Psychrometry and Instruments

Key Takeaways

  • A sling psychrometer (whirling wet/dry bulb hygrometer) provides two direct readings: dry-bulb temperature (ambient air) and wet-bulb temperature (evaporative cooling), which yield relative humidity and dew point via a psychrometric chart.
  • Dry-bulb minus wet-bulb is the depression; a zero depression means the air is saturated (100% RH) and the wet-bulb equals dry-bulb, so dew point equals air temperature.
  • Relative humidity is the ratio of actual vapor pressure to saturation vapor pressure at the dry-bulb temperature, expressed as a percentage; it is not the same as absolute humidity (mass of water per volume of air).
  • Surface temperature is measured separately from air temperature using a magnetic dial thermometer (ferrous only), an electronic thermistor probe, or an infrared (IR) thermometer, which requires a correct emissivity setting.
  • Dew point is the temperature at which condensation begins; it always falls between the wet-bulb and dry-bulb readings when RH is below 100%, so it is never equal to the wet-bulb except at saturation.
Last updated: July 2026

Quick Answer: Ambient condition measurement is the coatings inspector's first pre-application duty. A sling psychrometer (whirling wet/dry bulb hygrometer) gives two readings — dry-bulb and wet-bulb temperatures — from which relative humidity and dew point are derived using a psychrometric chart or calculator. Surface temperature is measured separately with a magnetic dial thermometer, electronic thermistor probe, or infrared (IR) thermometer. The inspector compares surface temperature to dew point before any coating is applied.

Sling Psychrometer Operation

The sling psychrometer — also called a whirling hygrometer — is the field instrument specified by AMPP CIP Level 1 for ambient moisture measurement. It consists of two thermometers mounted side-by-side on a frame with a swivel handle. One thermometer has a clean muslin wick (sock) fitted over its bulb and is wetted with distilled or deionized water; this is the wet-bulb thermometer. The other is bare and reads the dry-bulb temperature. The inspector whirls the assembly through the air for approximately 90 seconds (or until the wet-bulb reading stabilizes at its lowest point), then reads both thermometers immediately.

Wet-Bulb and Dry-Bulb Temperatures

  • Dry-bulb temperature (DBT): The actual ambient air temperature from the bare thermometer — the same reading any ordinary thermometer gives.
  • Wet-bulb temperature (WBT): The lowest temperature achievable by evaporative cooling of water into the air. The wet wick cools as water evaporates; the drier the air, the more evaporation occurs and the lower the wet-bulb reading.
  • Wet-bulb depression: DBT minus WBT. A large depression means low humidity; a depression of zero means the air is saturated (100% RH, wet-bulb equals dry-bulb, and dew point equals air temperature).

The depression is the raw input to a psychrometric chart or calculator that yields RH and dew point.

Relative Humidity vs Absolute Humidity

ConceptDefinitionField Relevance
Absolute humidityActual mass of water vapor per unit volume of air (g/m³)Rarely used in field work
Relative humidity (RH)Ratio of actual water vapor pressure to saturation vapor pressure at the same dry-bulb temperature, expressed as a percentageGoverns condensation risk; measured via psychrometer
Dew pointTemperature at which air becomes saturated and moisture condenses onto a surfaceThe critical value for the 5°F rule

RH is what matters for coating work because it governs condensation. Fifty percent RH at 90°F holds far more actual water vapor than 50% RH at 50°F — so absolute humidity is not the operative metric for coating inspection.

Psychrometric Chart Use and Worked Dew Point Calculation

The psychrometric chart plots dry-bulb temperature on the horizontal axis, with wet-bulb lines sloping diagonally and RH curves arching across the chart. To use it:

  1. Locate the dry-bulb temperature on the horizontal axis.
  2. Follow the sloping wet-bulb line from that point until it intersects the wet-bulb reading.
  3. Read RH from the curved RH lines passing through the intersection (50%, 70%, 85%, etc.).
  4. Find the dew point by following the horizontal line left from the intersection to the 100% RH (saturation) curve, then read down to the temperature axis.

Worked Example

A sling psychrometer reads dry-bulb 70°F and wet-bulb 60°F — a 10°F depression. On the psychrometric chart, the intersection of 70°F dry-bulb and 60°F wet-bulb gives RH approximately 55%; following the horizontal line left to the saturation curve gives dew point approximately 53°F.

Interpretation: condensation forms on any surface at or below 53°F. A steel surface at 58°F gives a 5°F margin — application may proceed. A steel surface at 52°F is 1°F below the dew point — coating must not begin.

Surface Temperature Instruments

Surface temperature must be measured on the substrate itself — it cannot be inferred from air temperature, because steel radiatively cools below air temperature at night. Three instruments are recognized in CIP Level 1:

InstrumentMethodTypical Use and Limitations
Magnetic dial thermometerMagnetic base clings to ferrous steel; bimetallic dial reads surface tempQuick field check on steel tanks and structural members; ferrous only; allow 2-3 min to stabilize
Electronic thermistor probeContact probe with digital readout; high accuracyPrecise measurement on any surface; faster response than dial; most common field choice
Infrared (IR) thermometerNon-contact; measures thermal radiationQuick scan of large areas; accuracy depends on correct emissivity setting; bare steel has low emissivity and reads falsely low unless taped or adjusted

Field Procedure Notes

  • Allow dial thermometers at least 2-3 minutes to stabilize before reading.
  • Take surface temperature on the actual area to be coated, not a nearby rail or scaffold.
  • IR readings of bare blasted steel are unreliable without emissivity correction; black tape on the steel gives a known-emissivity target.
  • Record the instrument used — auditors and spec writers may require a specific type.

Exam Traps

  • The wick must be wetted with distilled or deionized water — tap water leaves mineral deposits that skew wet-bulb readings.
  • The sling must be whirled long enough (approximately 90 seconds or until the wet-bulb stabilizes). A few swings give a falsely high wet-bulb reading, inflating calculated RH and dew point.
  • Avoid whirling in direct sunlight or near heat sources — radiant heat inflates the dry-bulb and corrupts the depression.
  • Magnetic dial thermometers only work on ferrous steel; they cannot measure aluminum, galvanized, or non-ferrous substrates.
  • Dew point is the temperature at which condensation begins — it is NOT the same as the wet-bulb temperature (dew point is always between the wet-bulb and dry-bulb when RH is below 100%).
Test Your Knowledge

What two readings does a sling psychrometer directly provide?

A
B
C
D
Test Your Knowledge

On a psychrometric chart, how is the dew point found from a dry-bulb and wet-bulb pair?

A
B
C
D
Test Your Knowledge

In the worked example, a sling psychrometer reads dry-bulb 70°F and wet-bulb 60°F. What is the approximate dew point?

A
B
C
D
Test Your Knowledge

What is a key limitation of magnetic dial thermometers for surface temperature measurement?

A
B
C
D