Hydraulic Principles
30%of exam
Assemblies Equipment
30%of exam
Field Test Procedures
20%of exam
Cross-Connection Control
10%of exam
ContainmentIsolationSurveysAir GapHazard Rating
Field Test Equipment
5%of exam
Differential GaugeHosesTest CocksBleedingCalibration
Codes Regulations
5%of exam
SDWAPurveyorRecordsReportingRecertification
Quick Facts
- Exam
- Backflow Tester
- Bodies
- ABPA / ASSE
- Written
- 100 questions
- Time
- 3 hours
- Pass
- 70%
- Practical
- Hands-on testing
- Assemblies
- RP DC PVB SVB
- Validity
- 3 years
- Gauge
- Annual calibration
Two Backflows
Pressure pushes; siphon pulls.
BackpressureBacksiphonage
Backpressure vs Backsiphonage
Backpressure
- Downstream pressure higher
- Pumps/boilers cause
Backsiphonage
- Supply pressure drops
- Vacuum draws back
Pressure direction decides
Selection Picker
- Health hazard→RP or air gap
- Low hazard→DC
- Backpressure exists→RP/DC(Not PVB)
- Backsiphonage only→PVB/SVB
- Maximum protection→Air gap
- Fixture protection→Isolation
Hydraulics Basics
- Backflow
- Reverse flow
- Backpressure
- Downstream pressure higher
- Backsiphonage
- Supply pressure drops
- Static pressure
- No-flow pressure
- Dynamic pressure
- Flowing pressure
- Pressure loss
- Drop across device
RP Parts
Check, zone, relief, check.
Check 1ZoneReliefCheck 2
RP vs DC
RP
- Relief valve present
- High hazard use
DC
- No relief valve
- Low hazard use
Health hazard needs RP
Failure Picker
- Reading unstable→Bleed hoses
- Check leaks→Clean seat
- Relief won't open→Inspect diaphragm
- Shutoff leaks→Repair shutoff
- Gauge suspect→Check calibration
- Wrong assembly→Hazard review
RP Assembly
- RP
- Reduced pressure principle
- Check 1
- Creates zone pressure
- Check 2
- Prevents outlet return
- Relief valve
- Vents failed zone
- Zone
- Reduced pressure area
- Use
- High hazard protection
PVB vs SVB
PVB
- Vacuum breaker
- May spill water
SVB
- Spill-resistant design
- Vacuum breaker
Both backsiphonage only
DC Assembly
- DC
- Double check assembly
- Check 1
- First closure point
- Check 2
- Second closure point
- Shutoff 1
- Inlet isolation
- Shutoff 2
- Outlet isolation
- Use
- Low hazard protection
Device vs Assembly
Device
- Often non-testable
- No test cocks
Assembly
- Field testable
- Has shutoffs/cocks
Testability matters
PVB SVB
- PVB
- Pressure vacuum breaker
- SVB
- Spill-resistant breaker
- Air inlet
- Opens on vacuum
- Check valve
- Holds downstream water
- Backpressure
- Not protected
- Elevation
- Install above outlets
Troubleshooting
- Debris
- Fouls check seat
- Scale
- Restricts movement
- Spring
- Weak closure force
- Diaphragm
- Relief valve failure
- Leaky shutoff
- Invalid test
- Air in hose
- Unstable reading
Test Start
Identify, isolate, connect, bleed.
IdentifyIsolateConnectBleed
Test Picker
- Before connection→Gauge zero
- Hoses attached→Bleed air
- RP assembly→Relief plus checks
- DC assembly→Two checks
- PVB/SVB→Air inlet/check
- Any failure→Repair retest
Test Setup
- Permission
- Notify responsible party
- Flow direction
- Confirm before testing
- Test cocks
- Open slowly
- Bleed hoses
- Remove trapped air
- Gauge zero
- Check before readings
- Record
- Document findings
RP Test Logic
- Relief opening
- Must open
- Zone pressure
- Lower than supply
- Check 1
- Holds differential
- Check 2
- Holds backpressure
- Shutoff 2
- Must be tight
- Fail
- Repair then retest
DC PVB Tests
- DC check 1
- Must hold tight
- DC check 2
- Must hold tight
- DC shutoff
- No leakage
- PVB check
- Holds pressure
- Air inlet
- Opens to atmosphere
- SVB spill
- Minimized discharge
Containment vs Isolation
Containment
- Service entrance
- Protects public system
Isolation
- Individual fixture
- Protects internal users
Location decides
Hazard Control
- Cross-connection
- Potable/nonpotable link
- Pollution
- Aesthetic quality hazard
- Contamination
- Health hazard
- Containment
- Service protection
- Isolation
- Fixture protection
- Air gap
- Physical separation
Pollution vs Contamination
Pollution
- Aesthetic concern
- Non-health hazard
Contamination
- Health concern
- Toxic/pathogenic hazard
Health risk escalates
Test Kit
- Differential gauge
- Measures pressure difference
- High hose
- Connect upstream side
- Low hose
- Connect downstream side
- Bypass hose
- Equalizes as needed
- Calibration
- Check yearly
- Needle valves
- Control gauge flow
Report Basics
Assembly, readings, result, signature.
AssemblyReadingsResultSignature
Records Regs
- SDWA
- Drinking water law
- Purveyor
- Water supplier
- Authority
- Local program rules
- Report
- Submit test results
- Serial number
- Assembly identifier
- Recertify
- Renew credential
Common Traps
PVB Trap
Backsiphonage only ≠ Backpressure protection
Hazard Trap
Pollution ≠ Contamination
Gauge Trap
Air in hose ≠ True pressure
Shutoff Trap
Leaky shutoff ≠ Valid test
RP Trap
Relief valve opens ≠ Relief valve closed
Location Trap
Containment ≠ Isolation
Last Minute
- 1.Name two backflow types
- 2.Classify hazard first
- 3.Match assembly to hazard
- 4.Confirm flow direction
- 5.Bleed gauge hoses
- 6.Test shutoffs matter
- 7.RP relief must open
- 8.PVB excludes backpressure
- 9.Record serial number
- 10.Repair then retest
Same family resources
Explore More ASSE Plumbing Certifications
Continue into nearby exams from the same family. Each card keeps practice questions, study guides, flashcards, videos, and articles in one place.
More From This Family
Videos and articles for deeper review.
