Psychrometry and Instruments
Key Takeaways
- A sling psychrometer (whirling wet/dry bulb hygrometer) provides two direct readings: dry-bulb temperature (ambient air) and wet-bulb temperature (evaporative cooling), which yield relative humidity and dew point via a psychrometric chart.
- Dry-bulb minus wet-bulb is the depression; a zero depression means the air is saturated (100% RH) and the wet-bulb equals dry-bulb, so dew point equals air temperature.
- Relative humidity is the ratio of actual vapor pressure to saturation vapor pressure at the dry-bulb temperature, expressed as a percentage; it is not the same as absolute humidity (mass of water per volume of air).
- Surface temperature is measured separately from air temperature using a magnetic dial thermometer (ferrous only), an electronic thermistor probe, or an infrared (IR) thermometer, which requires a correct emissivity setting.
- Dew point is the temperature at which condensation begins; it always falls between the wet-bulb and dry-bulb readings when RH is below 100%, so it is never equal to the wet-bulb except at saturation.
Quick Answer: Ambient condition measurement is the coatings inspector's first pre-application duty. A sling psychrometer (whirling wet/dry bulb hygrometer) gives two readings — dry-bulb and wet-bulb temperatures — from which relative humidity and dew point are derived using a psychrometric chart or calculator. Surface temperature is measured separately with a magnetic dial thermometer, electronic thermistor probe, or infrared (IR) thermometer. The inspector compares surface temperature to dew point before any coating is applied.
Sling Psychrometer Operation
The sling psychrometer — also called a whirling hygrometer — is the field instrument specified by AMPP CIP Level 1 for ambient moisture measurement. It consists of two thermometers mounted side-by-side on a frame with a swivel handle. One thermometer has a clean muslin wick (sock) fitted over its bulb and is wetted with distilled or deionized water; this is the wet-bulb thermometer. The other is bare and reads the dry-bulb temperature. The inspector whirls the assembly through the air for approximately 90 seconds (or until the wet-bulb reading stabilizes at its lowest point), then reads both thermometers immediately.
Wet-Bulb and Dry-Bulb Temperatures
- Dry-bulb temperature (DBT): The actual ambient air temperature from the bare thermometer — the same reading any ordinary thermometer gives.
- Wet-bulb temperature (WBT): The lowest temperature achievable by evaporative cooling of water into the air. The wet wick cools as water evaporates; the drier the air, the more evaporation occurs and the lower the wet-bulb reading.
- Wet-bulb depression: DBT minus WBT. A large depression means low humidity; a depression of zero means the air is saturated (100% RH, wet-bulb equals dry-bulb, and dew point equals air temperature).
The depression is the raw input to a psychrometric chart or calculator that yields RH and dew point.
Relative Humidity vs Absolute Humidity
| Concept | Definition | Field Relevance |
|---|---|---|
| Absolute humidity | Actual mass of water vapor per unit volume of air (g/m³) | Rarely used in field work |
| Relative humidity (RH) | Ratio of actual water vapor pressure to saturation vapor pressure at the same dry-bulb temperature, expressed as a percentage | Governs condensation risk; measured via psychrometer |
| Dew point | Temperature at which air becomes saturated and moisture condenses onto a surface | The critical value for the 5°F rule |
RH is what matters for coating work because it governs condensation. Fifty percent RH at 90°F holds far more actual water vapor than 50% RH at 50°F — so absolute humidity is not the operative metric for coating inspection.
Psychrometric Chart Use and Worked Dew Point Calculation
The psychrometric chart plots dry-bulb temperature on the horizontal axis, with wet-bulb lines sloping diagonally and RH curves arching across the chart. To use it:
- Locate the dry-bulb temperature on the horizontal axis.
- Follow the sloping wet-bulb line from that point until it intersects the wet-bulb reading.
- Read RH from the curved RH lines passing through the intersection (50%, 70%, 85%, etc.).
- Find the dew point by following the horizontal line left from the intersection to the 100% RH (saturation) curve, then read down to the temperature axis.
Worked Example
A sling psychrometer reads dry-bulb 70°F and wet-bulb 60°F — a 10°F depression. On the psychrometric chart, the intersection of 70°F dry-bulb and 60°F wet-bulb gives RH approximately 55%; following the horizontal line left to the saturation curve gives dew point approximately 53°F.
Interpretation: condensation forms on any surface at or below 53°F. A steel surface at 58°F gives a 5°F margin — application may proceed. A steel surface at 52°F is 1°F below the dew point — coating must not begin.
Surface Temperature Instruments
Surface temperature must be measured on the substrate itself — it cannot be inferred from air temperature, because steel radiatively cools below air temperature at night. Three instruments are recognized in CIP Level 1:
| Instrument | Method | Typical Use and Limitations |
|---|---|---|
| Magnetic dial thermometer | Magnetic base clings to ferrous steel; bimetallic dial reads surface temp | Quick field check on steel tanks and structural members; ferrous only; allow 2-3 min to stabilize |
| Electronic thermistor probe | Contact probe with digital readout; high accuracy | Precise measurement on any surface; faster response than dial; most common field choice |
| Infrared (IR) thermometer | Non-contact; measures thermal radiation | Quick scan of large areas; accuracy depends on correct emissivity setting; bare steel has low emissivity and reads falsely low unless taped or adjusted |
Field Procedure Notes
- Allow dial thermometers at least 2-3 minutes to stabilize before reading.
- Take surface temperature on the actual area to be coated, not a nearby rail or scaffold.
- IR readings of bare blasted steel are unreliable without emissivity correction; black tape on the steel gives a known-emissivity target.
- Record the instrument used — auditors and spec writers may require a specific type.
Exam Traps
- The wick must be wetted with distilled or deionized water — tap water leaves mineral deposits that skew wet-bulb readings.
- The sling must be whirled long enough (approximately 90 seconds or until the wet-bulb stabilizes). A few swings give a falsely high wet-bulb reading, inflating calculated RH and dew point.
- Avoid whirling in direct sunlight or near heat sources — radiant heat inflates the dry-bulb and corrupts the depression.
- Magnetic dial thermometers only work on ferrous steel; they cannot measure aluminum, galvanized, or non-ferrous substrates.
- Dew point is the temperature at which condensation begins — it is NOT the same as the wet-bulb temperature (dew point is always between the wet-bulb and dry-bulb when RH is below 100%).
What two readings does a sling psychrometer directly provide?
On a psychrometric chart, how is the dew point found from a dry-bulb and wet-bulb pair?
In the worked example, a sling psychrometer reads dry-bulb 70°F and wet-bulb 60°F. What is the approximate dew point?
What is a key limitation of magnetic dial thermometers for surface temperature measurement?