet/IP with CIP producer/consumer model, Profinet, Modbus TCP) over fault-tolerant physical topologies like Device Level Ring (DLR) and Rapid Spanning Tree Protocol (RSTP) managed switches, with strict physical separation from power conductors per CEC Rule 56-200 and IEEE 518.
12.1 Structured Cabling, Fiber Optics & Industrial Ethernet Networks
Industrial communications form the critical digital backbone connecting Programmable Logic Controllers (PLCs), Distributed Control Systems (DCS), Human-Machine Interfaces (HMIs), Variable Frequency Drives (VFDs), Motor Control Centers (MCCs), and field instrumentation. In heavy industrial environments—such as pulp and paper mills, petrochemical refineries, mining extraction facilities, and automotive assembly plants—networking systems are exposed to extreme electromagnetic interference (EMI), radio-frequency interference (RFI), physical vibration, corrosive atmospheres, moisture, and wide temperature swings. Industrial electricians are responsible for installing, terminating, testing, and troubleshooting these physical and logical communication links in strict compliance with the Canadian Electrical Code (CEC CSA C22.1), ANSI/TIA-568 standards, and IEEE industrial standards.
1. Structured Copper Cabling Standards & Physical Infrastructure
Copper structured cabling systems in commercial and light industrial applications follow the ANSI/TIA-568 commercial building telecommunications cabling standard, while harsh manufacturing environments adhere to ANSI/TIA-1005 (Telecommunications Infrastructure Standard for Industrial Premises) utilizing M.I.C.E. environmental classifications (Mechanical, Ingress, Climatic/Chemical, Electromagnetic).
Category Cable Performance & Specifications
Category twisted-pair cabling relies on differential signaling across twisted conductor pairs to reject common-mode electromagnetic noise. Tighter twist rates per metre increase common-mode rejection and reduce cross-talk between adjacent pairs.
| Cable Category | Maximum Bandwidth | Maximum Data Rate | Maximum Channel Distance | Typical Industrial Applications |
|---|---|---|---|---|
| Category 5e (Cat5e) | 100 MHz | 1 Gbps (1000BASE-T) | 100 m (90 m permanent + 10 m patch) | Legacy fieldbus migration, standard PLC-to-I/O racks, 100BASE-TX EtherNet/IP |
| Category 6 (Cat6) | 250 MHz | 1 Gbps / 10 Gbps (up to 37–55 m) | 100 m (90 m permanent + 10 m patch) | Plant floor supervisory switches, HMI server uplinks, machine vision systems |
| Category 6A (Cat6A) | 500 MHz | 10 Gbps (10GBASE-T) | 100 m full channel at 10 Gbps | Industrial backbone aggregation, plant-wide virtualization servers, edge computing nodes |
The 100-Metre Channel Rule & Attenuation Budget
Under TIA/EIA-568-C.2, the maximum certified transmission channel for Category twisted-pair copper cable is strictly 100 metres (328 feet):
- Permanent Link (90 metres / 295 feet maximum): Composed of solid-conductor 23 AWG or 24 AWG horizontal cable permanently installed in conduit, raceways, or cable trays between the telecommunications patch panel in the control room and the field enclosure. Solid conductors exhibit lower electrical resistance and lower signal attenuation over distance but possess limited flex fatigue resistance.
- Equipment and Work Area Patch Cords (10 metres / 33 feet total combined maximum): Composed of stranded-conductor patch cords connecting active hardware (such as switches and PLCs) to patch panels or wall jacks. Stranded conductors offer high flexibility to withstand enclosure door movement and mechanical vibration, but their signal attenuation is 20% to 50% higher than solid core wire. Exceeding 10 metres of total patch cord length degrades signal-to-noise margins below receiver sensitivity thresholds, causing packet retransmissions, jitter, and intermittent dropouts.
┌─────────────────┐ ┌─────────────────┐
│ Industrial │ │ Field PLC / │
│ Managed Switch │ │ Remote I/O Rack │
└────────┬────────┘ └────────┬────────┘
│ │
[Patch Cord ≤ 5m] [Patch Cord ≤ 5m]
(Stranded AWG) (Stranded AWG)
│ │
▼ ▼
┌─────────────────┐ SOLID HORIZONTAL PERMANENT LINK (≤ 90m) ┌─────────────────┐
│ Control Room ├───────────────────────────────────────────────────────┤ Field Enclosure │
│ Patch Panel │ (23/24 AWG Solid Conductor) │ Industrial Jack │
└─────────────────┘ └─────────────────┘
└────────────────────────────────── 100 METRES TOTAL CHANNEL ───────────────────────────────┘
Unshielded (UTP) vs. Shielded (STP / FTP) Cabling
- Unshielded Twisted Pair (UTP): Relies solely on differential twists for noise cancellation. Suitable only in clean control rooms or office environments isolated from power electronics.
- Foiled Twisted Pair (FTP / F/UTP): Features an overall aluminum Mylar foil shield wrapping all four pairs with an uninsulated tinned-copper drain wire. Protects against high-frequency electromagnetic interference (EMI) and radio frequency interference (RFI).
- Shielded Foiled Twisted Pair (S/FTP): Features individual foil shields around each conductor pair plus an overall braided tinned copper outer shield. Provides maximum protection against high-energy electromagnetic transients from VFDs, large induction motors, and resistance welders, while preventing internal pair-to-pair alien crosstalk.
2. Industrial Connectors: Standard RJ-45 vs. Heavy-Duty M12
While commercial IT infrastructure standardizes on the plastic 8-position, 8-contact (8P8C) RJ-45 modular plug, standard RJ-45 connectors fail rapidly on the industrial plant floor due to vibration-induced contact fretting, plastic latch breakage, and contamination from oil, moisture, and dust.
| Connector Type | Ingress Rating | Mechanical Latching | Pin Count & Coding | Common Industrial Applications |
|---|---|---|---|---|
| Standard RJ-45 | IP20 (open to dust/moisture) | Plastic snap-latch (fragile) | 8 pins | Clean control cabinets, climate-controlled server racks |
| Industrial RJ-45 | IP20 to IP67 (with threaded bayonet shroud) | Die-cast zinc or threaded locking collar | 8 pins (shielded 360-degree bonding) | Heavy industrial control cabinets, outdoor junction enclosures |
| M12 D-Coded | IP67 / IP68 / IP69K (dust-tight, washdown) | Threaded M12 x 1.0 metal screw collar | 4 pins (2 pairs, 100 Mbps Fast Ethernet) | Field sensors, I/O distribution blocks, robotic end-effectors |
| M12 X-Coded | IP67 / IP68 / IP69K (washdown, extreme shock) | Threaded metal collar with internal X-shield | 8 pins (4 shielded quadrants, up to 10 Gbps) | High-speed machine vision cameras, plant backbone switches |
3. Fiber Optic Communications in Industrial Environments
Fiber optic communication transmits digital data as pulses of light through high-purity silica glass cores. In industrial electrical installations, optical fiber provides two revolutionary advantages over copper:
- Total Immunity to Electromagnetic Interference (EMI/RFI): Photons are completely unaffected by magnetic flux, high-voltage arcing, high-power radio transmissions, or VFD switching harmonics.
- Complete Electrical Isolation: Because glass is a dielectric insulator, fiber cables conduct zero electrical current. This eliminates plant ground loops between separate substation grounding grids, prevents lightning strike transfer between outlying structures, and complies with CEC hazardous location requirements.
Single-Mode Fiber (SMF) vs. Multi-Mode Fiber (MMF)
SINGLE-MODE FIBER (SMF)
Light takes a single, direct axial path (No Modal Dispersion)
┌─────────────────────────────────────────────────────────────┐
│ Cladding (125 µm) │
│ ┌───────────────────────────────────────────────┐ │
│======│ Core (9 µm) ─────────────────────────────────>│======│ Laser Source (1310 / 1550 nm)
│ └───────────────────────────────────────────────┘ │ Distance: Up to 10–40+ km
│ Cladding (125 µm) │
└─────────────────────────────────────────────────────────────┘
MULTI-MODE FIBER (MMF)
Light travels along multiple reflective paths (Suffers from Modal Dispersion)
┌─────────────────────────────────────────────────────────────┐
│ Cladding (125 µm) │
│ ┌───────────────────────────────────────────────┐ │
│ /\ │ Core (50 µm or 62.5 µm) │ /\ │ VCSEL / LED (850 / 1300 nm)
│ / \─┼───────────────────────────────────────────────┼─/ \ │ Distance: 300–550 m (at 1 Gbps)
│/ └───────────────────────────────────────────────┘ \│
└─────────────────────────────────────────────────────────────┘
| Specification | Single-Mode Fiber (SMF) | Multi-Mode Fiber (MMF) |
|---|---|---|
| Core Diameter | 8 to 9 µm (extremely narrow) | 50 µm (OM2, OM3, OM4, OM5) or 62.5 µm (OM1) |
| Cladding Diameter | 125 µm | 125 µm |
| Light Source | Solid-state laser diode (Fabry-Perot or DFB) | Vertical-Cavity Surface-Emitting Laser (VCSEL) or LED |
| Operating Wavelengths | 1310 nm and 1550 nm (infrared spectrum) | 850 nm and 1300 nm (infrared spectrum) |
| Limiting Factor | Material attenuation (absorption and Rayleigh scattering) | Modal dispersion (different light rays arriving at different times) |
| Typical Distance Limits | 10 km to 40+ km without repeaters | 300 m to 550 m at 1 Gbps; 100 m to 400 m at 10 Gbps |
| Industrial Applications | Inter-building plant backbones, wind farm collection, pipeline telemetry | In-plant PLC-to-switch links, switchgear lineup backbones, MCC lineups |
Fiber Optic Connectors
- ST (Straight Tip): Features a round ceramic ferrule with a spring-loaded bayonet twist-lock mechanism (similar to BNC). Widely used in legacy plant installations and harsh vibration environments.
- SC (Subscriber Connector / Standard Connector): Features a square, molded push-pull latching body with a 2.5 mm ceramic ferrule. Commonly deployed in industrial patch panels and media converters.
- LC (Lucent Connector / Local Connector): Small-form-factor connector utilizing a 1.25 mm ferrule with a snap-in telephone-style latch. Standard in modern high-density industrial switches, SFP (Small Form-factor Pluggable) transceivers, and automation processors.
4. Fiber Splicing, Termination & Testing Methodologies
Fusion Splicing vs. Mechanical Splicing
- Fusion Splicing: Uses an electric arc from high-precision tungsten electrodes to melt and fuse the microscopic glass cores together. Yields an ultra-low insertion loss (typically < 0.02 dB to 0.05 dB) and near-zero back reflection (< -60 dB). Mandatory for high-speed industrial backbones and mission-critical networks.
- Mechanical Splicing: Aligns two cleave-cut fibers within an index-matching gel alignment sleeve inside a mechanical housing. Involves higher insertion loss (0.2 dB to 0.5 dB) and higher reflectance. Used primarily for temporary emergency repairs in the field.
Verification & Testing Instruments
- Visual Fault Locator (VFL): Emits visible red laser light (635–650 nm) into the fiber core. Bends, breaks, or damaged splices cause light leakage visible through the outer buffer jacket. Limited to short visible distances (typically < 3–5 km) and cannot measure decibel losses.
- Optical Loss Test Set (OLTS): Consists of a calibrated stabilized light source (OLS) at one end and an optical power meter (OPM) at the other. Measures overall channel insertion loss (attenuation in dB) across the link: OLTS testing provides Tier 1 Certification per TIA-568 standards, confirming whether the total link loss complies with the specified optical loss budget.
- Optical Time-Domain Reflectometer (OTDR): Injects high-speed, high-power optical pulses down the fiber and measures the timing and amplitude of reflected light (Rayleigh backscattering and Fresnel reflections).
- Generates an event trace displaying distance (X-axis) versus loss in decibels (Y-axis).
- Accurately calculates link attenuation (dB/km), identifies exact splice losses, connector insertion losses, optical return loss (ORL), macrobends (pinched fiber), and measures exact physical distance (in metres) to a cable break.
- Provides Tier 2 Certification. Essential for troubleshooting buried cables or runs inside complex tray systems.
5. Industrial Ethernet Protocols & Network Topologies
Standard commercial Ethernet (IEEE 802.3) with CSMA/CD (Carrier Sense Multiple Access with Collision Detection) is inherently non-deterministic—packet transmission delays vary unpredictably under heavy network load. Industrial Ethernet modifies the transport and application layers to ensure deterministic, time-critical delivery of automation commands.
Common Industrial Protocols
- EtherNet/IP (Industrial Protocol): Governed by ODVA, EtherNet/IP overlays the Common Industrial Protocol (CIP) on standard TCP/IP and UDP/IP stacks. It utilizes a Producer/Consumer model where data is broadcast once across the network and consumed by multiple controllers simultaneously. Time-critical I/O control data uses UDP multicast/unicast (implicit messaging), while parameter configuration uses TCP (explicit messaging).
- Modbus TCP: Encapsulates classic Modbus RTU register frames (Read Holding Registers, Write Coils) directly into TCP/IP packets over standard Port 502. Operates on a deterministic Client/Server (Master/Slave) request-response structure. Highly robust and universally supported by field power meters and PLCs.
- Profinet (Process Field Net): Developed by Profibus & Profinet International (PI). Uses standard TCP/IP for non-time-critical commissioning, but bypasses the IP protocol stack entirely for real-time cyclic I/O data using Profinet Real-Time (RT) (Ethernet Type 0x8892), achieving deterministic cycle times < 1 ms. For motion control, Profinet IRT (Isochronous Real-Time) uses dedicated hardware ASIC timing to eliminate jitter.
Network Topologies & Redundancy Mechanisms
STAR TOPOLOGY LINEAR / BUS TOPOLOGY DEVICE LEVEL RING (DLR)
┌──────────────┐ ┌──────┐ ┌──────┐ ┌──────┐ ┌──────┐ ┌──────┐
│ Managed │ │ Node │───│ Node │───│ Node │ │ Node ├───────┤ Node │
│ Switch │ └──────┘ └──────┘ └──────┘ └─┬────┘ └───┬──┘
└──┬───┬───┬───┘ Single break isolates downstream │ Ring breaks │
│ │ │ │ Auto-heals │
┌──┴┐ ┌┴──┐ ┌┴──┐ ┌─┴────┐ ┌───┴──┐
│PLC│ │HMI│ │VFD│ │ Node ├───────┤ Node │
└───┘ └───┘ └───┘ └──────┘ └──────┘
Clean isolation; Low wiring cost; Fault-tolerant; recovery
switch is single point of failure zero fault tolerance time < 3 milliseconds
- Star Topology: All devices connect to a central industrial switch. A severed cable isolates only the connected device, leaving the rest of the network operational. However, the switch is a single point of failure unless redundant switches are deployed.
- Linear / Daisy-Chain Topology: Embedded two-port Ethernet switches inside PLCs and VFDs allow devices to be wired in a line. Saves cabling, but a physical cable break or powered-down device severs all downstream nodes.
- Fault-Tolerant Redundant Rings:
- Device Level Ring (DLR): A single-fault-tolerant industrial protocol embedded at the hardware layer of EtherNet/IP devices. Devices contain an integrated 2-port switch. A designated Ring Supervisor monitors beacon frames around the closed loop. When a cable is cut, the supervisor detects beacon loss and unblocks its backup port in less than 3 milliseconds, converting the ring into two linear segments with zero operational disruption to active machines.
- Rapid Spanning Tree Protocol (RSTP, IEEE 802.1w): A standard network switch protocol that detects physical loops and blocks redundant paths to prevent broadcast storms. If an active link fails, RSTP re-converges and unblocks the backup link within 1 to 2 seconds. While fast for enterprise IT, 1 to 2 seconds is often too slow for synchronized robotic motion or high-voltage protective relaying, making DLR or PRP (Parallel Redundancy Protocol, zero-millisecond recovery) the preferred industrial choices.
6. Industrial Managed Switches vs. Unmanaged Switches
In industrial control systems, deploying cheap commercial unmanaged switches on the plant floor is a leading cause of production downtime.
| Feature / Capability | Industrial Managed Switch | Unmanaged Switch | Operational Consequence |
|---|---|---|---|
| IGMP Snooping | Supported (Essential for EtherNet/IP) | Not Supported (Floods all ports) | Without IGMP snooping, multicast CIP traffic floods every connected port, crashing HMIs and non-EtherNet/IP devices. |
| Virtual LANs (VLANs - IEEE 802.1Q) | Supported | Not Supported | Allows logical segmentation of safety, process I/O, and business network traffic on the same physical switch. |
| Quality of Service (QoS / CoS) | Supported (Prioritizes 802.1p tags) | FIFO (First In, First Out) | Ensures high-priority safety interlocking and drive synchronization packets precede large file transfers. |
| Port Mirroring | Supported | Not Supported | Enables an electrician to connect a laptop running Wireshark to mirror and capture all traffic for diagnostic analysis. |
| Redundancy Protocols | RSTP, DLR, MRP supported | None | Prevents catastrophic broadcast storms and provides sub-second failover when cables are severed. |
| Industrial Hardening | -40°C to +75°C, dual 24 VDC power, DIN rail mount | 0°C to 40°C, commercial wall-wart 120 VAC | Survives thermal extremes, vibration, and loss of a single control power supply. |
7. Noise Mitigation & Canadian Electrical Code Compliance
Electromagnetic compatibility (EMC) is a primary responsibility of the industrial electrician. High-frequency electrical noise from the pulse-width modulated (PWM) inverter outputs of VFDs, switching rectifiers, and high-current welding arcs readily couples onto adjacent communications conductors through capacitive (electrostatic) and inductive (magnetic) coupling.
Canadian Electrical Code (CEC) Rules for Separation
The CEC Part I regulates the installation and separation of communication and optical fiber cables from high-energy power conductors:
- CEC Rule 56-200 (Optical Fiber Cables): Non-conductive optical fiber cables (containing zero metal elements or metallic armor) are permitted to occupy the same raceway, cable tray, or enclosure as electric power and lighting conductors operating at any voltage. Conductive optical fiber cables (containing metallic strength members, armor, or metallic vapor barriers) must be handled like communication conductors and grounded per Rule 56-204.
- CEC Rule 60-308 & Section 16 (Separation of Conductors): Low-voltage Class 2 communication cables (such as Cat6) must not be placed in any raceway, compartment, outlet box, junction box, or cable tray with conductors of electric light, power, or Class 1 circuits, unless separated by a continuous, permanent metal or non-metallic barrier.
- IEEE 518 Noise Abatement Guide: Specifies minimum physical separation distances between communication cabling and 600 V power feeders:
- Inside open steel cable trays: minimum 300 mm (12 inches) separation when tray runs parallel to high-current power cables.
- When communication cables and power cables must intersect, they must cross at a 90-degree right angle. This aligns the communication conductors perpendicularly to the magnetic flux lines radiating from the power cable, reducing magnetic inductive coupling to near zero.
Cable Shield Grounding & Avoiding Ground Loops
A critical concept on the Red Seal exam concerns the grounding of cable shields:
- Low-Frequency Noise & Ground Loops (Single-Point Grounding): When an industrial communication cable shield is connected to earth ground at both ends of a long run (e.g., between two remote buildings or different switchgear lineups), any difference in earth potential between the two grounding electrodes forces current to flow through the shield. This circulating ground loop current induces 60 Hz hum and common-mode noise directly into the twisted pairs. Therefore, for low-frequency analog circuits and standard fieldbus trunks, the shield must be grounded at one end only (typically at the control cabinet or PLC end), and insulated/taped at the field end.
- High-Frequency RF Noise & 360-Degree Bonding: In modern high-speed Industrial Ethernet installations subjected to MHz-range VFD carrier frequencies, single-ended grounding acts as an open antenna. High-frequency noise is drained effectively only by utilizing shielded RJ-45 jacks mounted in metal patch panels that bond the shield 360 degrees to the chassis, or by utilizing metal bonding bushings and DIN-rail shield clamps. To prevent DC/60 Hz ground loops while maintaining RF grounding, managed switches incorporate internal capacitive grounding—passing high-frequency RF noise to chassis ground while blocking low-frequency 60 Hz circulating currents.
8. Concrete Industrial Scenario: Commissioning a Redundant DLR Network Across Four 600 V MCCs
An industrial electrician is assigned to commission a new packaging line featuring four 600 V Motor Control Centers (MCCs) distributed across a 150-metre processing hall. Each MCC contains a Rockwell ControlLogix remote I/O chassis and eight PowerFlex 755 VFDs communicating via EtherNet/IP.
┌─────────────────────────────────────────┐
│ PLC ControlLogix Rack 1 (Main Enclosure) │
│ 1756-EN2TR Module (Ring Supervisor) │
└────────┬───────────────────────▲────────┘
│ Port 1 │ Port 2 (Active Backup)
▼ │
┌─────────────────┐ │
│ MCC-1 (VFDs) │ │
└────────┬────────┘ │
│ │
▼ │
┌─────────────────┐ │
│ MCC-2 (VFDs) │ │
└────────┬────────┘ │
│ │
▼ │
┌─────────────────┐ │
│ MCC-3 (VFDs) │ │
└────────┬────────┘ │
│ │
▼ │
┌─────────────────┐ │
│ MCC-4 (VFDs) ├──────────────┘
└─────────────────┘
- Physical Cabling & Routing:
- The electrician pulls heavy-duty S/FTP Category 6 cable fitted with oil-resistant PUR outer jackets.
- Cabling between MCCs is laid inside dedicated telecommunications ladder tray maintaining a 450 mm physical clearance from the 600 V feeder conduit per IEEE 518. Where the Ethernet runs drop down to enter MCC cabinets, they cross the 600 V supply conductors at 90-degree right angles.
- Terminations:
- Solid horizontal runs terminate at shielded DIN-rail mounted RJ-45 patch modules inside each MCC.
- The electrician verifies that the cable foil shield and braided mesh are clamped 360 degrees inside the connector housing to maintain electrical continuity through the metal DIN rail, which is bonded to the MCC ground bus with a 6 AWG copper conductor.
- Configuring the DLR Network:
- The electrician daisy-chains Port 1 of the PLC communication module (1756-EN2TR) to MCC-1, through MCC-2, MCC-3, MCC-4, and loops the final cable from MCC-4 back into Port 2 of the 1756-EN2TR, completing the physical ring.
- In Studio 5000 software, the electrician configures the 1756-EN2TR communication adapter as the Ring Supervisor and enables the beacon interval (400 µs) and beacon timeout (80 µs).
- The supervisor verifies ring integrity: it transmits beacons out Port 1, receives them on Port 2, and places Port 2 into a blocking state to prevent a network loop. The status LED illuminates solid green: "Ring Normal".
- Fault Simulation Verification:
- To prove system reliability, the electrician disconnects the Ethernet patch cord between MCC-2 and MCC-3 while the packaging line runs in test mode.
- The Ring Supervisor immediately detects beacon loss (within 80 µs), unblocks Port 2, and transitions the network into "Ring Fault" state in under 2 milliseconds. All VFDs continue operating without missing a single motion control packet or tripping on communication timeouts.
- When the patch cord is reconnected, the supervisor detects beacon restoration, transitions Port 2 back to blocking, and returns the network to "Ring Normal" state with zero packet loss.
According to TIA/EIA-568 structured cabling standards, what is the maximum permitted channel distance for a Category 6A copper horizontal Ethernet link, and how is this distance divided between permanent link cabling and patch cords?
An industrial electrician is pulling optical fiber between a main plant server room and an outlying pumping station located 4.5 kilometres away across an industrial site. Which type of fiber optic cable and light source must be specified for this installation?
A multi-fiber optical backbone between two industrial control enclosures is experiencing intermittent packet loss. The maintenance supervisor requires a test instrument that can pinpoint the exact physical distance to a reflective fault, bad splice, or sharp bend along the cable span. Which test instrument should the electrician use?
When routing shielded twisted-pair (STP) industrial Ethernet cabling adjacent to 600 V variable frequency drive (VFD) motor feeders, which installation practice prevents common-mode noise coupling and eliminates circulating ground loop currents?