6.3 Nonmetallic-Sheathed Cable (Type NM) & Underground Feeder (Type UF)

Key Takeaways

  • Type NM cable (Romex®) is permitted in one- and two-family dwellings, multifamily dwellings, and other structures of Type III, IV, and V construction, but is strictly prohibited in commercial garages, theaters, places of assembly over 100 persons, hoistways, and any damp or wet locations per NEC 334.10 and 334.12.
  • Type NM cable must be secured within 12 inches of every box, cabinet, or fitting (or within 8 inches of single-gang nonmetallic boxes without cable clamps per 314.17(C)), and supported at intervals not exceeding 4.5 feet along the run per NEC 334.30.
  • Under NEC 300.4(A)(1), where cables pass through bored holes in wood framing members closer than 1.25 inches (32 mm) from the nearest edge of the stud or joist, they must be protected by a steel plate not less than 1/16 inch (1.6 mm) thick; 300.4(D) applies the same 1.25-inch rule to cables run parallel to framing members.
  • Per NEC 334.80, the allowable ampacity of Type NM cable must correspond to the 60°C temperature column of Table 310.16 (e.g., 14 AWG is 15A, 12 AWG is 20A, 10 AWG is 30A), although the 90°C conductor rating may be utilized as the baseline for ambient and bundling derating.
  • Type UF cable is listed under Article 340 for direct burial in the earth and wet locations; per Table 300.5, it requires a minimum burial cover of 24 inches for general direct burial, 18 inches under residential driveways, and 12 inches for 120V residential branch circuits protected by GFCI and rated 20A or less.
Last updated: September 2026

6.3 Nonmetallic-Sheathed Cable (Type NM) & Underground Feeder (Type UF)

Quick Answer: Nonmetallic-Sheathed Cable (Type NM, commonly known as Romex®) is governed by NEC Article 334 and permitted in one- and two-family dwellings, multifamily dwellings, and other structures of Types III, IV, and V construction. It is strictly prohibited in commercial garages, theaters, hoistways, exposed inside commercial dropped ceilings, and any damp or wet locations. Under NEC 334.30, Type NM must be secured within 12 inches of boxes (8 inches for single-gang plastic boxes without clamps) and supported every 4.5 feet. NEC 300.4 requires 1/16-inch steel nail plates where cables pass through studs closer than 1.25 inches from the framing edge. Crucially, NEC 334.80 caps Type NM ampacity at the 60°C column of Table 310.16, though 90°C ratings may be used for derating. Underground Feeder (Type UF, Article 340) is listed for wet locations and direct burial, requiring 24-inch minimum burial depth (or 12 inches for 120V 20A GFCI-protected residential branch circuits per Table 300.5).

Nonmetallic-sheathed cable assemblies represent the most widespread wiring method in residential electrical construction across the United States. First patented in 1922 under the trade name Romex®, nonmetallic cables offer remarkable installation speed and cost efficiency. However, because nonmetallic cables lack a metallic armor to resist physical penetration, crush damage, and environmental moisture, the NEC imposes strict construction limits, occupancy restrictions, and physical protection rules.


Physical Construction: Type NM vs. Type UF

  • Type NM-B (Article 334): The modern standard is designated NM-B. It incorporates individual copper conductors insulated with 90°C thermoplastic PVC and wrapped in a protective clear nylon jacket (essentially THHN conductors), wrapped in a flame-retardant kraft paper separator, accompanied by an uninsulated bare copper equipment grounding conductor (EGC), and enclosed in an outer moisture-resistant, flame-retardant polyvinyl chloride (PVC) overall sheath. Industry standard color coding of the outer PVC jacket designates wire gauge: White (14 AWG), Yellow (12 AWG), Orange (10 AWG), and Black (8 AWG and larger).
  • Type NMC and NMS: Type NMC is a corrosion-resistant variant with a solid neoprene or PVC inner web, formerly used in dairy barns and damp areas. Type NMS is a hybrid cable containing both power conductors and signaling/network communications conductors.
  • Type UF-B (Article 340): Underground Feeder cable is manufactured with a solid, seamless thermoplastic outer jacket that is molded integrally around each individual conductor and the bare copper equipment grounding conductor without internal air voids or paper liners. This monolithic thermoplastic encapsulation renders Type UF impervious to liquid moisture, soil acid, alkali corrosion, and fungal growth. The outer sheath is specifically listed as sunlight-resistant (UV-resistant).

Uses Permitted and Prohibited for Type NM (NEC 334.10 & 334.12)

One of the most heavily tested areas on the Alabama licensing exam involves the boundary between permissible residential applications and illegal commercial uses:

Uses Permitted (NEC 334.10)

Type NM cable is permitted in:

  1. One-family and two-family dwellings and their attached or detached garages and storage sheds.
  2. Multifamily dwellings permitted to be of Types III, IV, and V construction (combustible wood-frame or masonry exterior with wood interior construction as defined in the International Building Code).
  3. Other structures permitted to be of Types III, IV, and V construction, where cables are concealed within walls, floors, and ceilings that provide a thermal barrier of material that has at least a 15-minute finish rating (such as 1/2-inch gypsum drywall).
  4. In the void spaces of masonry block walls, provided the wall is dry and above grade.

Uses Prohibited (NEC 334.12)

Type NM cable shall NOT be used:

  1. In any dwelling or structure exceeding Types III, IV, and V construction (such as Type I fire-resistive or Type II noncombustible high-rise commercial structures).
  2. Exposed within dropped or suspended lay-in ceilings in other than one- and two-family and multifamily dwellings. (A frequent jobsite violation: running Romex above the 2x4 acoustic tile grid of a commercial office, retail store, or restaurant is illegal!).
  3. In commercial garages having hazardous (classified) locations under Article 511.
  4. In theaters and similar places of assembly designed for 100 or more persons (Article 520).
  5. In motion picture studios, storage battery rooms, hoistways, or embedded in poured concrete or masonry.
  6. In any damp or wet location. This includes exposed outdoor runs, underground conduits, outdoor carports subject to blowing rain, and concrete block walls below grade.

Securing and Supporting Mandates (NEC 334.30)

Proper mechanical support prevents cable sag, terminal strain, and insulation damage caused by vibration or thermal cycling:

  1. Distance to Enclosures: Type NM cable must be secured by listed staples, cable ties, or straps within 12 inches (300 mm) of every box, cabinet, or conduit fitting.
  2. The 8-Inch Single-Gang Box Exception (NEC 314.17(C) Exception): Where nonmetallic single-gang boxes without internal cable clamps are used, the cable must be secured within 8 inches (200 mm) of the box. The cable sheath must extend not less than 1/4 inch (6 mm) past the box clamp into the interior of the enclosure.
  3. Interval Spacing Along Runs: Type NM cable must be secured and supported at intervals not exceeding 4.5 feet (1.4 m) along framing members.
  4. Framing Member Horizontal Passes: Cable run horizontally through bored holes or notches in wooden or metal framing members is considered supported and secured, provided the framing members are spaced not more than 4.5 feet apart.
  5. Unsupported Fish Runs: Type NM cable is permitted to be fished without supports between access points in concealed spaces of existing walls, floors, or ceilings where structural support is impracticable.

Attic and Roof Framing Rules (NEC 334.23 & 320.23)

  • Where run across the top of ceiling joists or across the face of rafters within 7 feet (2.1 m) of floor joists, cables must be protected by substantial guard strips if accessible by a permanent stairway or ladder.
  • Where the attic is accessible only by a crawl hole or scuttle hole without permanent stairs, protection is required only within 6 feet (1.8 m) of the edge of the scuttle hole.

Protection Against Physical Damage: NEC 300.4

When electrical cables are concealed behind drywall or wood paneling, drywall installers and trim carpenters drive fasteners into framing members. NEC 300.4 imposes rigorous defense mechanisms:

+-------------------------------------------------------------------------+
|                   NEC 300.4 WOOD STUD BORING RULES                     |
+-------------------------------------------------------------------------+
|                                                                         |
|   | <--- 1.25" ---> |                   | <--- 1.25" ---> |             |
|   +-----------------+-------------------+-----------------+             |
|   |                 |   BORED HOLE      |                 |             |
|   |   STUD FACE     |   (Cable Safe     |   STUD FACE     |             |
|   |   (Drywall)     |    Centered)      |   (Drywall)     |             |
|   |                 |                   |                 |             |
|   +-----------------+-------------------+-----------------+             |
|                                                                         |
|   RULE: If bored hole is closer than 1.25 inches to EITHER edge,        |
|   a 1/16-inch (1.6 mm) steel nail plate is MANDATORY on that face!      |
+-------------------------------------------------------------------------+
  1. Bored Holes in Wood Framing (NEC 300.4(A)(1)): Holes bored in wood studs, joists, or rafters must have the edge of the hole not less than 1.25 inches (32 mm) from the nearest edge of the wood member. If the hole is bored closer than 1.25 inches, the cable must be protected from penetration by nails and screws by a steel plate not less than 1/16 inch (1.6 mm) thick of appropriate length and width.
  2. Notches in Wood Framing (NEC 300.4(A)(2)): Where framing members are notched, a 1/16-inch steel nail plate must be installed over the notch before drywall installation.
  3. Metal Framing Members (NEC 300.4(B)): Where cables pass through factory- or field-punched holes in metal framing studs, listed bushings or grommets must be securely installed in the opening prior to pulling cable to prevent sharp sheet metal from slicing the cable jacket. If the hole is closer than 1.25 inches to the stud edge, 1/16-inch steel nail plates are also required.

The Crucial 60°C Ampacity Limitation (NEC 334.80)

One of the most vital technical mandates for the Journeyman exam is the ampacity rating of Type NM cable under NEC 334.80:

The 60°C Rule: The allowable ampacity of Type NM, NMC, and NMS cable shall be in accordance with the 60°C (140°F) conductor temperature rating in Table 310.16.

Even though modern NM-B cable is manufactured with 90°C rated conductors, its final usable ampacity is legally restricted to the 60°C column:

  • 14 AWG NM-B: 15 Amperes (60°C column)
  • 12 AWG NM-B: 20 Amperes (60°C column)
  • 10 AWG NM-B: 30 Amperes (60°C column)
  • 8 AWG NM-B: 40 Amperes (60°C column — Notice: 8 AWG THHN is 50A at 75°C and 55A at 90°C, but 8 AWG NM-B is capped at 40A!)
  • 6 AWG NM-B: 55 Amperes (60°C column — Cannot be protected by a 60A breaker if the load exceeds 55A!)

The Derating Baseline Exception

NEC 334.80 contains a powerful exception for ampacity adjustment: The 90°C conductor rating shall be permitted to be used for ampacity adjustment and correction calculations, provided the final calculated ampacity does not exceed the 60°C value. For example, if three 12 AWG NM cables (6 current-carrying conductors) pass through a wood framing hole sealed with expanding thermal foam, bundling derating applies ($30\text{ A base at 90°C} \times 0.80 = 24\text{ A}$). Since 24A is greater than the 60°C limit of 20A, the cable retains its full 20A rating!


Type UF Cable Installations and Minimum Burial Depths (NEC Article 340 & Table 300.5)

Type UF cable is designed specifically for direct burial in the earth without conduit. Like Type NM, Type UF ampacity is restricted to the 60°C column of Table 310.16 under NEC 340.80.

Minimum Cover Requirements: NEC Table 300.5

When burying Type UF cable underground, the depth of burial (measured as "cover" from the top surface of the cable to finished grade) is governed by NEC Table 300.5:

Location of Wiring InstallationColumn 1: Direct Burial Cables (Type UF)Column 3: Nonmetallic Raceways (PVC)Column 4: Residential 120V 20A GFCI Circuits
General earth / soil under turf24 inches (600 mm)18 inches (450 mm)12 inches (300 mm)
In a trench below 2 inches of concrete or equivalent18 inches (450 mm)12 inches (300 mm)6 inches (150 mm)
Under residential driveways and parking18 inches (450 mm)18 inches (450 mm)12 inches (300 mm)
Under public commercial roads and streets24 inches (600 mm)24 inches (600 mm)24 inches (600 mm)

Crucial Exam Note on the GFCI Exception: Column 4 of Table 300.5 provides a major reduction for residential 120-volt branch circuits rated 20 amperes or less and provided with GFCI protection on the supply side. Under this rule, Type UF cable buried to supply outdoor garden lighting or a post lamp requires a minimum burial depth of only 12 inches (300 mm) instead of the standard 24 inches.

Test Your Knowledge

What is the maximum spacing between support straps along runs of Nonmetallic-Sheathed Cable (Type NM) under NEC 334.30?

A
B
C
D
Test Your Knowledge

In which of the following building locations is the installation of Type NM (nonmetallic-sheathed) cable strictly prohibited by NEC 334.12?

A
B
C
D
Test Your Knowledge

Under NEC 300.4(A)(1), what physical protection is required where Type NM cable passes through bored holes in wood framing members closer than 1.25 inches from the edge of the stud?

A
B
C
D
Test Your Knowledge

What is the minimum underground burial depth under Table 300.5 for a 120-volt, 20-ampere GFCI-protected residential branch circuit wired with direct-buried Type UF cable under a residential lawn?

A
B
C
D